NDT2920257

版次

Edition

2

Version 2

实施日期

Implementation date

2019-08-19

5

5

)短路短延时整定时间

Tsd;    Setting time of short-circuit short-delay Tsd; 

6

)短路瞬时整定电流

Ii

;

    Setting current of short-circuit instantaneous Ii; 

7

)电源指示灯

  Power;    Power light;

8

)过载指示灯

Over.    Overload light. 

控制器控制面板见下图

1

Control panel of controller is shown as follow Fig. 1:

1

控制器控制面板

Fig. 1 Control panel of controller

3.2.2 NDM3

EU

控制器控制面板各部分功能

Functions of each part in control panel of NDM3

EU

 

controller
3.2.2.1

测试端口

Test port

“TEST

”端口,

NDM3

EU

专用测试仪通过该端口与控制器相连,进行测试及调试等操作。

Through  this  “ TEST”   terminal,  special  tester  for  NDM3

EU

  is  connected  to  the  controller  to 

conduct testing and debugging etc. 
3.2.2.2

整定电流、整定时间调节旋钮

Adjusting knob for setting current 

setting time and tripping 

rating 

可通过电流、时间的调节,选择适当的组合以达到保护线路、保护设备的作用

,

此项操作应由专

业技术人员负责。

 

Suitable combinations of current and time are adjusted by this knob, so as to protect circuits and 

devices. This operation should be done by specialized technical personnel.

注:

1.Tr

表示当实际电流为

Ir

整定值的

2

倍时,断路器动作时间。

如:当

Ir

整定为

400A

Tr

整定为

100s

时,当主回路电流为

2×400A

时,断路器将持续

100s

时后断

开主回路。动作时间精度为±

10%

。在过载电流下,断路器断开主回路的时间遵循以下公式:

t=(2×Ir/I)

2

×Tr 

(其中

I

表示过载情况下,主回路实际电流值)

Notes: 1.Tr indicates the operating time of the breaker when actual current is twice of Ir setting.
E.g.: when Ir and T

r

 are set as 400A and 100s respectively, when the current in main circuit reaches 

2× 400A,  the  breaker  will  disconnect  the  main  circuit  after  lasting  for  100s.  The  time  precision  of 
action is  ±10%. Under the overcurrent, the time that the breaker disconnects the main circuit shall 
follow the following format: t=(2×Ir/I)

2

×Tr(Of which, I stands for the actual current in the main circuit 

under overcurrent.)
3.2.2.3 

指示灯

Indicator light

1

)过载指示灯

Overload light

过载指示红灯恒亮时,表示实际电流超过了过载长延时整定电流值

Ir

1.15

倍,处于过载状态,

2019.12.31

文件控制

Summary of Contents for NDM3EU-400

Page 1: ...ons Doc Code NDT2920257 Edition 1 Version 1 Product Model and Name NDM3EU 400 NDM3EU 400 MCCB Implementation Date 2019 08 19 Shanghai Nader Electrical Co Ltd NDM3EU 400 NDM3EU 400 Electronic MCCB Oper...

Page 2: ...19 1 Contents 2 Application Scope and Purpose 2 Description of Model 3 Technical Parameters 7 Working Environment 8 Dimensions and Installation Dimensions 9 Installation 10 Accessories 11 Operation a...

Page 3: ...and instantaneous short circuit the breaker can protect the circuit and electric power unit from being damaged 2 Description of model 1 Description of model is shown as follow Table 1 1 Table 1 Descri...

Page 4: ...and Bottom Horizontal Z2H4 Plug in Rear Connection Top Horizontal and Bottom Vertical 12 Ir A Setting current Ir A AC 250 AC 300 AC 350 AC400 AC 250 AC 300 AC 350 AC 400 13 Certification code U UL489...

Page 5: ...UPS working environment by customer Pollution class 3 Protection class IP20 Circuit breaker UL489 Certification Lug UL486E Accessories Terminal cover Double Auxiliary Contacts Shunt Trip Plug in Pre...

Page 6: ...rating Suitable combinations of current and time are adjusted by this knob so as to protect circuits and devices This operation should be done by specialized technical personnel 1 Tr Ir 2 Ir 400A Tr...

Page 7: ...lay a Ir 3 a Setting current Ir of overload long delay Allowable deviation is 3 b Tr 10 b Setting time Tr of overload long delay Accuracy of action time is 10 c I 1 15 Ir tr 2 Ir I 2 Tr c When actual...

Page 8: ...ing Environment 4 1 3 Storage condition is shown as follow Table 3 3 Table 3 Storage condition Item Specifications Ambient temperature 40 75 Relative humidity 25 95 when ambient temperature is 25 95 4...

Page 9: ...eed 50 at 40 the lowest temperature in the most humid month should not exceed 25 and the highest humidity in this month should not exceed 90 while condensation on breaker surface caused by temperature...

Page 10: ...low Table 6 6 Table 6 Installation dimensions Installation dimension Model L mm W mm H mm Y mm X mm mm Circuit breaker 277 150 123 204 48 6 Circuit breaker Plug in 357 150 155 158 70 6 2 6 Installatio...

Page 11: ...to test shunt release in the main circuit 4 12M 4 Insulation resistance should not be lower than 12M 6 2 Mounting method 3 4 Please install the breaker on flame retardants such as metal etc It can be...

Page 12: ...ram of shunt release is shown as follow Fig 5 5 Fig 5 Wiring diagram of shunt release 7 2 Auxiliary contact 7 3 Peripheral control circuits of connection of auxiliary contacts 8 Technical Data of auxi...

Page 13: ...at no short circuit or short to ground occurs between terminals of opposite polarity or exposes live parts 3 3 Check that terminal connection and fixing bolts are fastened without looseness 8 2 Commis...

Page 14: ...cludes following procedures 1 5 1 Re trip the breaker close and open the breaker use trip button to trip the breaker when it is closed repeat for 5 times to check that the breaker can reliably re trip...

Page 15: ...breaker with wet hands or electric shock would be resulted 2 2 Frequent operation will shorten service life of the breaker This product is manufactured in a sophisticated quality management system In...

Page 16: ...er can functions normally or the breaker will be replaced with a charge 10 Ordering Instruction 10 1 10 1 Customer should confirm that he or she is familiar with technical files of this product and pl...

Reviews: