Napoleon B36DFP Installation And Operation Instructions Manual Download Page 16

16

W415-0484 / A / 07.26.06

Vertical terminations may display a very active flame. As
this appearance is not desirable, the vent exit must be
restricted using restrictor plate, W500-0205.  This reduces
the velocity of the exhaust gases, slowing down the flame
pattern and creating a more traditional appearance.

Remove the two screws on either side of the exhaust collar
inside the firebox. Install the plate as shown. The plate is
adjustable depending on the required restriction. Replace
the screws.

Proceed once the vent installation is complete.

1.

 Move the fireplace into position and secure using the

nailing tabs and/or secure to the floor through the ¼"diam-
eter holes located at either end of the base.

2. 

Route a 3/8" N.P.T. black iron gas line, 1/2" type-L cop-

per tubing or equivalent to the fireplace.

3. 

For ease of accessibility, an optional remote wall switch

or millivolt thermostat may be installed in a convenient  lo-
cation. Route 2-strand (solid core) millivolt wire through
the electrical hole located at the bottom left side of the unit.
The recommended maximum lead length depends on wire
size:

WIRE SIZE

MAX. LENGTH

14 gauge

100 feet

16  gauge

  60 feet

18  gauge

  40 feet

Attach the two leads to terminals 1 and 3 located on the
gas valve.

4. 

Install rigid black pipe, 1/2" type-L copper tubing or, if

local codes permit, a 3/8" flex connector and shutoff  valve
to the gas line  and the fireplace gas valve.

Seal and tighten securely. An adapter fitting is required

between the gas valve and the copper tubing or flex con-
nector. 

Do not kink flex connector.

5. 

Check for gas leaks by brushing on a soap and water

solution. 

Do not use open flame.

Do not connect either the wall switch, thermostat or gas
valve to electricity (110 volts).
Purge all gas lines with the glass door of the fireplace
removed. Assure that a continuous gas flow is at the burner
before re-installing the door.

FIGURE 26

FIGURE 25

GAS INSTALLATION

RESTRICTING VERTICAL VENTS

FIGURE 23

FIREPLACE VENT CONNECTION

RESTRICTOR PLATE

TOP OF THE

FIREBOX

FLUE COLLAR

FIGURE 24

STORM 

COLLAR

FLASHING

CAULKING

WEATHER

    SEALANT

2”

AIR INLET

BASE

5. 

Remove nails from the shingles, above and to the sides

of the chimney. Place the flashing over the air terminal and
slide it underneath the sides and upper edge of the
shingles. Ensure that the air terminal is properly centred
within the flashing, giving a 3/4" margin all around. Fasten
to the roof. Do 

not

 nail through the lower portion of the

flashing. Make weather-tight by sealing with caulking.
Where possible, cover the sides and top edges of the
flashing with roofing material.

6. 

Apply a heavy bead of weatherproof caulking 2 inches

above the flashing. Slide the storm collar around the air
terminal and down to the
caulking. Tighten to ensure
that a weather-tight seal
between the air terminal
and the collar is achieved.
Attach the other storm
collar centred between the
air intake vent pipe and the
air exhaust slots onto the
air terminal. Tighten
securely. Attach the vertical
rain cap.

Spacers are attached to the exhaust liner at
predetermined intervals to maintain a 1-1/4" air gap to
the air intake vent pipe. These spacers must not be
removed.

1. 

Install the 5 inch diameter aluminium flexible liner to

the fireplace. Secure with 3 screws and flat washers. Seal
the joint and screw holes using the high temperature seal-
ant Mill Pac.

2. 

Install the 8 inch diameter aluminium flexible liner to

the fireplace. Attach and seal the joints.

FIGURE 22

Summary of Contents for B36DFP

Page 1: ...1 W415 0484 A 07 23 06 W415 0484 A 07 26 06...

Page 2: ...WHAT TO DO IF YOU SMELL GAS WARNINGS SAFETY PRECAUTIONS...

Page 3: ...rt of the control system and any gas control which has been under water Do not operate the fireplace with the glass door removed cracked or broken Replacement of the glass should be done by a licensed...

Page 4: ...are covered and eting and pilot assembly are covered and eting and pilot assembly are covered and eting and pilot assembly are covered and NAPOLEON NAPOLEON NAPOLEON NAPOLEON NAPOLEON will provide re...

Page 5: ...tates FOR YOUR SATISFACTION THIS FIREPLACE HAS BEEN TEST FIRED TO ASSURE ITS OPERATION AND QUALITY Maximum input is 23 000 BTU hr for natural gas and propane When the fireplace is installed at elevati...

Page 6: ...ce performance keep the vent length and number of elbows to a minimum The air terminal must remain unobstructed at all times Examine the air terminal at least once a year to verify that it is unobstru...

Page 7: ...tly closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance to unventilated soffit Cleara...

Page 8: ...m of 12 inches above grade The maximum allow able vent length depends on the fireplace as illustrated FIGURES3a c FIGURE4 TYPICAL VENT INSTALLATIONS SPECIAL VENT INSTALLATIONS NOTE When terminating ve...

Page 9: ...ntal run Horizontal run verti cal rise to maximum of 40 feet Vertical rise is less than horizontal run Horizontal run verti cal rise to m a x i m u m of 24 75 feet 4 2 times the vertical rise equal to...

Page 10: ...offset 135 in feet VT combined vertical vent lengths in feet feet inches 1 0 03 0 5 15 0 45 6 0 30 0 9 11 0 45 1 35 16 0 90 2 7 32 0 the first 45 and 90 offset has a zero value and is shown in the fo...

Page 11: ...ET HT when HT VT Simple venting configuration only one 45 and 90 elbow Example 2 V1 4ft V2 1 5ft VT V1 V2 4 ft 1 5 ft 5 5 ft H1 2ft H2 1ft H3 1ft H4 1 5ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 one 45...

Page 12: ...s are met this vent configuration is ac ceptable when HT VT Simple venting configurations FIGURE9 REQUIRED VERTICAL RISE IN FEET VT HORIZONTAL VENT RUN PLUS OFFSETS IN FEET HT FIGURE10 For vent config...

Page 13: ...eptable Formula 2 HT VT 40 feet 15 9 40 Since only formula 2 is met this vent configuration is unac ceptable and a new fireplace location or vent configuration will need to be established to satisfy b...

Page 14: ...nce the vent pipe liner is installed in its final position apply sealant between the pipe liner and the firestop spacer FIGURE16 This application occurs when vent ing through an exterior wall Having d...

Page 15: ...runs Use noncombustible strapping to maintain the minimum 1 clearance to combustibles FIGURE19 HORIZONTAL AIR TERMINAL INSTALLATION VERTICAL AIR TERMINAL INSTALLATION 4 Insert the liners through the...

Page 16: ...use open flame Do not connect either the wall switch thermostat or gas valve to electricity 110 volts Purge all gas lines with the glass door of the fireplace removed Assure that a continuous gas flow...

Page 17: ...for use with other gases unless a certified kit is used Conversion Kits The mobile home appliance is field convertible between Natural Gas NG and Propane LP To convert from Natural Gas to Propane ord...

Page 18: ...32b 2 To determine the final location of the nailing tab you must first determine the thickness of your finishing mate rial i e drywall This will determine the dimension from the front edge of the cor...

Page 19: ...g Secure using a screw through the centre slot LOWER LOUVRES Insert the hinge clips into the slots located at the bottom left and right corners of the unit To remove the louvres pull the back tabs of...

Page 20: ...ll of the burner area in front of the small logs 2 3 Care should be taken to shred the embers into thin small irregular pieces as only the exposed edges of the fibre hairs will glow The ember material...

Page 21: ...ireplace base or the firebox Attach the connectors from the black and white wires to the thermodisc and secure the thermodisc bracket to the unit at the bottom left of the unit using the ground screw...

Page 22: ...Steel Napoleon dealer With the thermostatic sensor option the fan when turned on becomes thermally activated and will automatically run approximately 15 30 minutes after the fireplace has been lit and...

Page 23: ...smell gas including near the floor Stop Follow B in the above safety information on this label If you don t smell gas go the next step 5 Turn gas knob counter clockwise to pilot 6 Depress slightly and...

Page 24: ...yellow flame but can lead to carboning Opening the air shutter will cause a more blue flame but can cause flame lifting from the burner ports The flame may not appear yellow immediately allow 15 to 30...

Page 25: ...KIT ARCHED BLACK 55 DK36 AG DOOR KIT ARCHED GOLD PLATED 56 DK36 W DOOR KIT WEBBED BLACK 56 DK36 WG DOOR KIT WEBBED GOLD PLATED 57 GA 566 HOT AIR KIT 58 GA 72 HOT AIR EXHAUST KIT 59 GA 70 EXTENSION KI...

Page 26: ...ouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd AT TE NT ION CH AU D CA UT ION HO T 5 4 6 3 22 46 49 50 53 52 51 38 21 54 57 55 28 23 5...

Page 27: ...an interlock device which will not allow the pilot burner to be lit until the ther mocouple has cooled Allow ap proximately 60 seconds for the thermocouple to cool System is not correctly purged purge...

Page 28: ...aned off regularly the glass may become permanently marked Main burner flame is a blue lazy transparent flame Blockage in vent remove blockage In extremely cold conditions ice buildup may occur on the...

Page 29: ...29 W415 0484 A 07 23 06 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Page 30: ...30 W415 0484 A 07 26 06 NOTES...

Reviews: