Munchkin OFB Venting Manual Download Page 7

MECHANICAL DRAFT APPLICATIONS

5

• Condensation of flue gasses.
• Positive outlet draft conditions.
• Reverse flow of fluegas during or after burner shutdown.

In addition, the following rules of good industry practice should be followed;

• Always try to keep chimney connector length to ten feet (10'), or less.
• The chimney connector must never be smaller than the boiler flue outlet, and

should be constructed of at least 24-gauge metal.

It is important to note that due to the high efficiency of the MUNCHKIN OFB boilers con-
densing temperatures in the chimney connector and venting system may be reached. 

If condensing temperatures of below 250 °F NET are reached in the chimney connector, the
following precautions may have to be taken;

• Seal all joints in venting system with high temperature silicone or mastic.
• Verify quality of chimney and liner. If a masonry, brick, or block chimney is used, or

the existing tile liner is in poor condition, a chimney liner suitably rated, and listed
for oil may have to be installed.

PART IV. MECHANICAL DRAFT APPLICATIONS

When using the MUNCHKIN OFB boilers in a mechanical draft application, the following
basic guidelines should be observed according to the venting system in use. In addition, it
is strongly recommended that the applicable precautions for Natural Draft Applications be
used.

In addition to all of the pertinent information regarding Natural Draft Applications whenever
a Mechanical Draft Application is used, it should be installed using the following instructions
and 

Figure 2, page 6 

as reference;

• The terminating vent hood, and the inlet air hood should be on the same wall sur-

face, and on the wall opposite from the prevailing wind wall, if possible.

• All of the air for combustion to the burner is supplied directly from outside of the

building or structure, following the suggested applications below.

Not less than 12" above the total accumulated snow and level grade.

Not less than 4' horizontally or below any window, door or air inlet, and also
not more than 1' above any of these openings.

Not less than 3' above a powered air inlet device that is within 10'.

Not less than 2' from any other building.

At least 3' from any inside corner of a building.

WARNING  

• NEVER connect the appliance into a chimney or liner serving an open fireplace.
• Inspect and clean chimney, and verify it is free of restrictions and obstructions.
• The chimney connector must always be properly supported.
• NEVER install a manual damper in the venting system.
• Chimney connectors should be free of as many 90° degree turns as possible, and

be pitched upwards towards the vent.

Summary of Contents for OFB

Page 1: ...Venting Manual for Munchkin Oil Fired Boilers Designed and Tested to the A S M E Boiler and Pressure Vessel Code LP 115 REV 6 1 03...

Page 2: ......

Page 3: ...ide Terminal 9 D Connections To Appliance 9 PART VII MAINTENANCE 10 PART VIII CERAFLEX FLEX L COMPONENTS LIST 11 DANGER Indicates a condition or hazard which will cause severe personal injury death or...

Page 4: ...is not operating but the operating automatic damper must fail in the open position The com bustion air duct must have direct access to the outdoors and have a rain hood and insect screen installed at...

Page 5: ...imneys power venting systems and direct vent systems should also conform to local and State codes and good industry practice In lieu of local codes NFPA 211 should be used as a reference BAROMETRIC DA...

Page 6: ...nd then slit the stock between the lines ver tically Bend the segments in alternate directions Replace the adjuster start the burner and verify settings taken earlier If unchanged bend tabs against fl...

Page 7: ...system in use In addition it is strongly recommended that the applicable precautions for Natural Draft Applications be used In addition to all of the pertinent information regarding Natural Draft Appl...

Page 8: ...sagging Follow the national codes for the installation of oil burning equipment in USA NFPA 31 in Canada CAN CSA B139 and local regulations Figure 2 PART V POWER VENTER APPLICATIONS When using a power...

Page 9: ...a thicker wall That the Heat Transfer Products Inc Flex L System is not designed for common venting Use this for a single appliance only unless otherwise approved Utilize an appliance adapter test po...

Page 10: ...UTSIDE TERMINAL Using Figure 6 and Figure 7 page 9 com plete the following steps 1 Determine the terminal location 2 Cut 8 1 4 diameter hole through the wall slightly larger than the O D of the termin...

Page 11: ...luminum tape and secure using air intake clamp Beaded end of the air intake clamp should go first over the air intake collar 9 Seal the gap between the vent pipe and the inner section with silicone se...

Page 12: ...PRODUCTS INC and Flex L International Inc recommends the entire heat ing system including the appliance and vent to be checked annually by a qualified heating professional THE CERAFLEX VENT TERMINAL...

Page 13: ...MAINTENANCE 11 THE CERAFLEX INSULATED VENT PIPE IS 1 CLEARANCE TO COMBUSTIBLES Figure 10 Figure 11 Figure 12 Figure 13...

Page 14: ...Pipe 20 Length CFV204 CeraFlex Appliance Adapter w Pt 6 4 CFAA64P CeraFlex Terminal Adapter 4 4 CFAT44 CeraFlex Vent Terminal 4 CFT4 CeraFlex Air Intake Flex 10 x4 L10 04 CeraFlex Air Intake Flex 15 x...

Page 15: ...FOR FURTHER TECHNICAL INFORMATION CONTACT HEAT TRANSFER PRODUCTS Inc 120 Braley Road PO Box 429 East Freetown MA 02717 0429 508 763 8071...

Page 16: ......

Reviews: