DT Series - Installation manual (V3_2020)
27
11.
START-UP INSTRUCTIONS
WARNING!
DO NOT SMOKE during gas heater start-up
The following information should only be used by a qualified technician for gas equipment
installation (with qualification cards) with knowledge in electricity and ventilation.
This unit is connected to high voltages and contains moving parts that can start unexpectedly.
Electrical shock, severe injury or death could occur if instructions given in this manual are not
followed. Always disconnect and lock out power before servicing this equipment. All work
should be done by a qualified technician. DO NOT bypass any interlock or safety switches
under any circumstances.
Proper commissioning of this equipment is the responsibility of the installing contractor. It is
recommended that an air balance be completed before the unit start up by a certified air
balancing contractor to ensure that the air volume being sent downstream of the unit into the
ventilation system matches the unit rating label. Failure to perform a proper air balance can
cause injury or death, damage to the equipment, property damage, system operational
problems, or be a cause of poor indoor air quality. Moisture carries over can also result from
improper air flow.
11.1.
RECOMMENDED TOOLS
•
Voltmeter
•
Ammeter
•
Air temperature reading device
•
Tachometer (Fan & motor [rpm])
•
Pressure gauge
o
0 - 5 in. w.c.
o
0 - 20 in. w.c.
•
Combustion analyzer
•
Flat and Philips Screwdrivers
•
Hex Wrenches