113903G -System Installation Manual
24
CHAPTER 7
S
ETTING THE
A
UTOMATIC
S
YSTEM
T
EST
P
ARAMETERS
Several parameters in the system software determine when and how your system conducts
the automatic monthly and annual tests. Refer to “Program Functions” in the “Front Panel
Display” chapter of the system user’s Guide for a description of each test.
Starting the Unit
Before you can set the parameters, you must start the system.
WARNING
Verify that the system AC Input Circuit Breaker and Installation Switch are off.
1. Turn on the AC input at the building service panel; ensure that the systems input
breaker (CB2) is off.
2. Turn on the Battery Circuit Breaker (CB1).
3. Turn on the System AC input circuit breaker (CB2).
4. Turn on the Installation Switch (S1). Leave the loads (protected equipment) off.
Unit will run on batteries, then transfer to normal mode.