并经一定的时间后断路器将断开。

过载指示灯快速闪烁时

(

频率

4Hz)

,表示在

3

次脱扣动作仍未导致产品脱扣。

Constant  light  of  overload  indicator  indicates  that  actual  current  is  more  than  1.5  times  of 

overload long-time delay current setting Ir. The breaker will break the circuit after certain duration.

When the overload indicator flashes fast

frequency is 4Hz

),

it indicates that the 3 trip has not 

caused the product tripped.

2

)电源指示灯

Power light

     

电源指示灯慢速闪烁时

(

频率

1Hz)

,表示正常运行;

电源指示灯快速闪烁时

(

频率

4Hz)

,代表控制器自检或系统运行过程中检测到故障。

When  the  overload  indicator  flashes  slow(frequency  is  1Hz)

it  indicates  that  the  system  is 

running normally

When the overload indicator flashes fast (frequency is 4Hz)

it indicates that self-checking of 

the controller or failure detected during the system operation.

注:两种指示灯应在每半年进行一次常规检验。

Note: Two indicator lights should have once routine inspection per half a year.

3.2.2.4

过载长延时保护

  Protection of overload long-delay 

a

)过载长延时整定电流

  Ir

,容许偏差±

3%;

a) Setting current Ir of overload long-delay, Allowable deviation is  ±3%;
b

)过载长延时整定时间

Tr

,动作时间精度为±

10%;

b) Setting time Tr of overload long-delay

Accuracy of action time is±10%;

c

)当实际电流

I

超过

1.15

倍的过载长延时整定电流值

Ir

时,视为过载状态。过载保护按反时限特

性进行,延时动作时间

tr=

2×Ir/I

2

×Tr

c) When actual current

s value is more than 1.15 times overload long delay setting current Ir, 

see  as  overload  status.  Overload  protection  is  carried  out  according  to  inverse  time-delay 
characteristics, delay action time tr=

2×Ir/I

2

×Tr.

3.2.2.5

短路短延时保护

  Short-circuit short-delay protection.

a

)短路短延时整定电流

Isd

,容许偏差±

3%

。设置为

off

时,控制器短路短延时保护功能关闭。

a) Setting current Is of short-circuit short-delay, Allowable deviation is  ±3%.
b

)短路短延时保护动作时间值

  Tsd

,动作时间精度为理论值±

10%

(注意:

0.1s

0.2s

这两个档

位,固有绝对误差

±

40ms

)。

b)  Action  time  value  of  short-circuit  short-delay  protection,  accuracy  of  action  time  is  ±

10%(Notes: Inherent absolute deviation is 

±

40ms for 0.1s and 0.2s these two gears).

c

)短路短延时保护分为定时限保护和反时限保护两种方案。

c)  Short-circuit  short-delay  protection  include  two  schemes  of  definite  time-delay  and  inverse 

time-delay protection.

当故障电流

1.5×Isd

I

Isd

时,具有反时限保护特性,即

tsd=

1.5×Isd/I

2

×Tsd

When fault current is 1.5×Isd

I

Isd, triggered by inversed time-delay characteristics

,即

tsd=

1.5×

2019.12.31

文件控制

Summary of Contents for NDM3EU-400

Page 1: ...ons Doc Code NDT2920257 Edition 1 Version 1 Product Model and Name NDM3EU 400 NDM3EU 400 MCCB Implementation Date 2019 08 19 Shanghai Nader Electrical Co Ltd NDM3EU 400 NDM3EU 400 Electronic MCCB Oper...

Page 2: ...19 1 Contents 2 Application Scope and Purpose 2 Description of Model 3 Technical Parameters 7 Working Environment 8 Dimensions and Installation Dimensions 9 Installation 10 Accessories 11 Operation a...

Page 3: ...and instantaneous short circuit the breaker can protect the circuit and electric power unit from being damaged 2 Description of model 1 Description of model is shown as follow Table 1 1 Table 1 Descri...

Page 4: ...and Bottom Horizontal Z2H4 Plug in Rear Connection Top Horizontal and Bottom Vertical 12 Ir A Setting current Ir A AC 250 AC 300 AC 350 AC400 AC 250 AC 300 AC 350 AC 400 13 Certification code U UL489...

Page 5: ...UPS working environment by customer Pollution class 3 Protection class IP20 Circuit breaker UL489 Certification Lug UL486E Accessories Terminal cover Double Auxiliary Contacts Shunt Trip Plug in Pre...

Page 6: ...rating Suitable combinations of current and time are adjusted by this knob so as to protect circuits and devices This operation should be done by specialized technical personnel 1 Tr Ir 2 Ir 400A Tr...

Page 7: ...lay a Ir 3 a Setting current Ir of overload long delay Allowable deviation is 3 b Tr 10 b Setting time Tr of overload long delay Accuracy of action time is 10 c I 1 15 Ir tr 2 Ir I 2 Tr c When actual...

Page 8: ...ing Environment 4 1 3 Storage condition is shown as follow Table 3 3 Table 3 Storage condition Item Specifications Ambient temperature 40 75 Relative humidity 25 95 when ambient temperature is 25 95 4...

Page 9: ...eed 50 at 40 the lowest temperature in the most humid month should not exceed 25 and the highest humidity in this month should not exceed 90 while condensation on breaker surface caused by temperature...

Page 10: ...low Table 6 6 Table 6 Installation dimensions Installation dimension Model L mm W mm H mm Y mm X mm mm Circuit breaker 277 150 123 204 48 6 Circuit breaker Plug in 357 150 155 158 70 6 2 6 Installatio...

Page 11: ...to test shunt release in the main circuit 4 12M 4 Insulation resistance should not be lower than 12M 6 2 Mounting method 3 4 Please install the breaker on flame retardants such as metal etc It can be...

Page 12: ...ram of shunt release is shown as follow Fig 5 5 Fig 5 Wiring diagram of shunt release 7 2 Auxiliary contact 7 3 Peripheral control circuits of connection of auxiliary contacts 8 Technical Data of auxi...

Page 13: ...at no short circuit or short to ground occurs between terminals of opposite polarity or exposes live parts 3 3 Check that terminal connection and fixing bolts are fastened without looseness 8 2 Commis...

Page 14: ...cludes following procedures 1 5 1 Re trip the breaker close and open the breaker use trip button to trip the breaker when it is closed repeat for 5 times to check that the breaker can reliably re trip...

Page 15: ...breaker with wet hands or electric shock would be resulted 2 2 Frequent operation will shorten service life of the breaker This product is manufactured in a sophisticated quality management system In...

Page 16: ...er can functions normally or the breaker will be replaced with a charge 10 Ordering Instruction 10 1 10 1 Customer should confirm that he or she is familiar with technical files of this product and pl...

Reviews: