Programming
Programming Control Unit CH_SV V00
6/9
•
Release push button „AUTO“
•
The function inflatable shelter On is stored
5.2 Function inflatable shelter Off
•
Dock leveler in resting position and door closed
•
Press push button door „STOP“ 5s
•
The two LED´s on the control units are flashing at the same time
•
Release push button door „STOP“
•
Press push button „AUTO“
•
On the display appears
S01
•
Release push button „AUTO“
•
The function inflatable shelter Off is stored
6 Choose interlocking door
This part describes how to choose the function interlocking door. The function of
interlocking door has two possibilities. It is possible to use a limit switch or a photocell
for the interlocking.
The description is only for control units “105”, “105A” and “205A”.
6.1 Choose limit switch
•
Replace the cable bridge on terminal X13 on pin 4 and 5
6.2 Choose photocell
•
Insert a cable bridge on terminal X13 pin 4 and 5
Note!
The programming in the programming mode P05 has no influence on this.
7 Indication on display
description
Function
symbol
Error and maintenance
indication
Maintenance:
Symbol lights if the control
units reach the adjusted
maintenance cycles.
Error message:
Symbol flashes if an error
appears.
Error and maintenance
indication
Function:
The symbol light if the dock
leveler is not ready for use.
Error message:
Symbol flashes if an error
appears.
Error and maintenance
indication
Function:
The display shows the actual
status of the loading bay.
Error message:
The display shows the actual
error code.