ML180-MLT350 Dehumidifiers
190TGB-1034-A
7 Appendix 1- Options
31
The push buttons have the following main functions:
SET
Display/change the required value and reset alarm
Increase value
Decrease value
% RH
Display position of control steps for reactivation heater ( 0=off; 1=on).
During normal operation and in any position of the mode switch the
current relative air humidity is displayed.
7.4.2 Display / change setpoint of relative humidity
1. Press/release
SET
button. The point on the bottom right-hand
corner of the display starts to flash indicating current setpoint. The
display returns after approx. 20 sec.automatically to normal i.e.
displaying current relative air humidity.
2. Press and hold
SET
button and current setpoint is steadily
displayed. If the button is released again the display starts to flash
before it automatically returns to normal.
3. Press and hold
SET
button and press simultaneously
or
buttons in order to set the required setpoint.
4. Release
SET
button and display starts to flash indicating the new
setpoint before it returns automatically to normal i.e. displaying
current relative air humidity.
7.4.3 Display / change of other parameters
The control setpoint is pre-set at the factory to 50 %RH. In addition to
the setpoint a number of internal settings are also possible, e.g.
differential, sensor offset and setpoint range,
see Table 3-1.
1. Press and hold
for more than 10 sec. to display the parameter
menu. The top and bottom segment in the left-hand display
characters start to flash. Parameter 10 is displayed. Release
.
2. Press
or
3. Press and hold
SET
button in order to display the current value of
the selected parameter.
4. Press and hold
SET
button and press
or
to increase or
decrease the parameter value.
5. Release
SET
button. The new parameter settings are automatically
saved. The display returns after approx. 20 sec. automatically to
normal, i.e. displaying current relative air humidity.
Summary of Contents for ML180
Page 2: ......
Page 34: ...ML180 MLT350 Dehumidifiers 34 7 Appendix 1 Options 190TGB 1034 A ...
Page 35: ......