background image

LIBRA LIB-P432EX Series Programming Instructions 

NAPCO Security Systems 

Page 14

 

 

Interior Zones 

(Appears for New Panel Only) 

Directly enter the zone numbers which are to be used as Interior Zones.  Valid entries are from 01 to 
32.  Directly enter each zone number, including leading zeros.  Use number buttons 

1

 

through 

9

.  

NOTE: 

 Press the 

0

 

button for a zero.  Press 

u

 to save and then repeat for any 

additional zone(s).  Press NEXT ("

r

" or 

p

) to proceed. 

NOTE: 

 All Interior zones will also be automatically programmed as “Exit/Entry Follower” and 

"Power Up Delay" zones. 

 

 
 

 
 

 
 
 

 
 

 
 

 

 

 
 

24 Hour Zones in Area 1 

(New Program Only) 

Enter the zone numbers of zones to be used as 24 Hour zones.  

Valid entries are from 01 to 32.  Directly enter each zone number, including leading zeros.  

Press 

u

 to save and repeat for any additional zone(s); press NEXT ("

r

" or 

p

) to proceed. 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 

Chime Zones in Area 1 

(New Program Only) 

Enter the zone numbers which are to be used as Chime Zones.  

Valid entries are from 01 to 32.  Directly enter each zone number, including leading zeros.  

Press 

u

 to save and then repeat for any additional zone(s), press NEXT ("

r

" or 

p

) to proceed. 

NOTE:

 A chime time of 2 seconds will be automatically programmed. 

 

 
 

 
 

 
 

 
 

 
 

 

 

 
 

 

 

 
 

Chime 2 Zones in Area 1 

(New Program Only) 

Enter the zone numbers which are to be used as Chime 2 Zones.  

Valid entries are from 01 to 32.  Directly enter each zone number, including leading zeros.  

Press 

u

 to save and then repeat for any additional zone(s), Press NEXT ("

r

" or 

p

) to proceed. 

NOTE:

   A chime time of 2 seconds will be automatically programmed. 

 

              Chime 2 zones give a distinct pulsating tone when zone is faulted.

 

 

 
 

 

 

 
 

 
 

 
 

 

 

 
 

Exit/Entry2 Zones in Area 1 

(New Program Only) 

Enter the zone numbers of zones to be used as Exit/Entry zones.  

Valid entries are from 01 to 32.  Directly enter each zone number, including leading zeros.  

Press 

u

 to save and repeat for any additional zone(s); press NEXT ("

r

" or 

p

) to proceed. 

NOTE:

 An Exit/Entry 2 Entry Time of 30 sec. will automatically be programmed.  

 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 

50 mS Loop Response Zones 

(New Program Only) 

Enter the zone numbers of zones to be have a 50mS loop response.  

Valid entries are from 01 to 8.  Directly enter each zone number, including leading zeros.  

Press 

u

 to save and then repeat for any additional zone(s), press NEXT ("

r

" or 

p

) to pro-

ceed.  

Note:  

Time can also be adjusted via address 2280.

 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 
 

 

Aux Output Activated on Alarm Zones 

(New Program Only) 

Enter the zone numbers of zones to activate the PGM2 Output upon alarm.  

Valid entries are from 01 to 32.  Directly enter each zone number, including leading zeros.  

Press 

u

 to save and then repeat for any additional zone(s), Press NEXT ("

r

" or 

p

) to pro-

ceed.

 

NOTE:

  A PGM2 Output Timeout of 15 Minutes will automatically be programmed.  

 

 
 
 
 

 
 

 

(Direct Entry) 

(Direct Entry) 

 

14 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

   

H

 

(Direct Entry) 

 

13 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

   

H

 

(Direct Entry) 

 

12 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

   

H

 

(Direct Entry) 

 

11 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

   

H

 

(Direct Entry) 

 

09 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

   

H

 

(Direct Entry) 

 

08 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

   

H

 

 

10 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

   

H

 

Summary of Contents for GEM-DXK2

Page 1: ...nu Driven Dealer Program Mode Press 456789 w Press NO X or q until TURNON PROG Y N appears on the keypad Press YES r or p to enter Dealer Program Mode See page 5 Quick Start for GEM DXK3 1 Refer to the wiring diagram connect Siren Aux Power PGM Out put Remote Bus Earth Ground Zone and Telephone Wiring NOTE See Installation Instructions WI1691 2 Connect AC power first and then the battery 3 Configu...

Page 2: ...ay be used in this manual as well The Instant z button and the AWAY q button operate identically in Program Mode for both key pads These buttons are also used to answer NO or PRIOR to questions that appear on the keypad display on occasion an X symbol or an up arrow may be used as well For consistency it is recommended that all keypads used in one alarm system either be all type DXRP or all DXK Se...

Page 3: ...mber of Keypads 16 Central Station Receiver 1 Tel Number 16 Central Station Receiver 1 Account Number 16 Central Station Receiver 1 Format 16 Enter User Codes 16 RF Transmitter Points 17 Key Fob Transmitters 18 Dealer Code 19 Clear Program 19 DIRECT ADDRESS PROGRAM MODE 20 Keypad Programming Overview 20 Accessing Direct Address Program Mode 20 Keypad Address Program Mode Display 21 Direct Address ...

Page 4: ...pad Programming The Direct Address Program Mode is an extension of the Dealer Program Mode wherein data is entered at the keypad by specific location This mode is accessed from the Easy Menu Driven Program Mode by pressing the y button at any time User Program Mode Keypad programming The User Program Mode is intended for authorized users and is limited to keypad programming of User Codes DOWNLOADI...

Page 5: ...r on Alarm Zones Auto Bypass re entry Zones Enable no EOLR Zones Enable Telco Line Fault Test Enable Burg Output Chirp on Keyfob Enable CP 01 Number of Keypads in Area 1 Central Station Receiver 1 Tel Number Central Station Receiver 1 Account Number Central Station Receiver 1 Format Enter User Codes RF Transmitter Points Quick Enroll Method Key Fob Transmitters Enter Zone Descriptions Dealer Code ...

Page 6: ...stallation Instructions If Panel Zone doubling is not desired press PRIOR X or q Fire Zones in Area 1 Appears for New Panel Only Enter the zone number of any zones which are to be used as Fire Zones both 2 wire 4 wire or wireless Valid entries are from 01 to 32 Directly enter each zone number including leading zeros and press u to save and then repeat for any additional zone s Press NEXT r or p to...

Page 7: ...e a distinct pulsating tone when zone is faulted Exit Entry2 Zones in Area 1 New Program Only Enter the zone numbers of zones to be used as Exit Entry 2 zones Valid entries are from 01 to 32 Directly enter each zone number including leading zeros Press u to save and repeat for any additional zone s press NEXT r or p to proceed NOTE An Exit Entry 2 Entry Time of 30 sec will automatically be program...

Page 8: ...e designed to reduce the incidence of false alarms See WI1691 Installer Pro gramming Quick Reference Chart SIA False Alarm Reduction and LIB P432EX Factory Default Description for more information NOTE Do not enable unless reporting otherwise system trouble Fail to Communi cate may occur Number of Keypads in Area 1 Directly enter the total number of Keypads to be installed in Area 1 Valid entries ...

Page 9: ...s w once to set the cursor to the User Code Use the number buttons 1 through 9 to enter a code from 3 to 6 digits Enter up to 6 digits 4 digits is recommended in the first six boxes from left to right for each user code Valid entries are 0 9 NOTE Press 0 for a zero and press G0 for a blank space No blank spaces in between leave blank any trailing boxes If Enable Global Ambush Code Address 0720 is ...

Page 10: ...t has been successfully enrolled Multi point transmitters can be mapped to successive zones simultaneously see example Example A 2 point transmitter has the RF ID number 287613 1 Map point 1 to Zone 6 and point 2 to Zone 9 1 Enter the Enroll mode as described above 2 Enter Zone 06 3 Open point 1 loop 4 Install the battery The keypad will beep once to indicate that one point has been programmed Tra...

Page 11: ...g to a Central Station or a pager and or annunciating on a keypad the key fob zone number with description location To assign a key fob to a zone program the keyfob as you would a transmitter entering the keyfob s ID code check sum and point number at the appropriate zone The Quick Method is not allowed The zone may be hardwired to an electrical sensor as well as assigned to a key fob either one w...

Page 12: ...y is not allowed NOTE Enter Easy Menu Driven Program Mode to program system again Cold Start Erases Entire Program This erases the entire program including Dealer Program by erasing Program Data Zone Description Data and System Status Data similar to a new panel Access address 2286 then press the u button Data entry is not allowed NOTE Some features schedules can only be programmed again with the ...

Page 13: ...Use number buttons 1 through 9 NOTE Press the 0 button for a zero Press u to save and then repeat for any additional zone s Press NEXT r or p to proceed NOTE Exit Entry Zones will have an entry delay of 30 seconds and an exit delay of 60 seconds Press YES r or NO X 06 INTERIOR BYPASS FIRE TBL SYS TBL CHIME Direct Entry 07 INTERIOR BYPASS FIRE TBL SYS TBL CHIME INTERIOR BYPASS FIRE TBL SYS TBL CHIM...

Page 14: ...zone is faulted Exit Entry2 Zones in Area 1 New Program Only Enter the zone numbers of zones to be used as Exit Entry zones Valid entries are from 01 to 32 Directly enter each zone number including leading zeros Press u to save and repeat for any additional zone s press NEXT r or p to proceed NOTE An Exit Entry 2 Entry Time of 30 sec will automatically be programmed 50 mS Loop Response Zones New P...

Page 15: ...ed Enable No EOLR Zones New Program Only Press NEXT r or p to program all zones except 24 Hr fire zones for No End Of Line Resistor Press the PRIOR NO button to continue Enable Telco Line Fault Test Press NEXT r or p to enable Telco Line Fault Test Press the PRIOR NO button to continue NOTE There is a preset 60 second Telco Line Fault Test Delay Enable Burg Output Chirp on KeyFob Press NEXT r or p...

Page 16: ...er Codes with User Options for each code Refer to the tables below for available data entries for User Options Press w once to set cursor to the User Number and enter the desired User Number Press w once again to set the cursor to the User Code Use the number buttons 1 through 9 to enter a code from 3 to 6 digits Enter up to 6 digits 4 digits are recommended in the first six boxes from left to rig...

Page 17: ...G 0 for Blank Space 2 For User Options press 0 for Blank Space 28 INTERIOR BYPASS FIRE TBL SYS TBL CHIME INTERIOR BYPASS FIRE TBL SYS TBL CHIME Quick Enroll Method If a receiver is already installed in the panel Napco transmitter wireless points can be programmed automatically enrolled using the following procedure NOTE The transmitter point will be enrolled only if the signal strength is 3 or gre...

Page 18: ... a maximum of 64 controlled zones can be assigned providing multiple wireless panic buttons on a system each reporting to the Central Station or a pager and or annunciating on a keypad the key fob zone number with description location To assign a key fob to a zone program the key fob as you would a transmitter entering the key fob s ID code check sum and point number at the appropriate zone The Qu...

Page 19: ...y to silence the keypad Direct Entry 33 INTERIOR BYPASS FIRE TBL SYS TBL CHIME INTERIOR BYPASS FIRE TBL SYS TBL CHIME rE ZONE DESCRIPTIONS GEM DXK3 or GEM DXRP3 cannot be used to enter Zone Descriptions To enter Zone Descriptions you must use the GEM DXK1 or GEM DXRP1 keypad or the Napco Quickloader Software DATE ENTRY GEM DXK3 or GEM DXRP3 cannot be used to enter the date To enter Date you must u...

Page 20: ...ode is more flexible allowing you to change all the options It consists of multiple address locations with two data entry locations each left and right as shown in the adjacent diagram LEFT DIGIT RIGHT DIGIT 3 C DATA ENTRY LOCATIONS ADDRESS LOCATIONS 0000 0000 TO 2287 HEXADECIMAL DATA BLANK No Options 1 to 9 Entries 1 to 9 0 Entry of 10 B to F Entries 11 to 15 DIRECT ADDRESS PROGRAM MODE 1 Press E...

Page 21: ...TBL CHIME FIRE TBL 1 2 Flashing GEM DXRP3 GEM DXK3 Keypads Press w followed by 1 the 4 digit address location and 2 the corresponding data shown Note A long beep sounds when in Address Program Mode 1 2 GEM DXK4RF Series Keypads P 3C 00003C To access press y in Dealer Program Mode 1 Toggle Cursor to 4 digit ad dress field using the w button 2 Enter address Number directly using number buttons 0 9 3...

Page 22: ...none of which are Exit Entry Follower Zones is entered as a blank PROGRAM THE DATA ENTRIES 1 Enter the panel s Dealer Security Code then press w 2 Answer NO X or q to all questions until ACTIVATE PROGRAM Y N is displayed then press NEXT r or p NOTE If you pass ACTIVATE PROGRAM scroll backward using x 3 Press y to enter the Address Program Mode Address 0000 will display 4 Press 0916 to access Addre...

Page 23: ...its on the left data display segment and the right digit on the right segment For those addresses having only one programmable nibble program the right segment only the left segment should display a blank 3 Keep the Keypad Programming Worksheets on file for future reference General Programming Steps 1 Contact the central station to ascertain receiver format data format event codes subscriber numbe...

Page 24: ...selected data entry in the boxes shown 4 For more information on a programming option refer to the Glossary at the end of this manual EXIT ADDRESS 0000 DELAY LEFT RIGHT sec Default 3 C ENTRY ADDRESS 0001 DELAY 1 LEFT RIGHT sec Default 1 E ENTRY ADDRESS 0002 DELAY 2 LEFT RIGHT sec Default 1 E PGM2 Output ADDRESS 1413 Access Cntrl LEFT RIGHT Timeout sec Default blank blank ABORT ADDRESS 1417 DELAY L...

Page 25: ...RMAT OPTIONS ADDRESS 0546 0547 LEADING DIGITS FOR PAGER FORMAT In Pager Format reporting the message typically begins with 00 However for some pager services this will cause the Pager s Voice Mail feature to activate This option allows you to program these digits to any number desired A typical Pager report is 003 22 1234 where 3 is the Event 22 is the zone and 1234 is the Subscriber ID number For...

Page 26: ...1 0837 8 4 2 1 PGM1 Output 8 4 2 1 0838 8 4 2 1 PGM2 Output 8 4 2 1 0839 8 4 2 1 Report Event Telco 1 8 4 2 1 0840 8 4 2 1 Report Restore Telco 1 8 4 2 1 0841 8 4 2 1 Report Event Telco 3 8 4 2 1 0842 8 4 2 1 Report Restore Telco 3 8 4 2 1 0843 8 4 2 1 GLOBAL SYSTEM EVENT TROUBLE RIGHT DATA VALUES CIRCLE Default blank blank from address 0856 0863 SYSTEM RESPONSE ACTIVATED BY AREA 1 AREA 1 SYSTEM E...

Page 27: ...arm Output 8 4 2 1 0872 8 4 2 1 Alarm Output 8 4 2 1 0873 8 4 2 1 PGM1 Output 8 4 2 1 0874 8 4 2 1 PGM2 Output 8 4 2 1 0876 8 4 2 1 Report Event Telco 1 8 4 2 1 0877 8 4 2 1 Report Event Telco 3 8 4 2 1 0879 8 4 2 1 AREA 3 SYSTEM EVENT TROUBLE RIGHT DATA VALUES CIRCLE Default blank blank from address 0880 0887 SYSTEM RESPONSE ACTIVATED BY AREA 4 AREA 4 SYSTEM EVENT TROUBLE LEFT DATA VALUES CIRCLE ...

Page 28: ...ireless Trouble Activates Telco 3 8 Enable Alarm Output on Telco Fail only when Armed RIGHT DATA VALUES CIRCLE SYSTEM OPTIONS 1 Automatic Interior Bypass Easy Exit RESERVED RESERVED 8 Resound on Wireless Smoke Low Battery SYSTEM OPTIONS LEFT DATA VALUES CIRCLE Disable Keypad Function Mode Download 1 Disable Callback Download 2 Chirp Output on Keyfob Arm Disarm 4 Change Pulse Output to Temporal Out...

Page 29: ... circling the data values for each digit left and right 2 Add the data values ex F 15 1 2 4 8 from the selected options See page 23 3 Enter in address location left and right digits NOTE Dark shaded data value box shows option not available 4 Press u to save Default 13 D 10 0 LEFT DIGIT SUM OF DATA VALUES RIGHT DIGIT SUM OF DATA VALUES ADDRESS 2054 SYSTEM OPTIONS LEFT DATA VALUES Enable EN501 Grad...

Page 30: ...u Question CENTRAL PHONE Default blank across digits 1 20 for CS Receiver Telephone Numbers 2 and 3 CS Receiver 1 LEFT RIGHT Format blank ADDRESS 0460 CS Receiver 2 LEFT RIGHT Format blank ADDRESS 0482 CS Receiver 3 LEFT RIGHT Format blank ADDRESS 0504 CS RECEIVER TELCO 1 OPTIONS LEFT DATA VALUES CIRCLE Sum Check 1 3 1 with Extended Restores 2 RESERVED 4 RESERVED 8 CS RECEIVER TELCO 2 OPTIONS LEFT...

Page 31: ...TS 1 4 0664 0665 0666 0667 CS Telco 1 Sub scriber Opening Closing ID Number Area 4 ADDRESS 0572 0575 RIGHT DIGITS 1 4 0572 0573 0574 0575 CS Telco 1 Sub scriber Opening Closing ID Number Area 3 ADDRESS 0568 0571 RIGHT DIGITS 1 4 0568 0569 0570 0571 CS Telco 3 Sub scriber Opening Closing ID Number Area 2 ADDRESS 0636 0639 RIGHT DIGITS 1 4 0636 0637 0638 0639 CS Telco 3 Sub scriber Opening Closing I...

Page 32: ...ose 0704 Keyfob Low Battery 0705 CS SYSTEM REPORTING OPTIONS ADDRESS 0670 0705 CS AREA SYSTEM REPORTING OPTIONS ADDRESS 0785 0786 0788 Default blank blank LEFT DIGIT SUM RIGHT DIGIT SUM ADDRESS 0788 CS AREA SYSTEM REPORTING OPTIONS 1 Select the desired option by circling the data values for each digit left and right 2 Add the data values ex F 15 1 2 4 8 from the selected options See page 23 3 Ente...

Page 33: ... desired delay timeout ex 20 sec B Divide it by 16 4 Press u to save EXIT ENTRY DELAYS Apply only to zones programmed with the following options Exit Entry 1 Exit Entry 2 Exit Entry Follower NOTE Sensor Watch Time Options are similar to above table except in hours Either use the tables provided or calculate your own timeout using the steps indicated WARNING Timers have uncertainty of 1sec so a tim...

Page 34: ...ADDRESS 0740 0743 ZONES REPORT CODE ZONE 21 ZONE 22 ZONE 23 ZONE 24 0740 0741 0742 L R L R L R L R 0743 ZONE REPORT CODE OPTIONS LEFT RIGHT DATA ENTRIES NOTE If Zone Doubling Address 1423 is not enabled then Zones 1 4 are included in the control panel and Zones 5 32 are wireless Zones If Zone Doubling is enabled then Zones 1 4 and 9 12 are included in the control panel Zones 5 through 32 are avail...

Page 35: ...6 User 25 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUES ADDRESS 0804 User Opening Telco 1 User 40 User 39 User 38 User 37 LEFT RIGHT User 36 User 35 User 34 User 33 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUE ADDRESS 0805 User 48 User 47 User 46 User 45 LEFT RIGHT User 44 User 43 User 42 User 41 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUE ADDRESS 0809 User Opening Telco 1 User 8 U...

Page 36: ...6 User 25 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUES ADDRESS 0822 User Opening Telco 3 User 40 User 39 User 38 User 37 LEFT RIGHT User 36 User 35 User 34 User 33 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUE ADDRESS 0823 User 48 User 47 User 46 User 45 LEFT RIGHT User 44 User 43 User 42 User 41 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUE ADDRESS 0827 User Opening Telco 3 User 8 U...

Page 37: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 37 This page left blank intentionally ...

Page 38: ...ESERVED 1 RESERVED 2 RESERVED 4 RESERVED 8 Default blank one 1 Burglary Output Turns Off upon Disarm LEFT DIGIT SUM OF DATA VALUES RIGHT DIGIT SUM OF DATA VALUES 1 ADDRESS 1475 RIGHT DATA VALUES CIRCLE Disarming Area 3 1 Area 1 Burg Output Silenced 2 Area 2 Burg Output Silenced 4 Area 3 Burg Output Silenced 8 Area 4 Burg Output Silenced RESERVED LEFT DATA VALUES CIRCLE RESERVED 1 RESERVED 2 RESERV...

Page 39: ...ERVED 1 RESERVED 2 RESERVED 4 RESERVED 8 Default blank one 1 Pulsed Burg Output Turns Off upon Disarm LEFT DIGIT SUM OF DATA VALUES RIGHT DIGIT SUM OF DATA VALUES 1 ADDRESS 1479 RIGHT DATA VALUES Disarming Area 3 1 Area 1 Pulsed Burg Output Silenced 2 Area 2 Pulsed Burg Output Silenced 4 Area 3 Pulsed Burg Output Silenced 8 Area 4 Pulsed Burg Output Silenced RESERVED LEFT DATA VALUES CIRCLE RESERV...

Page 40: ...RESERVED 1 RESERVED 2 RESERVED 4 RESERVED 8 Default blank one 1 PGM1 Output Turns Off upon Disarm LEFT DIGIT SUM OF DATA VALUES RIGHT DIGIT SUM OF DATA VALUES 1 ADDRESS 1483 RIGHT DATA VALUES CIRCLE Disarming Area 3 1 Area 1 PGM1 Output Silenced 2 Area 2 PGM1 Output Silenced 4 Area 3 PGM1 Output Silenced 8 Area 4 PGM1 Output Silenced RESERVED LEFT DATA VALUES CIRCLE RESERVED 1 RESERVED 2 RESERVED ...

Page 41: ...RESERVED 1 RESERVED 2 RESERVED 4 RESERVED 8 Default blank one 1 PGM2 Output Turns Off upon Disarm LEFT DIGIT SUM OF DATA VALUES RIGHT DIGIT SUM OF DATA VALUES 1 ADDRESS 1487 RIGHT DATA VALUES Disarming Area 3 1 Area 1 PGM2 Burg Output Silenced 2 Area 2 PGM2 Burg Output Silenced 4 Area 3 PGM2 Burg Output Silenced 8 Area 4 PGM2 Burg Output Silenced RESERVED LEFT DATA VALUES CIRCLE RESERVED 1 RESERVE...

Page 42: ...ddress locations above 3 Press u to save KEYPAD OPTIONS ADDRESS 1425 1431 1440 1446 RIGHT OPTION blank Disabled 1 Active Keypad KEYPAD ASSIGNMENT KEYPAD NO KEYPAD OPTIONS LEFT DATA VALUES CIRCLE ADDRESS 1440 1446 KEYPAD OPTIONS RIGHT DATA VALUES CIRCLE RSRVD PANEL ACCESS EASY ARMING AMBUSH LEFT ADDR RIGHT RSRVD KEYPAD PANIC KEYPAD AUX KEYPAD FIRE 1 8 4 2 1 1440 8 4 2 1 2 8 4 2 1 1441 8 4 2 1 3 8 4...

Page 43: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 43 This page left blank intentionally ...

Page 44: ...e is 255 If a value above 255 is entered the system will display 000 to request a re entry Note Only the panel zones integration times are programmable In addition zone re sponses are enabled only when armed PRIORITY ARMING AREA 1 OPTION LEFT RIGHT blank blank Not Used blank 1 Enabled DATA ENTRIES PRIORITY ARMING AREA 2 OPTION LEFT RIGHT blank blank Not Used blank 1 Enabled DATA ENTRIES Priority A...

Page 45: ... 8 4 2 1 8 4 2 1 0933 8 4 2 1 Trouble on Open 8 4 2 1 0998 8 4 2 1 8 4 2 1 0934 8 4 2 1 Trouble on Short 8 4 2 1 0999 8 4 2 1 8 4 2 1 0935 8 4 2 1 Zone Area 1 8 4 2 1 1000 8 4 2 1 8 4 2 1 0936 8 4 2 1 Zone Area 2 8 4 2 1 1001 8 4 2 1 8 4 2 1 0937 8 4 2 1 Interior Stay Bypass 8 4 2 1 1004 8 4 2 1 8 4 2 1 0940 8 4 2 1 Keypad Sounder on Alarm 8 4 2 1 1005 8 4 2 1 8 4 2 1 0941 8 4 2 1 2 Wire Smoke Det...

Page 46: ...tdown 8 4 2 1 1110 8 4 2 1 8 4 2 1 1046 8 4 2 1 Chime 8 4 2 1 1111 8 4 2 1 8 4 2 1 1047 8 4 2 1 Abort Delay 8 4 2 1 1112 8 4 2 1 8 4 2 1 1048 8 4 2 1 Power up Delay 8 4 2 1 1113 8 4 2 1 8 4 2 1 1049 8 4 2 1 Day Zone Open 8 4 2 1 1114 8 4 2 1 8 4 2 1 1050 8 4 2 1 Day Zone Short 8 4 2 1 1115 8 4 2 1 8 4 2 1 1051 8 4 2 1 Alarm on Day Zone 8 4 2 1 1116 8 4 2 1 8 4 2 1 1052 8 4 2 1 Alarm Telco 1 8 4 2 ...

Page 47: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 47 This page left blank intentionally ...

Page 48: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 48 This page left blank intentionally ...

Page 49: ...vent ID COND ADDRESS 1544 1548 RELAY EVENT 12 1544 1545 1546 1547 L R L R L R L R L R 1548 RELAY AREA Timeout Event ID COND ADDRESS 1549 1553 RELAY EVENT 13 1549 1550 1551 1552 L R L R L R L R L R 1553 RELAY AREA Timeout Event ID COND ADDRESS 1554 1558 RELAY EVENT 14 1554 1555 1556 1557 L R L R L R L R L R 1558 RELAY AREA Timeout Event ID COND ADDRESS 1559 1563 RELAY EVENT 15 1559 1560 1561 1562 L...

Page 50: ...g address locations left and right digit STEP 5 RELAY EVENT CONDITION OPTIONS Each relay event can be assigned an alarm type and an activation condition also select a timeout type for each 5A Select Alarm Type and Timeout Type from Table 5A shown on next page enter in corresponding address location left digit 5B Select Activation from from Table 5B shown on next page enter in corresponding address...

Page 51: ...5 General System Alarm D 8 Area 1 General System Alarm D 9 Area 2 General System Alarm D 0 Area 3 General System Alarm D B Area 4 General System Alarm F blank Relay Control Group 1 F 1 Relay Control Group 2 F 8 Entry Relay Area 1 F 9 Entry Relay Area 2 F 0 Entry Relay Area 3 F B Entry Relay Area 4 7 E Area 3 Fail to Close 7 F Area 4 KP Ambush 8 1 Area 4 KP Panic 8 2 Area 4 KP Fire 8 3 Area 4 KP Au...

Page 52: ...3 Press u to save NOTE These timers apply only to Supervised RF Transmitters see RF Transmitters in Easy Menu Driven Mode Programming Default blank blank from address 2029 2044 RF SUPERVISORY TIMER RF TRANSMITTER LEFT ADDR RIGHT Type 0 Window Door 2 Pt blank 2029 Type 1 Window Door 2 Pt blank 2030 Type 2 Window Door 2 Pt blank 2031 Type 3 Window Door 2 Pt blank 2032 Type 4 RESERVED blank 2033 Type...

Page 53: ... Software If power fails time and date restarts at 00 00 00 and a date of 01 01 04 January 1 2004 GEM DXRP1 Keypad 2286 XX GEM DXRP2 Keypad 2286 XX USER PROGRAM MODE PRELIMINARY INFORMATION The User Program Mode is covered in detail in the operating instructions for the keypad in use The Program Mode cannot be accessed while the communicator is transmitting except during the first three minutes af...

Page 54: ...digit User Number 01 64 directly using number buttons 0 9 2 Press the w button 3 Enter Code 1 6 digits directly using number buttons 0 9 4 Press the u button to save each code NOTE Press G 0 button to clear character at cursor To continue press the p or q button UP To Program User Codes 1 Enter 2 digit User Number 01 64 directly using number buttons 0 9 2 Press the w button 3 Enter Code 1 6 digits...

Page 55: ...M DXK3 and GEM DXK4RF Keypads Up to 7 GEM DXRP2 GEM DXK2 GEM DXRP3 GEM DXK3 and or GEM DXK4RF keypads may be connected to the panel Keypads 1 7 Each must be configured for a keypad address In addition the keypad may be configured to disable a touchpad backlight b LCD backlight and c entry sounder Keypads are configured by the proper selection of jumpers Refer to the label on the circuit board insu...

Page 56: ...Y PROGRAM MENU 10 AUTO BELL TEST ON ARMING ADDRESS 1421 28 AUTO BYPASS RE ENTRY ZONES EASY PROGRAM MENU 8 14 15 AUTO RESET AFTER BURGLARY OUTPUT TIMEOUT ADDRESS 1421 28 AUTO RESET ZONE OPTION 45 46 47 48 AUTO BYPASS RE ENTRY ZONE OPTION 45 46 47 48 AUTO BYPASS ZONE OPTION 45 46 47 48 AUTOMATIC INTERIOR BYPASS EASY EXIT ADDRESS 1424 28 AUX 1 AUX 2 OPTIONS EASY PROGRAM MENU 11 AUX OUTPUT ACTIVATED O...

Page 57: ...SCROLLING ADDRESS 1420 28 DON T CLEAR PGM2 OUTPUT WITH DISARM ADDRESS 1424 28 DOWNLOAD CALLBACK OPTIONS ADDRESS 2059 0526 0545 25 DOWNLOADING FROM A COMPUTER 4 E EASY ARMING KEYPAD OPTIONS 42 EASY MENU DRIVEN PROGRAM MODE 5 EASY MENU DRIVEN PROGRAM MODE 4 EASY PROGRAM MENU 13 ENABLE K SERIES STYLE KEYPADS ADDRESS 2051 29 ENABLE 2 COUNT SWINGER SHUTDOWN ADDRESS 2054 29 ENABLE ALARM OUTPUT ON TELCO ...

Page 58: ...IONS 42 KEYPAD INSTALLATION 55 KEYPAD OPTIONS ADDRESS 1425 1431 1440 1446 42 KEYPAD PANIC 26 27 KEYPAD PANIC KEYPAD OPTIONS 42 KEYPAD PROGRAMMING OVERVIEW 20 KEYPAD SOUNDER ON ALARM ZONES EASY PROGRAM MENU 7 14 KEYPAD SOUNDER ON ALARM ZONE OPTION 45 46 47 48 KEYPAD TAMPER 26 27 KEYPAD TYPE 42 KEYPAD UNBLANKING TIME WINDOW ADDRESS 2060 33 KEYSWITCH ARMING ZONE OPTION 45 46 47 48 L LCD BACKLIGHT 55 ...

