FP0 A/D Converter Unit
2.2
Input Range Setting (DIP) Switches
2-3
Matsushita Electric Works (Europe) AG
2.2
Input Range Setting (DIP) Switches
Mode
Switch
number
Range
Analog
input
1 and 2
0 to 5V 0 to 20mA
(see note 1)
–10 to 10V
–100 to 100mV
range
1
2
ON
or
Number
of input
channels
3 and 4
Conver-
sion
channel
Number
of input
channels
Conver-
sion
channel
Number
of input
channels
Conver-
sion
channel
Number
of input
channels
Conver-
sion
channel
Number
of input
channels
ch0 and 1
2
ch0 to 3
4
ch0 to 5
6
ch0 to 7
8
3
ON
4
Averaging
function
5
No averaging
(see note 2)
With averaging
(see note 3)
ON
5
Notes
1) It is possible to use the 0 to 5V range and 0 to 20mA range
together.
2) The A/D conversion data is set for the specified input contact
point area for each A/D conversion on each channel.
3) On each channel, for each A/D conversion, the maximum and
minimum values from the data of the last ten times are
excluded, and the data from the other eight times is averaged,
and the result set.
(Use when the environment contains a lot of noise.)
4) The switch reads only once when the power supply of FP0
control unit is turned on.
Summary of Contents for FP0-A80
Page 4: ...Table of Contents FP0 A D Converter Unit ii Matsushita Electric Works Europe AG...
Page 5: ...Chapter 1 Parts and Terminology...
Page 9: ...Chapter 2 Wiring and Input Range Setting Switch...
Page 13: ...Chapter 3 A D Conversion Characteristics...
Page 19: ...Chapter 4 I O Allocation and Program...
Page 27: ...Chapter 5 Specifications and Dimensions...
Page 32: ...FP0 A D Converter Unit Specifications and Dimensions 5 6 Matsushita Electric Works Europe AG...
Page 34: ...Index FP0 A D Converter Unit Matsushita Electric Works Europe AG I 2...