9.4. Technical data
Process air
(1)
Free-blowing air 50/60 Hz (m³/h)
225
Rated airflow at 60 Pa (m³/h)
190
Max. static pressure 50/60 Hz (Pa)
300
Fan motor power (kW)
0,09
Reactivation air
(1)
Rated airflow at 90 Pa (m³/h)
30
Max. static pressure (Pa)
260
Fan motor power (kW)
-
(2)
Reactivation air heater
Heater power (kW)
0,84
Factory set reactivation temperature (Rt) limit (°C)
130
Factory set wet air temperature (Wt) limit (°C)
75
Temperature increase across heater (°C)
100
Other
Sound pressure level, free blowing process fan (dBA)
58
IEC protection class (unit)
IP33
IEC protection class (electrical panel)
IP54
Fan motor winding insulation class
Class B
Drive motor winding insulation class
Class B
Rotor type
HPS
Environmental conditions
Operating temperature (°C)
-20... +40
Maximum installation altitude, above sea level (m)
2000
Transport and storage temperature (°C)
-20... +70
Total power, voltage and current
Voltage (V)
115
230
Frequency (Hz)
50/60
50/60
Total power (W)
950
950
Current (A)
8,2
4,1
Fuse
3 AG, 250 VAC, 10
A Slow
3 AG, 250 VAC, 6 A
Slow
(1)
The specified performance is based on 20 °C and air density of 1.2 kg/m³.
(2)
The same fan is used for process air and reactivation air.