Expel  the air (refer to the “Expel The Air”) after connecting the 
refrigerant pipe with the indoor unit and the outdoor unit.Then 
fasten the nuts at the repair-points.

Notices For Benable pipe.

The bending angle should not exceed 90

ć

Bending position is preferably in the bendable pipe. The larger 
the better it is .

Do not bend the pipe more than three times.

Bend the connecting pipe of small wall thickness.

Cut out a desired concave at the bending part of the insulating 
pipe.

12.   REFRIGERANT PIPE CONNECTION

12.1  Expel The Air

Bend the pipe with thumb

Make the ends
straight

Fig.11-3

Fig.11-2

Then, open  the stem of stop valves of the outdoor unit to make 
the  refrigerant  pipe connecting the indoor unit with the outdoor 
unit fluently flow.

Be sure of no leakage by checking it with leak detector or soap  
water.

Cover the joint of the connecting pipe to the indoor unit with the 
sound proof/insulating sheath  (fittings),  and bind it well with the 
tapes to prevent leakage.

Locate The Pipe

Drill a hole in the wall (suitable just for the size of the wall conduit, 
90mm in general), then set on the fittings such as the wall conduit 
and its cover.

Bind the connecting pipe and the cables together tightly with 
binding tapes. Do  not let air  in, which will cause water leakage 
by condensation.

Pass the bound connecting pipe through the wall conduit from 
outside.  Be careful of the pipe all ocation to do no damage to the 
tubing.

Connect the pipes.

Flaring

Cut a pipe with a pipe cutter.

Insert a flare nut into a pipe and flare the pipe.

Then expose the pipe(cover it with tapes after bending).

To prevent collapsing of deforming, please bend the pipe at its 
biggest radius.

Use bender to get a small radius pipes.

Use the market brass pipe.
Be sure to use the same insulating materials when you buy the 
brass pipe. (More than 9mm thick) 

Use frozen oil

Fig.11-1

Check all the joints with the leak detector or soap water. (See 

Fig.10-6

 as a reference illustration)

      

Be sure to with insulating materials cover all the exposed parts 
of the flare pipe joints and refrigerant pipe on the liquid-side and 
the gas-side. Ensure that there is no gap between them.

Incomplete insulation may cause water condensation.

12.2   Check The Leakage

12.3   Insulation

B

A

D

C

Check-point of indoor unit

Check-point of outdoor unit

            A. Lo-stop valve            B. Hi-stop valve
            C,D. Joints of the connecting pipe to the indoor unit.

Fig.12-2

Fig.12-1

90

lean

crude burr

A

90+4

45+2

Fig.12-3

maintenance of motor

˖

0 1 2

F

3

E

4

D

5

C

6

B

7

A

89

Installation manual

Duct 100% fresh air

13

Summary of Contents for CL23190

Page 1: ...MVD Duct 100 fresh air Installation manual English CL23190 to CL23194 www mundoclima com...

Page 2: ...n or a place full of oil steam There is strong electromagnetic wave CONTENTS PAGE INSTALLATION PRECAUTION 1 INSTALLATION PLACE 1 ACCESSORIES 2 INDOOR UNIT INSTALLATION 2 INSTALLATION SPACE 10 HIGH STA...

Page 3: ...Especially in case there is a ceiling position the refrigerant pipes drain pipes indoor outdoor lines to the connection places before hanging up the machine The installation of hanging screw bolts In...

Page 4: ...e air in grill Anti clockWise the bolts as indicated in follow figure sketch Then pull down the air in grill Pipe Connection The static pressure outside the unit is 200Pa the length of the air pipe at...

Page 5: ...NGE 400 AIR INTAKE DUCT FLANGE 4 12 25 OBLONG SUSPENTION BOLT HOLES AIR INTAKE 4 5 HOLES FOR AIR OUTLET DUCT CONNECTION 400 65 15 37 638 600 17 253 638 14 136 69 90 15 50 800 1148 137 125 11 28 169 69...

Page 6: ...nd then take off the tray as figure showed in Fig 4 11 3 Take off the tray along the direction of the arrow show in Fig 4 11 4 Clean the tray and evaporator 5 Re install the unit follow the reverse ab...

Page 7: ...12 2 Remove the all 11 screw from fixed Safety Drain Tray and then take off the tray as figure showed in Fig 4 12 3 Take off the tray along the direction of the arrow show in Fig 4 13 4 Clean the tray...

Page 8: ...rs to take off the fan assembly 3 Refer to Fig 4 15 horizontal pushing the fan assembly until it cannot not move any further and then lift up slightly and take down to remove it 4 After motor maintena...

Page 9: ...3 Refer to Fig 4 16 remove all 4 bolts from fan assembly see Fig 4 17 according to which orders to take off the fan assembly 4 Refer to Fig 4 17 horizontal pushing the fan assembly until it cannot no...

Page 10: ...r intake Air outlet Refrigerant pipe flared connection 16 5 8 Refrigerant pipe flared connection 9 52 3 8 Air outlet duct flange 4 12 25 oblong suspention bolt holes Electrical parts box Entrances and...

Page 11: ...f motor 1 2 3 4 5 As figure dismounting the bolt of bottom get down the bottom cover plate As figure dismounting 6 bolts in the front plate Support the fan subassembly from the bottom then litter up g...

Page 12: ...ut side Connecting air duct and blowout flange Attached by main body Use aluminum adhesive tapes etc to seal the connecting parts of the blowout flange and fan duct for avoiding air leakage Use the bo...

Page 13: ...the wooden building then it must do the electronic insulating for the fan duct and the wall Check whether the height drop between the indoor unit and outdoor unit the length of refrigerant pipe and th...

Page 14: ...Bind the connecting pipe and the cables together tightly with binding tapes Do not let air in which will cause water leakage by condensation Pass the bound connecting pipe through the wall conduit fro...

Page 15: ...onnect the charge hose of the manifold valve with the maintenance terminator of stop valve A Be sure that stop valves A and B are both closed Connect the joint of the charge hose with the vacuum pump...

Page 16: ...wiring mm2 Indoor outdoor connecting wiring mm2 Ground wiring Weak electric signal Power Phase 1 Phase 220 240V 50Hz 208 230V 60Hz Frequency and volt Table 14 1 A disconnection device having an air ga...

Page 17: ...32 5 6833 1 2 5 1 INDOOR UNIT 72 1 225 287 225 200 86 Fig 14 3 Terminal board diagram Please refer to the indoor unit wiring diagram for the detailed wiring In accord with the communication wiring te...

Page 18: ...er 11200W 4 0HP 12500W 5 0HP 14000W 5 0HP For set horsepower Note The horsepower has been set before leaving the factory anyone can t modify it except the maintenance person 6 5 4 3 2 1 0 8 9 2200W 0...

Page 19: ...After the malfunctions disappear it restores automatically If the malfunctions can t be solved in three min all the indoor alarm lamps flash at 0 5Hz Turn off the power to restore When the indoor unit...

Page 20: ...Fig 18 4 Fig 18 2 Fig 18 1 Low pressure pipe Hi pressure pipe Electric throttle part Liquid branch pipe Gas branch pipe 10m Low pressure pipe Hi pressure pipe Liquid branch pipe Gas branch pipe 9 5 1...

Page 21: ...air conditioner under the mode of COOLING with the remotecontroller andcheckthefollowingpointsperthe Owner s Manual If there is any malfunction please resolve it through chapter Troubles And Causes i...

Page 22: ...ASK FOR MORE INFORMATION Phone 34 93 446 27 80 eMail info mundoclima com TECHNICAL ASSISTANCE Phone 34 93 652 53 57 MVD www mundoclima com...

Reviews: