mundoclima CL23190 Installation Manual Download Page 15

Outside diameter

A(mm)

Max

8.7

Φ6.4mm

Φ9.5mm

Φ12.7mm

Φ15.9mm

Φ19.1mm

12.4

15.8

19.0

23.3

8.3

12.0

15.4

18.6

22.9

Min

Table.12-1

Fig.12-4

When the pumping has finished, close the Lo-lever of the manifold 
valve completely and turn off the vacuum pump.

When you have pumped for over 15 minutes, please confirm 
that the indicator of  multimeter is on  -1.0X105Pa (-76cmHg)

Loosen  and remove the quadrangle cover of stop valves A and 
B to open stop valve A and B completely, then fasten them.

Disassemble the charge hose from the repair-mouth of stop 
valve A, and  fasten the nut.

Turn on the vacuum pump. At  the beginning of pumping, loosen 
the maintenance terminator nut of stop valve B a little to check 
whether the air comes in (the sound of the pump changes, and the in-
dicator of compound meter turns below zero). Then fasten the 
nut.

The necessary filling amount of refrigerant  

Refrigerant volume to be added is calculated according to outdoor 
unit installation manual .Be sure to add refrigerant measuring 
by a scale. L: The length of the pipe

Please record the quantity added and store it carefully for future 
maintenance.

Expel the air with a vacuum pump (Refer to 

Fig.12-4

) (Please 

refer to its manual for the way of using manifold valve)

Loosen and remove the maintenance nuts of stop valves A and 
B, and connect the charge hose of the manifold valve with the 
maintenance terminator of stop valve A.  (Be sure that stop 
valves A and B are both closed)

Connect the joint of the charge hose with the vacuum pump.

Open the Lo-lever of the manifold valve completely.

Torque

Tubing size

14.4~17.2N.m

32.7~39.9N.m

49.5~60.3N.m

61.8~75.4N.m

92.7~118.6N.m

Φ6.4mm

Φ9.5mm

Φ12.7mm

Φ15.9mm

Φ19.1mm

Table.12-2

Fasten the nut
Put the connecting tubing at the proper position, wrench  the  
nuts  with  hands  then  fasten  it  with a wrench. (Refer to
 

Fig.12-4)

Too large torque will harm the bellmouthing and too small will 
cause leakage.  Please determine  the torque according to 
Table.12-2.

Install indoor unit drain pipe
The outlet has PTI screw bread, Please use sealing materials 
and pipe sheath (fitting) when connecting PVC pipes. 

      

13.   CONNECT THE DRAIN PIPE

All the stop valves should be opened before test operation. 
Each air conditioner has two stop valves of different sizes on 
the side of the outdoor unit which operate as Lo-stop value, respec-
tively. (Refer to 

Fig.10-6

)

Flare nut

Stopper

Cap

Valve body 

Valve stem 

Fig.12-6

Fig.12-5

-76 cmHg

Lo-lever

Hi-lever

Charge hose

Charge hose

Vacuum pump

Lo-lever

Manifold valve

Multi-meter

Pressure meter

The drain pipe of indoor unit must be heat insulated, or it will 
condense dew, as well as the connections of the indoor unit.

Hard PVC binder must be used for pipe connection, and make 
sure there is no leakage.

CAUTION

maintenance of motor

˖

0 1 2

F

3

E

4

D

5

C

6

B

7

A

89

Installation manual

Duct 100% fresh air

14

Summary of Contents for CL23190

Page 1: ...MVD Duct 100 fresh air Installation manual English CL23190 to CL23194 www mundoclima com...

Page 2: ...n or a place full of oil steam There is strong electromagnetic wave CONTENTS PAGE INSTALLATION PRECAUTION 1 INSTALLATION PLACE 1 ACCESSORIES 2 INDOOR UNIT INSTALLATION 2 INSTALLATION SPACE 10 HIGH STA...

Page 3: ...Especially in case there is a ceiling position the refrigerant pipes drain pipes indoor outdoor lines to the connection places before hanging up the machine The installation of hanging screw bolts In...

Page 4: ...e air in grill Anti clockWise the bolts as indicated in follow figure sketch Then pull down the air in grill Pipe Connection The static pressure outside the unit is 200Pa the length of the air pipe at...

Page 5: ...NGE 400 AIR INTAKE DUCT FLANGE 4 12 25 OBLONG SUSPENTION BOLT HOLES AIR INTAKE 4 5 HOLES FOR AIR OUTLET DUCT CONNECTION 400 65 15 37 638 600 17 253 638 14 136 69 90 15 50 800 1148 137 125 11 28 169 69...

Page 6: ...nd then take off the tray as figure showed in Fig 4 11 3 Take off the tray along the direction of the arrow show in Fig 4 11 4 Clean the tray and evaporator 5 Re install the unit follow the reverse ab...

Page 7: ...12 2 Remove the all 11 screw from fixed Safety Drain Tray and then take off the tray as figure showed in Fig 4 12 3 Take off the tray along the direction of the arrow show in Fig 4 13 4 Clean the tray...

Page 8: ...rs to take off the fan assembly 3 Refer to Fig 4 15 horizontal pushing the fan assembly until it cannot not move any further and then lift up slightly and take down to remove it 4 After motor maintena...

Page 9: ...3 Refer to Fig 4 16 remove all 4 bolts from fan assembly see Fig 4 17 according to which orders to take off the fan assembly 4 Refer to Fig 4 17 horizontal pushing the fan assembly until it cannot no...

Page 10: ...r intake Air outlet Refrigerant pipe flared connection 16 5 8 Refrigerant pipe flared connection 9 52 3 8 Air outlet duct flange 4 12 25 oblong suspention bolt holes Electrical parts box Entrances and...

Page 11: ...f motor 1 2 3 4 5 As figure dismounting the bolt of bottom get down the bottom cover plate As figure dismounting 6 bolts in the front plate Support the fan subassembly from the bottom then litter up g...

Page 12: ...ut side Connecting air duct and blowout flange Attached by main body Use aluminum adhesive tapes etc to seal the connecting parts of the blowout flange and fan duct for avoiding air leakage Use the bo...

Page 13: ...the wooden building then it must do the electronic insulating for the fan duct and the wall Check whether the height drop between the indoor unit and outdoor unit the length of refrigerant pipe and th...

Page 14: ...Bind the connecting pipe and the cables together tightly with binding tapes Do not let air in which will cause water leakage by condensation Pass the bound connecting pipe through the wall conduit fro...

Page 15: ...onnect the charge hose of the manifold valve with the maintenance terminator of stop valve A Be sure that stop valves A and B are both closed Connect the joint of the charge hose with the vacuum pump...

Page 16: ...wiring mm2 Indoor outdoor connecting wiring mm2 Ground wiring Weak electric signal Power Phase 1 Phase 220 240V 50Hz 208 230V 60Hz Frequency and volt Table 14 1 A disconnection device having an air ga...

Page 17: ...32 5 6833 1 2 5 1 INDOOR UNIT 72 1 225 287 225 200 86 Fig 14 3 Terminal board diagram Please refer to the indoor unit wiring diagram for the detailed wiring In accord with the communication wiring te...

Page 18: ...er 11200W 4 0HP 12500W 5 0HP 14000W 5 0HP For set horsepower Note The horsepower has been set before leaving the factory anyone can t modify it except the maintenance person 6 5 4 3 2 1 0 8 9 2200W 0...

Page 19: ...After the malfunctions disappear it restores automatically If the malfunctions can t be solved in three min all the indoor alarm lamps flash at 0 5Hz Turn off the power to restore When the indoor unit...

Page 20: ...Fig 18 4 Fig 18 2 Fig 18 1 Low pressure pipe Hi pressure pipe Electric throttle part Liquid branch pipe Gas branch pipe 10m Low pressure pipe Hi pressure pipe Liquid branch pipe Gas branch pipe 9 5 1...

Page 21: ...air conditioner under the mode of COOLING with the remotecontroller andcheckthefollowingpointsperthe Owner s Manual If there is any malfunction please resolve it through chapter Troubles And Causes i...

Page 22: ...ASK FOR MORE INFORMATION Phone 34 93 446 27 80 eMail info mundoclima com TECHNICAL ASSISTANCE Phone 34 93 652 53 57 MVD www mundoclima com...

Reviews: