Nailor UNI2-VAV Assembly Download Page 6

IOM-TBN

Date: 12-2021 

Supersedes: NEW

Page 6 of 6

IOM 

 BACnet

®

 UNI2-VAV Diffuser Assembly

Nailor reserves the right to change any information concerning product or specification without notice or obligation.

TBN    Wiring Diagram:

NOTE:

1.  Dashed  lines  indicate  new  field  wiring.  Sold  lines  indicate 

existing wiring to remain or new field wiring by others.
2. All field wiring must meet or exceed the requirements of the 

National Electrical Code (NEC) and the Sate Local requirements.
3.  For  inputs  and  outputs,  the  shield  wire  is  grounded  at  the 

controller end only.
4. Wiring for inputs and outputs is 18 AWG, shielded, twisted pair 

with stranded tinned copper conductors.

5.  The  BACnet

®

  MS/TP  network  wire  is  24  AWG  (0.65  mm) 

 

stranded,  twisted  shield  pair  (Jackson  system  part#:  24/2 

BACnet

®

). The BACnet

®

 MS/TP communication wire is polarity 

sensitive and the only acceptable topology is to Daisy-chain the 

cable from one controller to the next.
6. Mount space temperature sensor per ADA requirements. Field 

verify location and coordinate with other trades.

SMART VUE

COMMUNICATING

SPACE SENSOR

WIRELESS

PORT

SHIELD

NET

--

NET+ RX/TX

24V

AC

24V COM

PRESSURE

HIGH

LOW

24V COM

POWER

ST

ATUS

SUBNET

UI3

UI2

COM

UI1

COM

UO4

DO3

DO2

DO1

24V

AC

 OUT

Reviews: