This application occurs
when venting through a
roof. Installation kits for
various roof pitches are
available from your Napo-
leon dealer. See Accesso-
ries to order the specific
kit required.

1. 

Determine the air terminal location, cut and frame 10

inch openings in the ceiling and the roof to provide the
minimum 1 inch clearance between the fireplace pipe /
liner and any combustible material. Try to center the ex-
haust pipe location midway between two joist to prevent
having to cut them. Use a plumb bob to line up the center of
the openings.  DO NOT FILL THIS SPACE WITH ANY TYPE
OF MATERIAL. A vent pipe shield will prevent any materials
such as insulation, from filling up the 1" air space around
the pipe. Nail headers
between the joist for
extra support.

2. 

Apply a bead of

caulking (not sup-
plied) to the frame-
work or to the Wolf
Steel vent pipe shield
plate or equivalent (in the case of a finished ceiling), and
secure over the opening in the ceiling. 

 

 A firestop must be

placed on the bottom of each framed opening in a roof or
ceiling that the venting system passes through. 

 

Apply a

bead of caulking all around and place a firestop spacer
over the vent shield to restrict cold air from being drawn
into the room or around the fireplace. Ensure that both
spacer and shield maintain the required clearance to
combustibles. Once the vent pipe / liner is installed in its
final position, apply sealant between the pipe / liner and
the firestop spacer.

FIGURE 16

This application occurs when vent
ing through an exterior wall. Having
determined the air terminal location,
cut and frame a hole in an exterior
wall with a minimum opening as
required. 

See Note above. 

(As an

alternative to framing, a vent pipe
shield may be installed, ensuring
a 1" clearance to combustibles.

1. 

Mark and cut the vent pipe shield to the determined

depth of the combustible wall. Apply a bead of caulking
(not supplied) to the framework or to the shield plate (in the
case of a finished wall) and secure the shield through the
opening to the interior wall. 

The final location of the vent

pipe shield should maintain the required clearance to the
8" vent pipe / liner. (See note above). Do not fill this cavity
with any type of material.  

Apply a bead of caulking all around

and place a firestop spacer over the vent shield to restrict
cold air from being drawn into the room or around the fire-
place. Ensure that both spacer and shield maintain the
required clearance to combustibles. Once the vent
pipe / liner is installed in its final position, apply sealant
between the pipe / liner and the firestop spacer.

FIGURE 15

FIGURE 14

OR

FOR SAFE AND PROPER OPERATION OF THE FIREPLACE,
FOLLOW THE VENTING INSTRUCTIONS EXACTLY.

NOTE: Only a clearance to combustibles of 2" at the
top of the vent pipe is required and 1" at the bottom
and sides.

HORIZONTAL INSTALLATION

VERTICAL INSTALLATION

INSTALLATION

WALL AND CEILING PROTECTION

FIGURE 17

Summary of Contents for B36DFP

Page 1: ...1 W415 0484 A 07 23 06 W415 0484 A 07 26 06...

Page 2: ...WHAT TO DO IF YOU SMELL GAS WARNINGS SAFETY PRECAUTIONS...

Page 3: ...rt of the control system and any gas control which has been under water Do not operate the fireplace with the glass door removed cracked or broken Replacement of the glass should be done by a licensed...

Page 4: ...are covered and eting and pilot assembly are covered and eting and pilot assembly are covered and eting and pilot assembly are covered and NAPOLEON NAPOLEON NAPOLEON NAPOLEON NAPOLEON will provide re...

Page 5: ...tates FOR YOUR SATISFACTION THIS FIREPLACE HAS BEEN TEST FIRED TO ASSURE ITS OPERATION AND QUALITY Maximum input is 23 000 BTU hr for natural gas and propane When the fireplace is installed at elevati...

Page 6: ...ce performance keep the vent length and number of elbows to a minimum The air terminal must remain unobstructed at all times Examine the air terminal at least once a year to verify that it is unobstru...

Page 7: ...tly closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance to unventilated soffit Cleara...

Page 8: ...m of 12 inches above grade The maximum allow able vent length depends on the fireplace as illustrated FIGURES3a c FIGURE4 TYPICAL VENT INSTALLATIONS SPECIAL VENT INSTALLATIONS NOTE When terminating ve...

Page 9: ...ntal run Horizontal run verti cal rise to maximum of 40 feet Vertical rise is less than horizontal run Horizontal run verti cal rise to m a x i m u m of 24 75 feet 4 2 times the vertical rise equal to...

Page 10: ...offset 135 in feet VT combined vertical vent lengths in feet feet inches 1 0 03 0 5 15 0 45 6 0 30 0 9 11 0 45 1 35 16 0 90 2 7 32 0 the first 45 and 90 offset has a zero value and is shown in the fo...

Page 11: ...ET HT when HT VT Simple venting configuration only one 45 and 90 elbow Example 2 V1 4ft V2 1 5ft VT V1 V2 4 ft 1 5 ft 5 5 ft H1 2ft H2 1ft H3 1ft H4 1 5ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 one 45...

Page 12: ...s are met this vent configuration is ac ceptable when HT VT Simple venting configurations FIGURE9 REQUIRED VERTICAL RISE IN FEET VT HORIZONTAL VENT RUN PLUS OFFSETS IN FEET HT FIGURE10 For vent config...

Page 13: ...eptable Formula 2 HT VT 40 feet 15 9 40 Since only formula 2 is met this vent configuration is unac ceptable and a new fireplace location or vent configuration will need to be established to satisfy b...

Page 14: ...nce the vent pipe liner is installed in its final position apply sealant between the pipe liner and the firestop spacer FIGURE16 This application occurs when vent ing through an exterior wall Having d...

Page 15: ...runs Use noncombustible strapping to maintain the minimum 1 clearance to combustibles FIGURE19 HORIZONTAL AIR TERMINAL INSTALLATION VERTICAL AIR TERMINAL INSTALLATION 4 Insert the liners through the...

Page 16: ...use open flame Do not connect either the wall switch thermostat or gas valve to electricity 110 volts Purge all gas lines with the glass door of the fireplace removed Assure that a continuous gas flow...

Page 17: ...for use with other gases unless a certified kit is used Conversion Kits The mobile home appliance is field convertible between Natural Gas NG and Propane LP To convert from Natural Gas to Propane ord...

Page 18: ...32b 2 To determine the final location of the nailing tab you must first determine the thickness of your finishing mate rial i e drywall This will determine the dimension from the front edge of the cor...

Page 19: ...g Secure using a screw through the centre slot LOWER LOUVRES Insert the hinge clips into the slots located at the bottom left and right corners of the unit To remove the louvres pull the back tabs of...

Page 20: ...ll of the burner area in front of the small logs 2 3 Care should be taken to shred the embers into thin small irregular pieces as only the exposed edges of the fibre hairs will glow The ember material...

Page 21: ...ireplace base or the firebox Attach the connectors from the black and white wires to the thermodisc and secure the thermodisc bracket to the unit at the bottom left of the unit using the ground screw...

Page 22: ...Steel Napoleon dealer With the thermostatic sensor option the fan when turned on becomes thermally activated and will automatically run approximately 15 30 minutes after the fireplace has been lit and...

Page 23: ...smell gas including near the floor Stop Follow B in the above safety information on this label If you don t smell gas go the next step 5 Turn gas knob counter clockwise to pilot 6 Depress slightly and...

Page 24: ...yellow flame but can lead to carboning Opening the air shutter will cause a more blue flame but can cause flame lifting from the burner ports The flame may not appear yellow immediately allow 15 to 30...

Page 25: ...KIT ARCHED BLACK 55 DK36 AG DOOR KIT ARCHED GOLD PLATED 56 DK36 W DOOR KIT WEBBED BLACK 56 DK36 WG DOOR KIT WEBBED GOLD PLATED 57 GA 566 HOT AIR KIT 58 GA 72 HOT AIR EXHAUST KIT 59 GA 70 EXTENSION KI...

Page 26: ...ouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd AT TE NT ION CH AU D CA UT ION HO T 5 4 6 3 22 46 49 50 53 52 51 38 21 54 57 55 28 23 5...

Page 27: ...an interlock device which will not allow the pilot burner to be lit until the ther mocouple has cooled Allow ap proximately 60 seconds for the thermocouple to cool System is not correctly purged purge...

Page 28: ...aned off regularly the glass may become permanently marked Main burner flame is a blue lazy transparent flame Blockage in vent remove blockage In extremely cold conditions ice buildup may occur on the...

Page 29: ...29 W415 0484 A 07 23 06 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Page 30: ...30 W415 0484 A 07 26 06 NOTES...

Reviews: