Assembly
1.
For roof installation, use appropiate roof base in order to
provide correct distance from a roof.
2.
Use insulation material as shown in fig.
3.
A fan connects to assembly duct, see fig.
4.
Secure the fan against extreme weather conditions, with
steel cables prevent it from falling.
5.
Correctly connect the power cord, make sure to look at
the wiring diagram. All poles of a circuit breaker moun
-
ted devices connect with the separator.
6.
Be sure to install according to the direction of air flow.
7.
Please try to run the fan after installation, check for vibra
-
tion and errors.
Wiring
•
Products should be installed only by authorized persons.
•
Installation of the product should be specified in the project, installation to the wall or floor must be securely mounted. If
mounted on the wall, it should be mounted with bracket or with clamps.
•
Fan blades must be installed at least 2.3 m above floor level, in case of wall installation.
•
Fan can not be installed outside the window or wall.
•
Necessary precautionary measures should be done to avoid back flow of gases into the chamber from outdoor gas pipe or
other fuels device. Wearing gloves is recommended during the assembly process.
•
The product must be connected to the input and output ducts.
•
Turn off the power before connecting electrical cords.
•
When mounting brackets and mounts are installed correctly, make sure that they are solid enough to safely carry the weight
of product.
ROOF FAN
DV-ROF-V
ASSEMBLY DUCT
INSULATION
ROOF BASE
PDI-BRF
Markings on the products or declared values on the other printed documents has been obtained in the laboratory in accordance with
related standards. These values may vary depending on product usage and environmental conditions.
Technical data
Model
Voltage
[V]
Frequency
[Hz]
Power
[W]
Current
[
A]
Capacitor
[
µF]
Speed
[rpm]
Air flow
[m
3
/h]
Sound level
[dB(A)]
Weight
[kg]
DV-ROF-V-225
230
50/60
160/220
0.71/0.99
6
2650
850
43-35
7
DV-ROF-V-315
230
50/60
150/175
0.92/0.85
6
1450/1725
1900/2260
45-37
22
DV-ROF-V-355
230
50/60
200/255
1.1/1.25
8
1400/1600
2850/3250
46-38
34
DV-ROF-V-400
230
50/60
310/460
1.56/2.27
10
1380/1560
4000/4521
47-39
39
DV-ROF-V-450
230
50/60
425/630
2.17/3.15
10
1390/1550
5400/6000
50-42
51
DV-ROF-V-500
380 Δ/Y
50
960/620
2/1.1
-
1400/1050
7600/5700
52-44
60
ALNOR
®
systemy wentylacji
jest prawnie chronionym znakiem i technicznym patentem. Prawo do zmian zastrzeżone.
10