NANO NRC0020-0200 UL Operating And Maintenance Manual Download Page 9

7

OPERATING AND MAINTENANCE MANUAL

Chapter 4 

- Description

NRC0020-0200 UL

The data in this manual are not binding and may be changed by the manufacturer without notice. 

Reproduction of this manual, even partial, is strictly prohibited.

C

HAPTER

 4

D

ESCRIPTION

4 . 1

O p e r a t i n g   p r i n c i p l e

A refrigerant circuit cools a patented “thermal mass” through which the humid compressed air to be dried flows.
The air cools, resulting in condensation of the water vapor it contains, which is subsequently separated and discharged.
The temperature of the thermal mass is regulated by an electronic controller, which stops the refrigerant compressor when the programmed set-
point is reached.

4 . 2

A i r   a n d   r e f r i g e r a n t   c i r c u i t s

(See attached refrigerant circuit diagrams)

4.2.1 Air circuit

The warm and humid compressed air entering the dryer flows through the air/air exchanger section of the thermal mass.
Here the air is precooled by the cold and dry compressed air leaving the air/refrigerant or evaporator section of the thermal mass.
The precooled air then enters the evaporator section of the thermal mass where it is cooled (in most applications to a temperature of 
approximately 3°C/37.4 °F) exchanging heat with the refrigerant fluid and the silica thermal mass.
Heat is exchanged by a process of conduction through the aluminium fins that join the copper tubes through which the compressed air flows, to 
the copper tubes in which the refrigerant fluid evaporates.
The aluminium fins exchange heat also with the silica thermal mass keeping it at a temperature of approximately 0°C (32°F).
At this point the compressed air is saturated and conveys with it the condensation produced during the cooling process.
The precooled air then enters a high efficiency condensate separator (demister type with stainless steel mesh) where the condensate is 
precipitated and collected on the bottom of the enclosure.
A condensate drain either of the timer controlled or capacitive type, depending on the unit's configuration, opens periodically and drains the 
condensate which is expelled by compressed air pressure.
The dry cold air at the outlet of the separator flows for the second time through the air/air section of the thermal mass, where it absorbs the heat 
of the warm and humid compressed air entering the dryer and thereby cools the inlet flow.
This air/air exchanger both reduces the amount of energy required to dry a given flow of air and also has the benefit of reducing the relative 
humidity thereby avoiding the risk of the formation of condensate at the dryer outlet.

4.2.2 Refrigerant circuit

The high pressure compressed refrigerant gas flows into the condenser.
In the condenser the refrigerant changes from the gaseous to the liquid phase.

The condenser is a heat exchanger of the finned core type and it is cooled by an air flow provided by fan.
The condenser is generously sized in such a way that it can function partially also as a liquid receiver.

Downstream from the condenser the refrigerant enters a filter drier and a capillary tube where refrigerant pressure is reduced to lower its boiling 
pressure.
The refrigerant then enters the tubes of the evaporator section of the thermal mass, cooling both the compressed air and the thermal mass itself.
The refrigerant at the dryer outlet is now in the form of a cold vapor, which is returned to the compressor to repeat the cycle.
Since the heat provided by the compressed air to cause the refrigerant to evaporate varies significantly because of fluctuations in the compressed 
air temperature and flow rate, the dryer is equipped with an electronic system to control the temperature of the thermal mass. This system fulfils 
3 important roles:

it ensures an almost constant pressurised dew point (approx. +3°C (+37.4°F));

it prevents the compressed air temperature from falling below 0°C (32°F) with consequent freezing of the condensate;

it ensures that all the refrigerant is evaporated in the evaporator, thus avoiding the risk of any liquid entering the compressor 
suction side.

When the load is low or zero, the temperature of the thermal mass tends to fall.
When it reaches 0°C (32°F) the electronic controller stops the compressor.
The compressed air that continues to flow in the evaporator is cooled by the cooling energy stored in the silica.
When the silica temperature starts to rise, the refrigerant compressor is started automatically so that it can cool it down again.
This system offers the benefit of reducing average energy consumption of the dryer in such a way as to make it approximately proportional to 
demands.

Summary of Contents for NRC0020-0200 UL

Page 1: ...R e f r i g e r a t e d a i r d r y e r s OPERATING AND MAINTENANCE MANUAL Our contact details www n psi com 38178800655 Original instructions NRC0020 0200 UL...

Page 2: ......

Page 3: ...Location 8 5 2 Piping 8 5 3 Electrical connections 9 Chapter 6 START UP 11 Chapter 7 IDRY ELECTRONIC CONTROLLER 12 7 1 User interface 12 7 1 1 Display 12 7 1 2 Buttons 12 7 1 3 Icons 13 7 2 Main func...

Page 4: ...in the dimensional drawings and refrigerant circuit diagrams in this manual The meaning of each symbol is indicated hereinafter The following warning symbols are to be found on the decals affixed to t...

Page 5: ...long working life If spare parts are needed use exclusively genuine original components Requests for SPARE PARTS and any INFORMATION concerning the dryer must be made to the nearest dealer or service...

Page 6: ...n strictly necessary Handling of dryers must be carried out in compliance with the diagrams given see the final part of this manual The manufacturer does not supply bars belts and lifting hooks with t...

Page 7: ...pted to protect against the toxic fumes that may be given off Before removing any panels or dismantling any parts of the unit perform the following steps Isolate the unit from the electrical power sup...

Page 8: ...max Sum of FLA of all loads INSTALLED POWER P max Sum of the maximum power input of all loads PROTECTION RATING According to European standard UL508A and EN60529 ELECTRICAL DIAGRAM Identifies the elec...

Page 9: ...h the air air section of the thermal mass where it absorbs the heat of the warm and humid compressed air entering the dryer and thereby cools the inlet flow This air air exchanger both reduces the amo...

Page 10: ...lation drawing 1 The inlet and outlet connections are clearly marked see Chapter 1 General Information The piping and connections must be correctly sized and suitable for the working pressure of the a...

Page 11: ...the electrical panel components undo the nuts fixing its protective cover to the front panel 2 Connect the unit terminal in the electrical panel to the electrical earthing system of the building 3 Ma...

Page 12: ...ing ambient temperature according to the chosen installation type see the indications on the electrical diagram Use exclusively copper cables marked UL in compliance with NEC NATIONAL ELECTRICAL CODE...

Page 13: ...see Chapter 7 iDRY Electronic Controller 6 Press button of the control unit Once the programmed delay has elapsed the compressor and fan will start On three phase power supply models make sure the fa...

Page 14: ...ges shown on the LCD display The display messages can be Unit OFF Unit running normal operation High Dew Point temperature BUTTON FUNCTION Displays or edits the set point During programming selects a...

Page 15: ...he display will show the message 0 W The icon indicates compressor operation In the event of sudden power failure when the unit is running the unit will resume operation automatically when the power i...

Page 16: ...ithin the time interval set in parameter the alarm is activated The message is displayed the compressor is shut down and control is suspended To resume normal operation the device must be switched off...

Page 17: ...played Press and hold buttons and for a few seconds until the message flashes on display The keypad is now unlocked NOTE The new value entered is saved to the memory also when you quit programming mod...

Page 18: ...vated on opening of the contact the digital input is activated on closure of the contact oP CL CL X Pr1 Digital input configuration external alarm external shutdown alarm pressure switch remote On Off...

Page 19: ...he instrument off 7 5 2 High and low temperature alarm memorization When the icon illuminates the unit is in alarm status Flashing Alarm active Steady Temperature alarm reset and memorised To check th...

Page 20: ...ic board monitors the signal sent by the capacitive sensor continuously When the condensate level reaches the sensor lower limit the solenoid valve is de energized thereby interrupting condensate drai...

Page 21: ...rom the insulated condensate drain pipe which protrudes from the underside of the dryer The pipe fittings of the condensate drain are supplied in a plastic bag secured to the condensate drain insulate...

Page 22: ...end breaks without any problem In this case remember when the unit is required for duty again to switch the dryer on at least 10 15 minutes before the air compressor 9 2 M a i n t e n a n c e CAUTION...

Page 23: ...n the limit for which the dryer was selected normally 35 40 C 95 104 F When the compressor is running check that its upper part is not too hot more than approximately 50 C 122 F Check that the dryer s...

Page 24: ...sitioning Circuit has insufficient refrigerant charge Isolate the dryer from the air network dismantle the solenoid valve clean the components and refit the valve Air cooled dryers front surface of th...

Reviews: