NAPCO Gemini C-Series Control Panel Programming Instructions--Volume 1 

Page 10 

Programming Instructions, Volume 1 

side of Quickloader, the "

ERROR CHECK REQ'D

" warning automatically appears at the keypad to warn of a possible 

panel/Quickloader mismatch.  To select "

ENABLE PROGRAMMING

" at any unlocked GEMC-FK1 Fire keypad, simply 

press 

MENU

 to enter and press 

NEXT

 to scroll through the menu selections until "

ENABLE PROGRAMMING

" appears.  

See the "

FUNCTION MENU

" section further in this manual for more details regarding the Function menu. 

 

REMOTE DOWNLOADING RULES (CONT'D) 

 

Local Connection 

Remote (Telco and TCP/IP) with no one on site to unlock 

the keypad and "Enable Programming" 

Remote (Telco and TCP/IP) with someone on site to 

unlock the keypad and "Enable Programming" 

Full Down-

load 



Error check will be performed before the operation;  



if error(s) are found and user decides to continue, the 

"

ERROR CHECK REQ'D

" will appear on keypad.  



if error(s) are not found, the "

ERROR CHECK 

REQ'D

" will clear.  



Unrestricted Burg or Fire changes permitted  



Account will be Locked after operation completes 



Error check will be performed before the operation;  



if error(s) are found, the download attempt will termi-

nate.  



if error(s) are not found, the "

ERROR CHECK 

REQ'D

" will clear. 



Burg changes allowed 



Fire changes disallowed 



Will check to ensure panel and Quickloader match 



Account will be Locked after operation completes 



Error check will be performed before the operation;  



if error(s) are found and user decides to continue, the 

"

ERROR CHECK REQ'D

" will appear on keypad.  



if error(s) are not found, the "

ERROR CHECK 

REQ'D

" will clear. 



Burg changes allowed 



Fire changes allowed 



Account will be Locked after operation completes 

Partial 

Download 



Unrestricted Burg or Fire changes permitted  



Error check will be performed before the operation; if 

errors are found and user decides to continue, the 

"

ERROR CHECK REQ'D

" will appear on keypad.   



Burg changes allowed 



Fire changes disallowed 



Will check to ensure panel and Quickloader match 



Error check will be performed before the operation; if 

errors are found, the download attempt will terminate.   



Unrestricted Burg or Fire changes permitted  



Error check will be performed before the operation; if 

errors are found and user decides to continue, the 

"

ERROR CHECK REQ'D

" will appear on keypad.   

Full Upload 



Unrestricted Burg or Fire changes permitted  



Account will be Locked after operation completes 



No restrictions to upload 



Account will be Locked after operation completes 



No restrictions to upload 



Account will be Locked after operation completes 

Partial 

Upload 



Unrestricted Burg or Fire changes permitted  



No restrictions to upload 



No restrictions to upload 

Smart 

Download 



Error check will be performed before the operation;  



if error(s) are found and user decides to continue, the 

"

ERROR CHECK REQ'D

" will appear on keypad.  



if error(s) are not found, the "

ERROR CHECK 

REQ'D

" will clear. 



Unrestricted Burg or Fire changes permitted  



Account will be Locked after operation completes 



Error check will be performed before the operation;  



if error(s) are found, the download attempt will termi-

nate.  



if error(s) are not found, the "

ERROR CHECK 

REQ'D

" will clear. 



Burg changes allowed 



Fire changes disallowed 



Will check to ensure panel and Quickloader match 



Account will be Locked after operation completes 



Error check will be performed before the operation;  



if error(s) are found and user decides to continue, the 

"

ERROR CHECK REQ'D

" will appear on keypad.  



if error(s) are not found, the "

ERROR CHECK 

REQ'D

" will clear. 



Burg changes allowed 



Fire changes allowed 



Account will be Locked after operation completes 

Smart 

Upload 



Unrestricted Burg or Fire changes permitted  



Account will be Locked after operation completes 



No restrictions to upload 



Account will be Locked after operation completes 



No restrictions to upload 



Account will be Locked after operation completes 

Verify 



No restrictions  



No restrictions  



No restrictions  

Event Log 



No restrictions  



No restrictions  



No restrictions  

Attempt to 

Clear Error 

Check Req'd 

Trouble 



Error check must find no errors, the Quickloader account 

must not be modified and the original account program-

ming must match the panel programming.  If errors are 

found, the operation will be aborted; if mismatch is found, 

the Account and Panel Mismatch dialog will appear. 



Error check must find no errors, the Quickloader account 

must not be modified and the original account program-

ming must match the panel programming.  If errors are 

found, the operation will be aborted; if mismatch is found, 

the Account and Panel Mismatch dialog will appear. 



Error check must find no errors, the Quickloader account 

must not be modified and the original account program-

ming must match the panel programming.  If errors are 

found, the operation will be aborted; if mismatch is found, 

the Account and Panel Mismatch dialog will appear. 

(Telco) 

Callback 

Establish 

Connection 



Not Applicable 



Will check to ensure panel and Quickloader match, if a 

mismatch, the Account and Panel Mismatch dialog will 

appear. 



No restrictions  

Keypad 

Establish 

Connection 



Not Applicable 



Will check to ensure panel and Quickloader match, if a 

mismatch, the Account and Panel Mismatch dialog will 

appear. 



No restrictions  

One Step 

Download 



Not Applicable 



Error check will be performed before the operation;  



if error(s) are found, the download attempt will termi-

nate.   



if error(s) are not found, the "

ERROR CHECK 

REQ'D

" will clear. 



Burg changes allowed 



Fire changes disallowed 



Will check to ensure panel and Quickloader match, 

operation will abort if mismatch occurs. 



Account will be Locked after operation completes 



Burg changes allowed 



Fire changes allowed 



Account will be Locked after operation completes 

Quick Reference Table

 

Summary of Contents for GEMINI GEMC-255

Page 1: ...ini C Series Control Panels with the GEMC FK1 Fire Keypad or the GEMC BK1 Burglary Keypad for Burglary Only systems KEYPAD PROGRAMMING INSTRUCTIONS VOLUME 1 Publicly traded on NASDAQ Symbol NSSC WIREL...

Page 2: ...age 92 and updated indexes Added Keypad 1 Always Unlocked for User Functions and All Keypads Unlocked for Silence Reset and Supp to pages 13 17 and 92 and updated indexes Added Unattended Download Mod...

Page 3: ...onfiguration Mode 24 GEMC BK1 Keypad Configuration Mode 25 Easy Menu Driven Program Mode 27 37 Easy Menu Programming Worksheets 38 50 Direct Address Program Mode 51 Address Mode Displays 51 Programmin...

Page 4: ...l PCD Windows Quickloader version 6 0 introduces a new concept that applies to all Commercial Fire related Quickloader accounts A Locked or Unlocked account When a Quickloader account is Unlocked all...

Page 5: ...current Quickloader account will Unlock and all Fire related fields will display as clear non red to allow changes To lock an Unlocked account you must simply perform an operation that will result in...

Page 6: ...control panel programming If they match the new changes are downloaded to the panel if they differ selected pan el programming areas are first uploaded into Quickloader then Quickloader downloads the...

Page 7: ...ce of the account and panel programming because the dealer is by definition physically located on site and therefore restrictions to all local download related operations are both unnecessary and unde...

Page 8: ...ng any action In summary for every download operation Quickloader will attempt to check if the account and panel program are identical If a mismatch is found Quickloader will warn of the mismatch with...

Page 9: ...trouble is by using Quickloader There are several ways to do this in Quickloader One way to remove this ERROR CHECK REQ D keypad trouble is by immediately correcting all errors in the Quick loader ac...

Page 10: ...error s are found and user decides to continue the ERROR CHECK REQ D will appear on keypad if error s are not found the ERROR CHECK REQ D will clear Unrestricted Burg or Fire changes permitted Accoun...

Page 11: ...t after approximately 5 minutes of inactivity at the keypad the keypad will automatically re lock In addition the 5 minute keypad lock countdown and the 30 minute download window countdown are timed i...

Page 12: ...pro grammed tested and placed in operation that keypad programming is not to be used and any changes to the programming be made only using PCD Windows Quickloader Burg Only Systems To enable GEMC BK1...

Page 13: ...must display SYSTEM NORMAL before initiating test In addition call central station before initiating test To initiate system test s Unlock keypad press MENU until DO FIRE DRILL displays Press YES or E...

Page 14: ...ditions to display clearly with flashing icons ADVANCED MENU FUNCTIONS LOCK KEYPAD Immediately locks keypad against affecting any system operation DISPLAY FIRE LOG For Fire Chief serviceman use See OI...

Page 15: ...etermine the part of the system that was affected view events in the Fire log etc Anoth er example of a person in possession of a Fire User Code is the principal of a school who is required to initiat...

Page 16: ...Also see PCI2000 3000 Installation Instructions WI443 FUNCTION MODE WITH A COMPUTER Start by establishing a Telco connection between the computer operator and the system During this proce dure voice c...

Page 17: ...etermine the part of the system that was affected view events in the Fire log etc Note Some systems may use a key switch mounted adjacent to the keypad in place of a code After approximately 5 minutes...

Page 18: ...ewing selected zone will un disable the displayed zone OUTPUT DIRECTORY Displays a listing of the motherboard outputs and up to 40 external output relays and NAC boards in the system Press NEXT and PR...

Page 19: ...d from the system using the keypad instead simply change the old code to a different code using the directions above Change an existing Fire User Code Using PCD Windows Quickloader download software F...

Page 20: ...instructs each device to use its pre existing configuration FULL FSLC INITIALIZATION Use this selection when you wish to re establish a starting condition for all Fire SLC devices in the system withou...

Page 21: ...tiate dialing of the displayed number the phone will appear to be disconnected while dialing but will return to normal after a few sec onds Display System Troubles Displays 1 or 2 digit error code alo...

Page 22: ...his function Displays most recent system events Line 1 displays event and date line 2 displays time and other pertinent information where necessary depending upon event To check previous system events...

Page 23: ...sure the new code entered in step 3 is correct re enter new code then press ENTER Erase an existing Burg User Code Burg User Codes cannot be erased from the system using the keypad instead simply chan...

Page 24: ...w and in the following pages CONFIGURING EACH KEYPAD Each GEMC FK1 keypad can be configured for a keypad tactile beep and b keypad address Be aware that when in Keypad Configuration Mode the Fire alar...

Page 25: ...eypads may be intermixed but require different configuration procedures as described in the following paragraphs and further in this manual If there is more than one keypad in the system only the keyp...

Page 26: ...ely Press the R button to continue or press the C button to exit Zone Response The normal loop response of each keypad expansion zone is 750mS however the response time of any zone can be reduced to 5...

Page 27: ...his procedure you will configure the panel for This procedure will automatically set up system keypads EZM s wireless transmitters etc After your basic default program has been loaded you may alter it...

Page 28: ...Test Seenduring initial configuration only Enable Telco Line Test Y N Enable Burg Bell Chirp on Keyfob Seenduring initial configuration only Enable Burg Out Chirp Y N Number of Fire Keypads in Area 1...

Page 29: ...Zones in Areas 2 8 Seen during initial configuration only Enter the zone numbers of zones to be used as Exit Entry zones Valid entries are from 01 to 96 Directly enter each zone number including leadi...

Page 30: ...h zone number including leading zeros Press U to save and then repeat for any additional zone s Press the NEXT button to proceed Note Only panel zones 01 08 can be programmed for Quick Loop Response A...

Page 31: ...ell will chirp once on Keyfob Arm and twice on Keyfob Disarm Number of Fire Keypads in Area 1 Enter the total number of Fire Keypads to be installed in Area 1 Valid entries from 01 07 Directly enter t...

Page 32: ...0 through 9 and D0 for blank Press D1 through D4 for letters B E Press U to save and press the NEXT button to proceed Easy Programming of Auto download ID s and PC Preset Callback Numbers GEMC FK1 ke...

Page 33: ...r to the tables below use the number buttons to enter the data for Keypad 1 4 in the right digit and the data for Keypad 5 8 data in the left digit Press the 0 buttons for blank Press U to save each c...

Page 34: ...codes The master user code and the dealer program code can view all codes User Program User Program Option is enabled for Keypad 1 only wherever it is connected any area If enabled Level 3 must also...

Page 35: ...ving a description on the keypad that describes the person holding the keyfob the location where the person holding the keyfob is stationed or the special purpose of the keyfob button being de pressed...

Page 36: ...s Press U to save each descrip tion To proceed to the next description place the cursor under the Zone Number e g 01 and change the Zone Number using 3 and 6 NOTE Zone Descriptions can only be entered...

Page 37: ...to reprogram system Cold Start Erases Entire Program This erases all programmed data Dealer Program Zone Description Data and Schedules Access address 8179 and press U Data entry is not allowed NOTE...

Page 38: ...nes in Area 2 and Up Exit Entry 2 Zones in Area 2 and Up 50mS Loop Response Zones Note 750mS is required for Loop Response time in UL installations Burg Module PGM1 Output Activated on Alarm Zones Sen...

Page 39: ...A 1 OPTIONS AREA 2 OPTIONS 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 USER CODE up to 6 digits AREA 1 OPT...

Page 40: ...igits AREA 1 OPTIONS AREA 2 OPTIONS 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 USER CODE up to 6 di...

Page 41: ...NT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 RF ID printed on xmtr box 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 XMTR ZONE CHECK SUM POINT 49 50 51 5...

Page 42: ...111 112 RF ID printed on xmtr box 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 XMTR ZONE CHECK SUM POINT 145 146 147...

Page 43: ...CK SUM POINT 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 RF ID printed on xmtr box 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 2...

Page 44: ...gramming Instructions Volume 1 Page 44 Programming Instructions Volume 1 EASY MENU PROGRAMMING WORKSHEET 7 OF 13 KEYFOB Area 2 8 CHECK SUM OPTION 1 OPTION 2 1 2 3 4 5 6 7 8 RF ID Printed on transmitte...

Page 45: ...RS See below 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 4...

Page 46: ...ions Volume 1 EASY MENU PROGRAMMING WORKSHEET 9 OF 13 ZN AVAILABLE CHARACTERS See below 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 43 44 45 46 47 48 49 50 51 52 53 5...

Page 47: ...ASY MENU PROGRAMMING WORKSHEET 10 OF 13 Zone Descriptions cont d ZN AVAILABLE CHARACTERS See below 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 86 87 88 89 90 91 92 93...

Page 48: ...ABLE CHARACTERS See below 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152...

Page 49: ...ABLE CHARACTERS See below 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195...

Page 50: ...VAILABLE CHARACTERS See below 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237...

Page 51: ...ss displays when programming in Direct Entry Program Mode as follows A BINARY BIT FORMAT Settings such as Zone Features display and accept data in binary bit or number format For example Zone Features...

Page 52: ...moving to the right upon each key press EXAMPLE Entries with the GEMC FK1 keypads Program Abort Delay to be 15 seconds DETERMINE THE DATA ENTRIES Referring to SYSTEM DELAYS TIMEOUTS in the Programming...

Page 53: ...DES table in the programming worksheets that follow the Wireless Low Battery reporting code is located at address 7925 the data entries needed to assign a code of 1B are 1 and D1 PROGRAM THE DATA ENTR...

Page 54: ...ram or to make minor field alterations to an existing control panel program The panel MUST be uploaded to NAPCO s PCD Windows software following any keypad program ming the PCD Windows s error check f...

Page 55: ...s 60 seconds and the maxi mum entry delay is 45 seconds NOTE Sensor Watch Time Options are similar to above table except in hours 2 Press U to save 1 Enter delay timeout in corresponding address locat...

Page 56: ...in both left and right digits of address locations 2 Valid entries are 0 9 Note Also Access Control on Burg Module PGM1 Output Address 5323 and Burg PGM 1 Output Control Timeout Address 5302 must bot...

Page 57: ...2300Hz Handshake Kissoff OFF 2 2300Hz Handshake Kissoff OFF 3 Enable Zone Number on Pulse Alarm OFF 3 Enable Zone Number on Pulse Alarm OFF 4 Single Digit Only OFF 4 Single Digit Only OFF 5 Sum Check...

Page 58: ...omputer see Glossary in WI1093 Initial value of 000 becomes 15 rings 1 Enter digits only 2 Valid entries are 003 015 NOTE Default is 15 Rings Press U to save CALLBACK TELEPHONE NUMBERS Enter telephone...

Page 59: ...05 AREA 7 ADDRESS 1206 1209 DIGITS 1 4 1206 1207 1208 1209 AREA 8 ADDRESS 1210 1213 DIGITS 1 4 1210 1211 1212 1213 SYSTEM ADDRESS 1214 1217 DIGITS 1 4 1214 1215 1216 1217 AREA 1 ADDRESS 1218 1221 DIGI...

Page 60: ...NG ID NUMBERS AREA 2 ADDRESS 1290 1293 DIGITS 1 4 1290 1291 1292 1293 AREA 3 ADDRESS 1294 1297 DIGITS 1 4 1294 1295 1296 1297 AREA 4 ADDRESS 1298 1301 DIGITS 1 4 1298 1299 1300 1301 AREA 5 ADDRESS 130...

Page 61: ...REPORTING OPTIONS 1 Select the desired option entering the option number 1 8 for each digit 2 Enter corresponding option number in address location NOTE Dark shaded data value box shows option not ava...

Page 62: ...7 ZONE 38 ZONE 39 ZONE 40 1476 1477 1478 1479 ADDRESS 1496 1499 ZONES REPORT CODE GROUP 13 ZONE 57 ZONE 58 ZONE 59 ZONE 60 1496 1497 1498 1499 ADDRESS 1500 1503 ZONES REPORT CODE GROUP 14 ZONE 61 ZONE...

Page 63: ...ADDRESS 1624 1627 ZONES REPORT CODE GROUP 45 ZONE 185 ZONE 186 ZONE 187 ZONE 188 1624 1625 1626 1627 ADDRESS 1628 1631 ZONES REPORT CODE GROUP 46 ZONE 189 ZONE 190 ZONE 191 ZONE 192 1628 1629 1630 16...

Page 64: ...0 USERS 41 48 ADDR U33 U34 U35 U36 U37 U38 U39 U40 ADDR U41 U42 U43 U44 U45 U46 U47 U48 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 User Opening Telco 1 1729 1730 User Closing Telco 1 1754 1755 User Opening Telco...

Page 65: ...6 7 8 User Opening Telco 1 1741 1742 User Closing Telco 1 1766 1767 User Opening Telco 3 1791 1792 User Closing Telco 3 1816 1817 Enable Users to Report USERS 145 152 USERS 153 160 ADDR U145 U146 U14...

Page 66: ...NAPCO Security Group NAPCO Gemini C Series Control Panel Programming Instructions Volume 1 Page 66 Programming Instructions Volume 1 NOTES...

Page 67: ...NAPCO Gemini C Series Control Panel Programming Instructions Volume 1 NAPCO Security Group Programming Instructions Volume 1 Page 67 NOTES...

Page 68: ...nstructions Volume 1 Publicly traded on NASDAQ Symbol NSSC 333 Bayview Avenue Amityville New York 11701 For Sales and Repairs 800 645 9445 For Technical Service 800 645 9440 or visit us at http tech n...

Reviews: