DIRECT VENT APPLICATIONS

7

PART VI. DIRECT VENT APPLICATIONS

When using MUNCHKIN OFB- Models 3MOFB, 4MOFB AND 5MOFB on 'sealed' or 'direct'
vented systems, they must be ordered from the factory with a Direct Vent System manu-
factured by Flex-L International, Inc. whose part numbers are at the end of this section.

Figure 3

In addition to all of the previous stated information regarding Natural Draft Applications and
Mechanical Draft Applications the following additional instructions for Direct Vent
Applications must be followed while referencing 

Figure 3;

• The maximum wall thickness should be no more than 14". Contact HEAT TRANS-

FER PRODUCTS, INC. for recommendations in case of a thicker wall.

• That the Heat Transfer Products, Inc. Flex-L System is not designed for common

venting. Use this for a single appliance only unless otherwise approved.

• Utilize an appliance adapter test port for combustion testing as required by Flex-L.
• Follow the national codes for the installation of oil burning equipment: in USA -

NFPA 31, in Canada - CAN/CSA-B139 and local regulations.

A. INSTALLING THE JOINT ASSEMBLY

1) Loosen the gear clamps attached to the adapter sleeve and slide the adapter sleeve over
the vent pipe, 

Figure 4

and 

Figure 5, page 8.

2) Pull the corrugated inner tube out of the vent pipe for easy access to insert the adapter.

3) Apply sealant around the corrugated end of the adapter.

4) Align the flat seams at the end of both corrugated tubes and insert the adapter into the
vent tube. Screw the adapter into the vent pipe with a counter-clockwise motion. The

Summary of Contents for OFB

Page 1: ...Venting Manual for Munchkin Oil Fired Boilers Designed and Tested to the A S M E Boiler and Pressure Vessel Code LP 115 REV 6 1 03...

Page 2: ......

Page 3: ...ide Terminal 9 D Connections To Appliance 9 PART VII MAINTENANCE 10 PART VIII CERAFLEX FLEX L COMPONENTS LIST 11 DANGER Indicates a condition or hazard which will cause severe personal injury death or...

Page 4: ...is not operating but the operating automatic damper must fail in the open position The com bustion air duct must have direct access to the outdoors and have a rain hood and insect screen installed at...

Page 5: ...imneys power venting systems and direct vent systems should also conform to local and State codes and good industry practice In lieu of local codes NFPA 211 should be used as a reference BAROMETRIC DA...

Page 6: ...nd then slit the stock between the lines ver tically Bend the segments in alternate directions Replace the adjuster start the burner and verify settings taken earlier If unchanged bend tabs against fl...

Page 7: ...system in use In addition it is strongly recommended that the applicable precautions for Natural Draft Applications be used In addition to all of the pertinent information regarding Natural Draft Appl...

Page 8: ...sagging Follow the national codes for the installation of oil burning equipment in USA NFPA 31 in Canada CAN CSA B139 and local regulations Figure 2 PART V POWER VENTER APPLICATIONS When using a power...

Page 9: ...a thicker wall That the Heat Transfer Products Inc Flex L System is not designed for common venting Use this for a single appliance only unless otherwise approved Utilize an appliance adapter test po...

Page 10: ...UTSIDE TERMINAL Using Figure 6 and Figure 7 page 9 com plete the following steps 1 Determine the terminal location 2 Cut 8 1 4 diameter hole through the wall slightly larger than the O D of the termin...

Page 11: ...luminum tape and secure using air intake clamp Beaded end of the air intake clamp should go first over the air intake collar 9 Seal the gap between the vent pipe and the inner section with silicone se...

Page 12: ...PRODUCTS INC and Flex L International Inc recommends the entire heat ing system including the appliance and vent to be checked annually by a qualified heating professional THE CERAFLEX VENT TERMINAL...

Page 13: ...MAINTENANCE 11 THE CERAFLEX INSULATED VENT PIPE IS 1 CLEARANCE TO COMBUSTIBLES Figure 10 Figure 11 Figure 12 Figure 13...

Page 14: ...Pipe 20 Length CFV204 CeraFlex Appliance Adapter w Pt 6 4 CFAA64P CeraFlex Terminal Adapter 4 4 CFAT44 CeraFlex Vent Terminal 4 CFT4 CeraFlex Air Intake Flex 10 x4 L10 04 CeraFlex Air Intake Flex 15 x...

Page 15: ...FOR FURTHER TECHNICAL INFORMATION CONTACT HEAT TRANSFER PRODUCTS Inc 120 Braley Road PO Box 429 East Freetown MA 02717 0429 508 763 8071...

Page 16: ......

Reviews: