background image

Programming

                                                                

                                        

Programming Control Unit CH_SV V00 

6/9

 

 

Release push button „AUTO“ 

 

The function inflatable shelter On is stored 

 

5.2  Function inflatable shelter Off 

 

Dock leveler in resting position and door closed 

 

Press push button door „STOP“ 5s 

 

The two LED´s on the control units are flashing at the same time 

 

Release push button door „STOP“ 

 

Press push button „AUTO“ 

 

On the display appears 

S01

 

 

Release push button „AUTO“ 

 

The function inflatable shelter Off is stored 

 

6  Choose interlocking door 

This part describes how to choose the function interlocking door. The function of  
interlocking door has two possibilities. It is possible to use a limit switch or a photocell  
for the interlocking. 
The description is only for control units “105”, “105A” and “205A”. 
 

6.1  Choose limit switch 

 

Replace the cable bridge on terminal X13 on pin 4 and 5 

 

6.2  Choose photocell 

 

Insert a cable bridge on terminal X13 pin 4 and 5 

 

Note!  

The programming in the programming mode P05 has no influence on this. 
 

7  Indication on display 

 
description 

Function 

symbol 

Error and maintenance 
indication 

Maintenance: 
Symbol lights if the control 
units reach the adjusted 
maintenance cycles. 
Error message: 
Symbol flashes if an error 
appears.  

 

Error and maintenance 
indication 

Function: 
The symbol light if the dock 
leveler is not ready for use. 
Error message: 
Symbol flashes if an error 
appears. 

 

Error and maintenance 
indication 

Function: 
The display shows the actual 
status of the loading bay. 
Error message: 
The display shows the actual 
error code. 

 

 

Summary of Contents for DS0290020

Page 1: ... 9 Hanover 05 08 2010 Project Control unit 105 105A i105 205A i205 i305 Project leader Document Programming control unit 105 105A i105 205A i205 i305 Version 00 Revision Copy Programming Programming button 1 Programming button 2 Programming button 3 ...

Page 2: ... Start reading 4 3 1 2 Select program no 4 3 1 3 Confirm subprogram no 4 3 1 4 Finish reading 4 3 2 FINISH PROGRAMMING 4 4 OPERATING CYCLES 5 4 1 READING OPERATING CYCLES 5 4 1 1 Start reading 5 4 1 2 Select operating cycles 5 4 1 3 Select operating cycles 5 4 2 FINISH OPERATING CYCLES 5 5 SELECT INFLATABLE SHELTER ON OFF 5 5 1 FUNCTION INFLATABLE SHELTER ON 5 5 2 FUNCTION INFLATABLE SHELTER OFF 6...

Page 3: ... no Press programming button 1 as often as necessary until the wished no Of the program is indicated counting upwards from P00 to P99 By actuating the programming button 3 it is possible to scroll backwards 2 1 3 Confirm program no If the wished program no Is indicated press the programming button 2 once The subprogram of the selected program no flashes 2 1 4 Select subprogram no Press programming...

Page 4: ...By actuating the programming button 3 it is possible to scroll backwards 3 1 3 Confirm subprogram no If the wished subprogram no Is indicated press programming button 2 once The last error message appears for example F01 after the error message appears the storage space U01 The control unit is in the program mode error message You can scroll with the programming 1 through the error list from the b...

Page 5: ...ess programming button 1 once the number starts automatically from left to right A number with 8 digits will follow At the end of the number the display shows By pressing the programming button 1 once again the number starts a second time By pressing the programming button 3 the display shows the pre selected operating cycles no 4 2 Finish operating cycles Select S10 Press programming button 3 5s ...

Page 6: ...or a photocell for the interlocking The description is only for control units 105 105A and 205A 6 1 Choose limit switch Replace the cable bridge on terminal X13 on pin 4 and 5 6 2 Choose photocell Insert a cable bridge on terminal X13 pin 4 and 5 Note The programming in the programming mode P05 has no influence on this 7 Indication on display description Function symbol Error and maintenance indic...

Page 7: ...eveler by photocell P05 U00 Motor power 2 6A U01 Motor power 3 2A U02 Motor power 3 8A U03 Motor power 4 4A U04 Motor power 5 0A U05 Motor power 5 6A U06 Motor power 6 2A U07 Motor power 6 8A U08 Motor power 7 4A U09 Motor power 8 0A U10 Motor power 8 6A U11 Motor power 9 2A P06 U00 Maintenance cycle 1000 U01 Maintenance cycle 1500 U02 Maintenance cycle 2000 U03 Maintenance cycle 2500 U04 Maintena...

Page 8: ...s U02 Automatic retraction 0 4s U03 Automatic retraction 0 6s U04 Automatic retraction 0 8s U05 Automatic retraction 1 0s U06 Automatic retraction 1 2s U07 Automatic retraction 1 4s U08 Automatic retraction 1 6s U09 Automatic retraction 1 8s U10 Automatic retraction 2 0s P14 U00 Delay door opens 0 0s U01 Delay door opens 5 0s U02 Delay door opens 10 0s U03 Delay door opens 15 0s U04 Delay door ope...

Page 9: ... over current hydraulic motor L2 U03 F03 over current hydraulic motor L3 U04 F04 phase sequence feedback signal contactor U05 F05 error Y1 defect U06 F06 error Y2 defect U07 F07 error Y1 is missing U08 F08 error Y2 is missing U09 F09 error RAM test U10 F10 error Flash Test F11 error push button F12 motor current detection defect F13 control voltage 24 V DC defect P99 U00 Factory settings hinged li...

Reviews: