DIRECT VENT APPLICATIONS

9

8) Seal with a weatherproof sealant around the bead and edge of the outer wall plate to pre-
vent water from getting inside.

C. CONNECTIONS TO OUTSIDE TERMINAL

Using 

Figure 8

and 

Figure 9

complete the

following steps:

1) Slide the inner section over the vent pipe.

2) Connect the terminal adapter to the vent pipe
as per joint assembly.

3) Apply a bead of sealant around the terminal
flue collar.

4) Slide the appliance adapter over the flue
collar.

5) Tighten the gear clamp of the terminal
adapter around the flue collar.

6) Seal the seam in the adapter with sealant. 

7) Slide the inner section over the outer section and secure by tightening the gear clamp. 

8) Stretch the air intake flex to the desired length and slide over the air intake collar. Seal the
connection with the aluminum tape and secure using air intake clamp. Beaded end of the air
intake clamp should go first over the air intake collar. 

9) Seal the gap between the vent pipe and the inner
section with silicone sealant. 

D. CONNECTIONS TO APPLIANCE

Using 

Figure 10, Figure 11, Figure 12 

and 

Figure 13

complete the following steps:

1) Connect the appliance adapter to the vent pipe as
per joint assembly.

2) Apply sealant around the appliance flue collar.

3) Slide the appliance adapter over the appliance flue
collar.

4) Tighten the gear clamp of the appliance adapter around the flue collar.

5) Seal the seam in the adapter with sealant.

6) Install burner air adapter.

7) Slide the end of air intake flex over the burner air adapter. Seal the connection with alu-
minum tape and secure using air intake clamp. Beaded end of the air intake clamp should
go first over burner air adapter.   

8) A vacuum relief device may need to be installed if required by the appliance manufac-
turers' installation instructions.

Figure 6

Figure 7

Summary of Contents for OFB

Page 1: ...Venting Manual for Munchkin Oil Fired Boilers Designed and Tested to the A S M E Boiler and Pressure Vessel Code LP 115 REV 6 1 03...

Page 2: ......

Page 3: ...ide Terminal 9 D Connections To Appliance 9 PART VII MAINTENANCE 10 PART VIII CERAFLEX FLEX L COMPONENTS LIST 11 DANGER Indicates a condition or hazard which will cause severe personal injury death or...

Page 4: ...is not operating but the operating automatic damper must fail in the open position The com bustion air duct must have direct access to the outdoors and have a rain hood and insect screen installed at...

Page 5: ...imneys power venting systems and direct vent systems should also conform to local and State codes and good industry practice In lieu of local codes NFPA 211 should be used as a reference BAROMETRIC DA...

Page 6: ...nd then slit the stock between the lines ver tically Bend the segments in alternate directions Replace the adjuster start the burner and verify settings taken earlier If unchanged bend tabs against fl...

Page 7: ...system in use In addition it is strongly recommended that the applicable precautions for Natural Draft Applications be used In addition to all of the pertinent information regarding Natural Draft Appl...

Page 8: ...sagging Follow the national codes for the installation of oil burning equipment in USA NFPA 31 in Canada CAN CSA B139 and local regulations Figure 2 PART V POWER VENTER APPLICATIONS When using a power...

Page 9: ...a thicker wall That the Heat Transfer Products Inc Flex L System is not designed for common venting Use this for a single appliance only unless otherwise approved Utilize an appliance adapter test po...

Page 10: ...UTSIDE TERMINAL Using Figure 6 and Figure 7 page 9 com plete the following steps 1 Determine the terminal location 2 Cut 8 1 4 diameter hole through the wall slightly larger than the O D of the termin...

Page 11: ...luminum tape and secure using air intake clamp Beaded end of the air intake clamp should go first over the air intake collar 9 Seal the gap between the vent pipe and the inner section with silicone se...

Page 12: ...PRODUCTS INC and Flex L International Inc recommends the entire heat ing system including the appliance and vent to be checked annually by a qualified heating professional THE CERAFLEX VENT TERMINAL...

Page 13: ...MAINTENANCE 11 THE CERAFLEX INSULATED VENT PIPE IS 1 CLEARANCE TO COMBUSTIBLES Figure 10 Figure 11 Figure 12 Figure 13...

Page 14: ...Pipe 20 Length CFV204 CeraFlex Appliance Adapter w Pt 6 4 CFAA64P CeraFlex Terminal Adapter 4 4 CFAT44 CeraFlex Vent Terminal 4 CFT4 CeraFlex Air Intake Flex 10 x4 L10 04 CeraFlex Air Intake Flex 15 x...

Page 15: ...FOR FURTHER TECHNICAL INFORMATION CONTACT HEAT TRANSFER PRODUCTS Inc 120 Braley Road PO Box 429 East Freetown MA 02717 0429 508 763 8071...

Page 16: ......

Reviews: