Technical Data
User manual 9000-41011-0200000_hdb_en_20
47 / 92
4.5.2.3
Electrical safety
4.5.2.4
EMC-interference
4.5.2.5
EMC-immunity
4.5.3
Protection
4.5.3.1
Device protection
Parameter
Conditions
Value
Degree of protection
EN 60529
IP20
Pollution degree
2
Overvoltage category
III
Insulation voltage
input-output
Type testing / routine check test
50 V
Parameter
Conditions
Value
Radio interference field strength
housing
EN 61000-6-3
Industrial and residual areas
Conducted emission
DC inputs and outputs
EN 61000-6-3
Industrial and residual areas
Parameter
Conditions
Value
Fast transients / burst
DC inputs and outputs
EN 61000-6-2,
EN 61000-4-4
±2 kV / 5 kHz
Fast transients / burst
signal connections
EN 61000-6-2,
EN 61000-4-4
±2 kV / 5 kHz
Surge voltage
DC inputs and outputs
EN 61000-6-2,
EN 61000-4-5
±0.5 kV DM
Electrostatic discharge housing
EN 61000-6-2,
EN 61000-4-2
Contact ± 4 kV; air ± 8 kV
Conducted HF
DC connections
EN 61000-6-2,
EN 61000-4-6
10 VRMS; 1 kHz,
80 % AM sine
Conducted HF
control terminals
EN 61000-6-2,
EN 61000-4-6
10 VRMS; 1 kHz,
80 % AM sine
High-frequency electrical
RF fields housing
EN 61000-6-2,
EN 61000-4-3
80 MHz ... 1.0 GHz: 10 V/m
Parameter
Conditions
Value
Short circuit protection
Short circuit-proof
Overvoltage protection input
Suppressor diode 36 V
Overvoltage protection output
Suppressor diode 36 V
Overload protection
See Disconnecting charac-
teristics
Voltage monitoring
No
Safety fuse variants: Internal fuse (Fail-Safe-Element), per channel
Art.-No.
Designation
Tripping current
Fuse
9000-41011-0200000 Mico Pro fix 1.2 2 A
Safety fuse
4 A (T) time-lag fuse
9000-41011-0400000 Mico Pro fix 1.4 4 A
Safety fuse
4 A (T) time-lag fuse
9000-41011-0600000 Mico Pro fix 1.6 6 A
Safety fuse
6,3 A (T) time-lag fuse