TBN BACnet Thermostat 

 General Configuration

13. Press the 

Menu

 button again the Unocc Heat Setpoint will 

appear. The default setting is 62

°

F. To change the default, use the 

arrow keys.

14. Press the 

Menu

 button again the Unocc Cool Setpoint will 

appear. The default setting is 78

°

F. To change the default, use the 

arrow keys.

15.  Press  the 

Menu

  button  again  and  the  Max  Duct

 

Temp will appear if either 1 or 2 stage reheat or 0-10/2-10 volts 

was enabled. The default setting is 80

°

F. To change the default 

setting,  use  the  arrow  keys.  This  screen  will  be  skipped  if  no 

reheat is selected.
16. Press the 

Menu

 button again and the Max Duct Discharge 

will appear if either 1 or 2 stage reheat or 0-10/2-10 volts was 

enabled.  The  default  setting  is  120

°

F.  To  change  the  default 

setting,  use  the  arrow  keys.  This  screen  will  be  skipped  if  no 

reheat is selected.
17. Press the 

Menu

 button again and the Slave Damper Enable 

will appear. The default setting is Disable. To change the default, 

use the arrow keys.

 

18. Press the 

Menu

 button again and Motion Bypass will appear 

if the TBN has a motion detector on board. The default setting is 

Enable. To change the default setting, use the arrow keys.
19. Press the 

Menu

 button again and Motion Bypass Time will 

appear if the TBN has a motion detector on board. The default 

setting  is  60  Minutes.  To  change  the  default  setting,  use  the 

arrow keys.
20. Press the 

Menu

 button again and CO

2

 Setpoint will appear if 

the TBN has CO

2

 detection on board. The default setting is 800 

ppm. To change the default setting, use the arrow keys.

Advanced 

Menu

and 

-

 Enters Advanced Menu, when held for 5 sec

- Navigates between parameters

- Submits a modified parameter

- Goes up one level, when held for 5 sec

- Cancels a modified parameter, when held for 5 sec

- Modifies a parameter

- Goes up one level when pressed in Exit screen

- Releases an override when both are pressed

- Enters into a submenu

Button Navigation Guide:

21.  Press  the 

Menu

  button  again  and  Operation  -  Auto  will 

appear. This is the default for automatic damper operation.

22. To use Hand Positions, press the UP arrow button until the 

display reads Operation - Hand. This allows Hand Position to be 

active.
If the UP arrow button is pressed again, the display will toggle 

back to Auto. Press 

Menu

 to advance to next screen.

23. When in Hand Position, use the arrow buttons to increase or 

decrease the damper position value. The default percentage is 

25% which is the fixed position the damper will open.

24. Exit the submenu via the arrow keys or let stat timeout.