
L
NAPCO Security Systems
Freedom F-64 Programming Instructions
Page 7
WI1502A 9/06
Chime Zones in Area 1
(New Program Only)
•
Enter the zone numbers which are to be used as Chime Zones.
•
Valid entries are from 01 to 64. Directly enter each zone number, including leading zeros.
•
Press
U
to save and then repeat for any additional zone(s), press the
NEXT/YES
button to proceed.
NOTE:
A chime time of 2 seconds will be automatically programmed.
Chime 2 Zones in Area 1
(New Program Only)
•
Enter the zone numbers which are to be used as Chime 2 Zones.
•
Valid entries are from 01 to 64. Directly enter each zone number, including leading zeros.
•
Press
U
to save and then repeat for any additional zone(s), Press the
NEXT/YES
button to proceed.
NOTE:
A chime time of 2 seconds will be automatically programmed.
Chime 2 zones give a distinct pulsating tone when zone is faulted.
Exit/Entry2 Zones in Area 1
(New Program Only)
•
Enter the zone numbers of zones to be used as Exit/Entry zones.
•
Valid entries are from 01 to 64. Directly enter each zone number, including leading zeros.
•
Press
U
to save and repeat for any additional zone(s); press the
NEXT/YES
button to proceed.
NOTE:
An Exit/Entry 2 Entry Time of 30 seconds will automatically be programmed.
50 mS Loop Response Zones
(New Program Only)
Note: 750mS is required for Loop Response
time in UL installations.
•
Enter the zone numbers of zones to be have a 50mS loop response.
•
Valid entries are from 01 to 08. Directly enter each zone number, including leading zeros.
•
Press
U
to save and then repeat for any additional zone(s), Press the
NEXT/YES
button to proceed.
Note:
Only panel zones 01-08 can be programmed for Quick Loop Response. All other zones can be
programmed via their respective EZM's (hardwire). Time can also be adjusted via address 2280.
Aux Output Activated on Alarm Zones
(New Program Only)
•
Enter the zone numbers of zones to activate the PGM2 upon alarm.
•
Valid entries are from 01 to 64. Directly enter each zone number, including leading zeros.
•
Press
U
to save and then repeat for any additional zone(s), Press the
NEXT/YES
button to proceed.
NOTE:
A PGM2 Timeout of 15 minutes will automatically be programmed.
Sensor Watch Zones
(New Program Only)
•
Enter the zone numbers of zones to be Sensor Watch zones.
•
Valid entries are from 01 to 64. Directly enter each zone number, including leading zeros.
•
Press
U
to save and then repeat for any additional zone(s), Press the
NEXT/YES
button to proceed.
NOTE:
A Sensor Watch Time of 24 hours will automatically be programmed.
Keypad Sounder On Alarm Zones
(New Program Only)
•
Enter the zone numbers of all zones to activate the Keypad Sounder upon alarm.
•
Valid entries are from 01 to 64. Directly enter each zone number, including leading zeros.
•
Press
U
to save and then repeat for any additional zone(s), Press the
NEXT/YES
button to proceed.
Auto Bypass Re-entry Zones
(New Program Only)
(Not Evaluated by UL)
•
Enter the zone numbers of zones to be Auto Bypass Re-entry zones.
•
Valid entries are from 01 to 64. Directly enter each zone number, including leading zeros.
•
Press
U
to save and then repeat for any additional zone(s), Press the
NEXT/YES
button to proceed.
•
Auto Bypass Re-entry Zones allow the system to be armed with the zone faulted but come back into
the system (armed) when the zone is subsequently closed.
Enable No EOLR Zones
(New Program Only)
•
Press
YES
to program all zones except 24 Hr & fire zones for No End Of Line Resistor. Press
NO
to
continue. Do NOT program this feature for UL installations.
Enable Telco Line Fault Test?
•
Press
YES
to enable Telco Line Fault Test.
•
Press
NO
to continue.
NOTE: If enabled, a Telco Line Fault Test Delay of 60 sec. will auto-
matically be programmed.
(Direct Entry)
C h i m e Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
C h i m e 2 Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
E x i t / E n t r y 2 Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
5 0 m S L o o p Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
A u x O u t p u t Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
S e n s o r W a t c h Z n s
E n t e r Z o n e # ° °
(Direct Entry)
K P S n d r A l r m Z n s
E n t e r Z o n e # ° °
(Direct Entry)
A u t o B y p R E n t Z n
E n t e r Z o n e # ° °
(Press YES or NO)
E n a b l e N o E O L R
Z o n e s Y / N
(Press YES or NO)
Enable Telco
Line Test? Y/N
E
A
SY MEN
U
DR
IVEN
PRO
G
RA
M
MOD
E