Page 59: ...PORT EVENT TELCO 1 ADDRESS 0869 26 27 REPORT EVENT TELCO 1 ADDRESS 0877 27 REPORT EVENT TELCO 3 ADDRESS 0842 26 REPORT EVENT TELCO 3 ADDRESS 0863 26 REPORT EVENT TELCO 3 ADDRESS 0871 26 27 REPORT OPTIONS CS SYSTEM 32 REPORT RESTORE TELCO 1 ADDRESS 0841 26 REPORT RESTORE TELCO 3 ADDRESS 0843 26 RESET DAY ZONE WITH ARM DISARM ONLY ADDRESS 1422 28 RESOUND ON WIRELESS SMOKE LOW BATTERY ADDRESS 1424 28...

Page 60: ... OPTIONS 17 USER PROGRAM MODE 4 USER PROGRAM MODE 53 V VERTEX RECEIVER FORMAT 16 W WIRELESS TROUBLE ACTIVATES TELCO 1 ADDRESS 1423 28 WIRELESS TROUBLE ACTIVATES TELCO 3 ADDRESS 1423 28 WIRING DIAGRAM 64 X XMITTER LOW BATTERY REPORTING OPTIONS ADDRESS 0673 32 XMITTER SUPERVISION REPORTING OPTIONS ADDRESS 0674 32 XMITTER TAMPER REPORTING OPTIONS ADDRESS 0675 32 Z ZONE ANDING GROUP 1 ZONE OPTION 45 4...

Page 61: ...G AFTER ALARM REPORTING OPTIONS 32 ADDRESS 0680 CONDITIONAL CLOSE REPORTING OPTIONS 32 ADDRESS 0681 CANCEL REPORTING OPTIONS 32 ADDRESS 0682 TEST TIMER REPORTING OPTIONS 32 ADDRESS 0683 TELCO FAIL REPORTING OPTIONS 32 ADDRESS 0684 RF REC TROUBLE REPORTING OPTIONS 32 ADDRESS 0685 MEMORY FAIL REPORTING OPTIONS 32 ADDRESS 0686 LOW BATTERY REPORTING OPTIONS 32 ADDRESS 0687 PANEL AC FAIL REPORTING OPTI...

Page 62: ... CLOSE STATUS 28 ADDRESS 1420 OPENING REPORT ONLY AFTER ALARM REPORT 28 ADDRESS 1420 STATUS REPORT 28 ADDRESS 1421 ACCESS CONTROL ON PGM2 OUTPUT 28 ADDRESS 1421 AUTO BELL TEST ON ARMING 28 ADDRESS 1421 AUTO RESET AFTER BURGLARY OUTPUT TIMEOUT 28 ADDRESS 1421 DISABLE KEYPAD INSTANT MODE 28 ADDRESS 1421 ENABLE LOCAL ALARM ON FIRST ZONE AND TRIP 28 ADDRESS 1421 ENABLE MANAGER S MODE 28 ADDRESS 1421 M...

Page 63: ...53 DISABLE CALL WAITING ON 1ST ATTEMPT 29 ADDRESS 2053 ENABLE CP 01 EGRESS TONES ONLY 29 ADDRESS 2053 ENABLE CP 01 LIMITS 29 ADDRESS 2053 ENABLE KEYPAD 1 ONLY PROGRAMMING 29 ADDRESS 2053 EXIT TIME RESTART 29 ADDRESS 2053 RPT EXIT ERR RECENT CLOSE 29 ADDRESS 2053 SOUND ALARM ON EXIT ERROR 29 ADDRESS 2054 ENABLE 2 COUNT SWINGER SHUTDOWN 29 ADDRESS 2054 ENABLE DISPLAY TIME ON BLANKED KEYPADS 29 ADDRE...

Page 64: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 64 LIB P432EX WIRING DIAGRAM ...

Page 65: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 65 LIB P432EXT WIRING DIAGRAM ...

Page 66: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 66 LIB P432EXT 230 WIRING DIAGRAM ...

Page 67: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 67 NOTES ...

Page 68: ...e 68 R Publicly traded on NASDAQ Symbol NSSC NAPCO Security Group Inc 333 Bayview Avenue Amityville New York 11701 For Sales and Repairs call toll free 800 645 9445 For direct line to Technical Service call toll free 800 645 9440 Internet http www napcosecurity com NAPCO 2008 ...

Reviews: