background image

FW Murphy – CANdrive installation and operation                                                                           00-02-0618   revision F   7

th

 January 2011   p4/4 

 

Operation 

Gauge driver outputs 

The gauge outputs operate when CANdrive reads valid J1939 
data for engine speed, oil pressure and coolant temperature.  
If CANdrive stops receiving valid data, the gauge outputs  
are maintained at the last known value for approximately  
5 seconds, after which time the outputs turn off. 

Indicating LEDs 

All standard models have a green CAN LED. A flashing  
CAN LED indicates that CANdrive is powered, but is not 
receiving any J1939 data. A constantly lit CAN LED indicates  
power on with good CANbus connection and J1939 activity. 
(Note: J1939 activity can originate from ANY device on the 
CANbus network, and may not necessarily be valid data from 
the engine ECU.) 

Model CDV300R has additional LEDs for indication of J1939-
transmitted engine faults. CANdrive responds to single  
DM1 (active fault code) messages that contain SPN (Suspect 
Parameter Number), FMI (Fault Mode Indicator) and 
warning/stop lamp data. CANdrive also reads multi-packet 
transport messages broadcast using the BAM protocol. 

Typically, LEDs light continuously to indicate a shutdown fault, 
and flash to indicate a (non-shutdown) warning fault: 

LED Mode Fault 

J1939 

SPN FMI

 

On 

Low oil pressure shutdown 

100

Flashing  Low oil pressure warning 

100 > 1

 

On Coolant 

temperature 

shutdown 

110

Flashing  Coolant temperature warning  110 > 0

 

On Overspeed 

shutdown 

190

Flashing  Overspeed warning 

190 > 0

 

Reserved for future use 

- - 

  - 

Reserved for future use 

- - 

 

Flashing Warning 

fault 

- - 

 

Flashing Shutdown 

fault 

- - 

CANdrive can handle up to 8 simultaneous faults at  
one time: additional fault messages are not registered.  
When a fault becomes inactive and is no longer broadcast,  
the appropriate LED goes out after approximately 2 seconds. 

Maintenance and Warranty 

CANdrive has no user-serviceable parts. Maintenance is 
therefore limited to the following preventative checks: 

x

 

Check that electrical connections are secure. 

x

 

Check that the CANdrive is securely mounted, and  
kept free from ingress of water or build up of excessive 
dust/dirt. The front label and casing may be wiped with  
a clean, damp cloth. Do not use cleaning solvents. 

CANdrive is supplied with a 2 year warranty on parts and 
workmanship. In the event of a fault or technical query, please 
contact your Murphy representative for technical support.  

Further information 

Document Description 

00-02-0251 EG(S)21 series electric gage installation 

00-02-0258 AT series tachometer installation 

 

Operation and Maintenance 

FW MURPHY 

P.O. Box 470248, Tulsa, Oklahoma 74147 USA 
+1 918 317 4100   Fax: +1 918 317 4266 
E-mail: [email protected] 

INDUSTRIAL PANEL DIVISION 

Fax: +1 918 317 4124 
E-mail: [email protected] 

MURPHY POWER IGNITION 

Website: www.murphy-pi.com 

CONTROL SYSTEMS AND SERVICES DIVISION 

P.O. Box 1819, Rosenberg, Texas 77471 USA 
Phone: +1 281 633 4500   Fax: +1 281 633 4588 
E-mail: [email protected] 

FRANK W. MURPHY LTD. 

Church Road, Laverstock,  
Salisbury, SP1 1QZ, United Kingdom 
Tel: +44 1722 410055 
Fax: +44 1722 410088 
E-mail: [email protected] 
Web: www.fwmurphy.co.uk 

COMPUTRONIC CONTROLS 

41 – 46 Railway Terrace, Nechells,  
Birmingham, B7 5NG, United Kingdom 
E-mail: [email protected] 
Web: www.computroniccontrols.com 

FW MURPHY INSTRUMENTS (HANGZHOU) CO., LTD. 

77 23

rd

 Street, Hangzhou Economic & Technological Development Area 

Hangzhou, Zhejiang, 310018, China 
Phone: +86 571 8788 6060   Fax: +86 571 8684 8878 
E-mail: [email protected] 
 

 

 

 

 

Reviews: