2.
Grounding of the cabinet
If outdoor cables containing metal are imported into the rack, the stand must always be grounded. Ground
the cabinet by connecting it to the ground potential or ground of the IT area. Use a grounding cable of at
least 16 mm² and connect the grounding cable to the grounding bar.
3. Terminating cables in the cabinet
The termination of cables to the NAF1000 cabinet can be done in two ways:
1
Splicing to the pigtail cables are done on a splice tray, which is mounted on the splice
tray holder inside the cross-connection cabinet.
2
Splicing to the pigtail cables are done on a splice tray, which is mounted on the splice
tray holder outside the cross-connection cabinet.
3.1
Installation of the splice tray holder inside the cross-connection cabinet
The splice tray holder is to be installed first. Cage nuts are installed as follows: 23cm and 43cm from the
bottom of the rotating frame. The splice tray holder is installed using the cage nuts. The holder comes on
the frontside of the rotating frame.