15
3-6. LCD Setting
There are three parameters to set up the UPS. Refer to following diagram.
Parameter 1: It’s for program alternatives. Refer
to below table for the programs to set up.
Parameter 2 and parameter 3 are the setting
options or values for each program.
Note: Please select “Up” or “Down” button to
change the programs or parameters.
Programs available list for parameter 1:
Code Description
Bypass
AC
CVCF Battery Battery Test
01
Output voltage
Y
02
Output frequency
Y
03
Voltage range for bypass
Y
04
Frequency range for bypass
Y
05
Reserved
06
Reserved
07
Reserved
08
Bypass mode setting
Y
Y
09
Battery maximum discharge time setting
Y
Y
Y
Y
Y
10
Reserved
11
Reserved
12
Reserved
13
Battery voltage Calibration
Y
Y
Y
Y
Y
14
Charger voltage adjustment
Y
Y
Y
Y
Y
15
Inverter voltage Calibration
Y
Y
Y
16
Reserved
17
Reserved
18
Charger maximum current setting
Y
Y
Y
Y
Y
19
Battery capacity and groups setting
Y
Y
Y
Y
Y
20
Backup time calibration
Y
Y
Y
Y
Y
*Y means that this program can be set in this mode.
01: Output voltage
Interface
Setting
Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208: Presents output voltage is 208Vac
220: Presents output voltage is 220Vac
230: Presents output voltage is 230Vac
240: Presents output voltage is 240Vac
Parameter 1
Parameter 2
Parameter 3