4
Installation and operation manual
–
DTHR-V9-2020
Electrical supply: 120VAC / 1ph/60Hz
–
(from 4 to 15 Amp. Refer to name plate for specific value)
Notes:
1
. Intended for a temperature rise of 50°F to 120°F (28°C to 67°C)
-
1 MBTU: 1000 BTU/ Hr
-
CFM: Cubic foot per minute
-
Ratings are based on 1000 Btu/ft
3
for natural gas and 2500 Btu/ft
3
for propane at sea level. Reduce burner
capacity for altitude over 2000ft by 4% for each 1000ft above sea level.
Important
All gas piping must be performed by a qualified personel following the local codes and CSA B149.1
installation code for Canada or ANSI Z223.1/NFPA 54 for the United States.
*: With 10’’w.c. minimum inlet pressure.
**: With optional 2’’ NPT gas train for 7’’w.c. inlet pressure. The vent
must be piped to outdoor.
***: To be used in ventilated space only. In other case the regulator vent must be piped to outdoor. Use
½’’
NPT tubing.
Note:
•
This table should not be used to size the site gas supply line.
•
If supply gas pressure exceeds 14 inches w.c., a high-pressure regulator must be installed at gas piping
inlet. The regulator must be suitable for modulation ratio of 40:1 to properly regulate gas pressure at
low fire.
•
The regulator vent must be piped separately towards the outside of the building as stated by CSA B149.1
for Canada and ANSI Z223 for USA and local codes.
DTHR
Model
Input capacity
Output capacity
Turndown
ratio
Air flow
1
MBTU
kW
MBTU
kW
CFM
kW
Min.
Max.
Min.
Max.
35
438
128
350
102
15:1
2701
6481
1275
3059
40
500
143
400
117
17:1
3086
7407
1457
3496
50
625
183
500
146
21:1
3858
9259
1821
4370
55
688
201
550
161
17:1
4247
10193
2004
4810
65
813
238
650
190
20:1
5019
12054
2368
5684
75
938
275
750
220
23:1
5790
13896
2733
6558
85
1063
311
850
249
27:1
6562
15748
3097
7432
100
1250
366
1000
293
31:1
7716
18519
3642
8740
125
1563
458
1250
366
26:1
9645
23148
4552
10925
150
1875
549
1500
439
31:1
11574
27778
5462
13110
Dim
Gas train connections (NPT)
Model
35
40
50
55
65
75
85
100
125
150*
150**
Ø Gas
1
1
1
1
1
1
1-1/2 1-1/2
1-1/2
1-1/2
2
Ø Regulator Vent***
N/A: Vent limiter factory installed
***
1/2
Ø Vent valve
N/A: Valve proving system included with IRI gas train option.
Specifications
Gas supply