background image

MGC-02030N page 1 of 8

Installation and Operation Manual for 
Generator Control System

®

MGC2000 

MGC-02030N

Effective 04-03

Section 75

00-02-0505

Description

The compact and powerful MGC2000 generator control system features a
unique, simple-to-install and setup design and enhanced operation.
The control method for the MGC2000 may be specified for using either the
AS3000 Autostart automatic controller or the 518APH electrically tripped
annunciator method. 
The system is available in 2 basic configurations: 

1. MGC2000 

features mechanical gages: 

MGC2000-A

Automatic Control:

with AS3000 Generator Controller.

MGC2000-M

Manual Control:

with 518APH annunciator control.

Both configurations include standard AC voltmeter, AC ammeter, and
frequency meter. Available for single phase, standard three phase, and three
phase re-configutable generators.

2. MGC2000E

features electric gages: 

MGC2000E-A

Automatic Control:

with AS3000 Generator Controller.

MGC2000E-M

Manual Control:

with 518APH annunciator control.

Both configurations include standard AC voltmeter, AC ammeter, and
frequency meter. Available for single phase, standard three phase, and three
phase re-configutable generators.

System Specifications

Pressure gage:

100°psi (680 kPa) [7 bar] 

Mechanical gage pressure connection: 

1/8" NPT. 

Electric gage pressure connection:

2-wire.

Temperature gage:

0-250°F (121°C)

Mechanical gage temperature connection: 

12ft. (3.67 m) capillary tubing

and sensing bulb. 

Electric gage temperature connection:

2-wire.

Enclosure: 

16 Ga CRS powder coated.

Optional NEMA 4X Type Enclosure: 

Water and dust tight indoor/outdoor enclosure intended to protect
enclosed equipment against splashing, seepage, falling or hose-directed
water and severe external condensation.

AC Meters:

AC ammeter and an AC voltmeter and a frequency meter are

standard features. Ranges must be specified.

Single or Three phase:

Specify.

Control Method: 

may be specified:

- AS3000 Autostart automatic controller or
- 518APH Annunciator control method. 

NOTE:

Autostart method is highly recommended.

DC Voltage:

12 or 24 volt DC voltage must be specified.

Power supply:

• Continuous voltage range: 8-35 VDC
• Brown out voltage < 5 VDC for 2 secs (recovery to 8V)
• Blackout voltage: 0V for 50mS (from 10V, recovery to 5V)
• Overvoltage withstand: 50 VDC for 5 seconds (to SAEJ1810 load dump

immunity

• Reverse voltage withstand: 100 VDC continuous

Current consumption (standby):

50mA

Current consumption (max):

500mA (plus output loads)

DC Inputs:

• Pressure, coolant temperature
• Closed to negative DC (±3V) on fault auxiliary and charger faults
• Remote start positive open from positive DC to start
• Remote start negative  close to negative DC (±3V) to start DC (±3V) to

activate DC input protection ±50 VDC max.

continued on next page

Please read the following information before installing

.  

A visual inspection of this product for damage during shipping is

recommended before mounting. It is your responsibility to have a qualified person install this unit and make sure it conforms to
NEC and local codes.

GENERAL INFORMATION

WARNING

BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT

Disconnect all electrical power to the machine.

Make sure the machine cannot operate during installation.

Follow all safety warnings of the machine manufacturer.

Read and follow all installation instructions.

WARNING: Do not bundle AC and DC wiring together. It is required
to use separate conduit runs and keep apart by at least 2 inches. 

Summary of Contents for MGC2000

Page 1: ...ded to protect enclosed equipment against splashing seepage falling or hose directed water and severe external condensation AC Meters AC ammeter and an AC voltmeter and a frequency meter are standard...

Page 2: ...m 6 81 in 173 mm kPa PSI 50 75 100 0 0 25 350 700 kPa PSI 50 75 100 0 0 25 350 700 QUARTZ HOURS kPa PSI 50 75 100 0 0 25 350 700 OFF STOP REMOTE START DEMAND OVERCRANK ENGINE RUNNING LOW OIL PRESSURE...

Page 3: ...FF STOP REMOTE START DEMAND OVERCRANK ENGINE RUNNING LOW OIL PRESSURE BATTERY CHARGER FAIL A C VOLTS A C AMPERES HERTZ HIGH ENGINE TEMPERATURE PLANT FAIL AUXILIARY INPUT OVERSPEED MANUAL START AUTO ST...

Page 4: ...protection are provided by either the AC frequency input the magnetic pickup input or the two ground to activate inputs labeled crank disconnect and overspeed AC Voltage AC Voltage is measured via a s...

Page 5: ...M 12 or VM 24 MGC2000 Typical Wiring WARNING Turn the power source off before attempting to perform the wiring operation Do not bundle AC and DC wiring together It is required to use separate conduit...

Page 6: ...C2000E Typical Wiring WARNING Turn the power source off before attempting to perform the wiring operation Do not bundle AC and DC wiring together It is required to use separate conduit runs and keep a...

Page 7: ...esent when the engine is past crank disconnect speed b If the application is using magnetic pickup crank disconnect overspeed make sure that the wiring is correct and that the output is at least 3Vrms...

Page 8: ...ground sender ES2PM 2 wire ungrounded sender EST 1 wire to ground sender ES2T 2 wire ungrounded sender ESDT 2 wire ungrounded sender drives two 2 gages Thru 100 psi 689 kPa 6 89 bar Ranges above 100...