6
MUP-16-W9 /MUP-18-W9
Model
MUP-16-W9
MUP-18-W9
Power supply
V/Ph/Hz
220-240/1/50
Air flow (H/M/L)
m
3
/h
862/741/634
979/849/717
CFM
507/435/372
575/499/421
Cooling
1
Capacity (H/M/L)
kW
4.47/3.98/3.48
4.87/4.26/3.79
Water flow rate(H/M/L)
m
3
/h
0.77/0.68/0.61
0.85/0.72/0.65
Water pressure drop(H/M/L)
kPa
41.17/33.54/27.05
50.68/39.47/33.66
Power input(H/M/L)
W
26/18/13
38/26/18
Heating
2
Capacity (H/M/L)
kW
4.84/4.23/3.62
5.26/4.68/3.96
Water flow rate(H/M/L)
m3/h
0.84/0.73/0.64
0.89/0.80/0.68
Water pressure drop(H/M/L)
kPa
36.82/33.83/26.26
47.12/42.75/32.95
Power input(H/M/L)
W
22/16/12
33/23/16
Heating
3
Capacity (H/M/L)
kW
5.68/4.94/4.24
6.31/5.57/4.77
Water flow rate(H/M/L)
m
3
/h
0.77/0.68/0.61
0.85/0.72/0.65
Water pressure drop(H/M/L)
kPa
43.74/29.69/23.98
51.65/36.3/30.3
Power input(H/M/L)
W
23/16/12
33/23/16
Sound pressure level (H/M/L)
dB(A)
38/34/30
44/40/35
Rated current
A
0.32
0.39
Fan motor
Type
DC Motor
DC Motor
Quantity
1
1
Fan
Type
Tangential fan
Tangential fan
Quantity
1
1
Coil
Row
2
Max. Working pressure
MPa
1.6
Coil length x height
mm
785x26.74
Fin spacing
mm
1.5
Fin type
Hydrophilic aluminium
Number of circuits
7
Diameter
mm
Φ7
Body
Net dimensions (W×H×D)
mm
1072×315×237
1072×315×237
Packing size (W×H×D)
mm
1180×415×315
1180×415×315
Net weight
kg
15.1
14.9
Gross weight
kg
19
18.6
Pipe connection
Water inlet/outlet pipe
inch
G3/4
Drain pipe
mm
ODΦ20
Notes:
Based on Eurovent conditions:
H: High fan speed; M: Medium fan speed; L: Low fan speed.
1: Cooling mode (2 and 4-pipe coil): entering air temperature 27°C DB/19°C WB, entering/leaving water temperature 7°C /12°C.
2: Heating mode (1): (2-pipe coil): entering air temperature 20°C DB, entering/leaving water temperature 45/40°C.
3: Heating mode (2): (2-pipe coil): entering air temperature 20°C DB, enter water teperaure/water flow 50°C.
(same water flow as in standard rating condition in cooling)