9.4 Operation Modes and Functions
9.4.1 Fan mode
(
1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled,
and no setting temperature is displayed.
(3) Indoor fan can be set to
high/med/low/auto.
(4) The louver operates same as in cooling
mode.
(5) Auto fan:
a
b
c
d
T1
e
9.4.2 Cooling Mode
9.4.2.1 Compressor running rules
When T1-Td<
ΔT -2
℃
, the compressor will stop,
when T1
—
Td >
ΔT -0.5
℃,
the compressor will
be activated.
ΔT is the programmed parameter of
temperature compensation.
When the AC run in mute mode, the
compressor will run with low frequency.
When the current is more than setting value,
the current protection function will be activated,
and the compressor will stop.
9.4.2.2 Outdoor fan running rules
The outdoor unit will be run at different fan
speed according to T4.
For different outdoor units, the fan speeds are
different.
T4
A+
A
B
C
D
E
9.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time
and the speed can be selected as high,
medium, low and auto.
When the setting temp. is reached, if the
compressor stop running, indoor fan motor will
run in Minimum speed or setting speed.
The indoor fan is controlled as below:
Setting fan
speed
Actual fan speed
H+(H+=H+G)
A
H(=H)
B
C
M+(M+=M+Z)
D
M(M=M)
E
F
L+(L+=L+D)
G
L(L=L)
H
I
T1-Td
℃
(°F)
L
L-(L-=L-D)
H
H-(H-=H-G)
M
M-(M-=M-Z)
The auto fan acts as below rules:
a
b
c
d
T1
e
Summary of Contents for MUPR-H6
Page 8: ...8 For MUPR 09 H6 UI20015...
Page 9: ...9 For MUPR 12 H6 UI20016 For MUPR 18 H6 UI20017...
Page 10: ...10 For MUPR 24 H6 UI20018 3 2 Outdoor Unit...
Page 11: ...11 For MUPR 09 H6 UE20015...
Page 12: ...12 For MUPR 12 H6 UE20016 MUPR 18 H6 UE20017...
Page 13: ...13 For MUPR 24 H6 UE20018...