ELECTRICAL
It is important that the electrical power is not turned on at this time. Double check all connections and then
turn the power on. The display that is provided with the Munchkin should now be reading the outlet
temperature. Note: see Part 6/Startup Procedure section in the manual to change the temperature setting
or run the heater.
NORMALLY OPEN
T
T
GROUND
BUS
SWITCH JUNCTION BOX
120V 60 HZ
ELECTRICAL
SWITCH JUNCTION BOX
120V 60 HZ
ELECTRICAL
NORMALLY OPEN
THERMOSTAT
CONNECTION
WIRING DIAGRAM WITHOUT CONNECTION TO CIRCULATOR
GREEN
(GROUND)
GRAY
GRAY
CONNECTION
THERMOSTAT
(NEUTRAL)
WHITE
BLACK
(HOT)
GRAY
T
T
GRAY
WIRING DIAGRAM CONNECTING TO CIRCULATOR
BLACK
WHITE (NEUTRAL)
GREEN (GROUND)
DIAGRAM "A"
(HOT)
BLACK
GREEN
(GROUND)
(NEUTRAL)
WHITE
DIAGRAM "B"
BROWN (NEUTRAL)
ORANGE (HOT)
GREEN (GROUND)
ORANGE (HOT)
BROWN (NEUTRAL)
GREEN (GROUND)
IMPORTANT NOTE:
BE CERTAIN THAT THE ORANGE
WIRE IS SECURELY CAPED.
FAILURE TO DO SO COULD
RESULT IN INJURY OR FIRE
AND COULD DAMAGE THE CONTROL.
ORANGEBROW
N
GREEN
NOTICE
Do not power zone valves directly from the heater transformer. Doing so will greatly
reduce the life of the transformer. Use a separate transformer sized to handle the total
electric load of all zone valves.
Figure 2-1: Connection Wiring Directly to
Central Heating Circulator
Figure 2-2: Connection Wiring without Wiring
Central Heating Circulator
Note to Electrical Contractor:
The
orange
wire
is 120 Volt/4 Amp maximum for central
heating circulator only. Loads greater than 4
amps or 3 amps for HA models only will blow the
fuse on the board. The
brown wire
is the neu-
tral wire for the central heating pump only.
Figure 2-3: For circulator amp loads greater
than 4 amps (3 amps for “HA” models) use the
wiring diagram shown at left. The brown and
orange wires will not be used in this
application.
5
T
1
2
3
6
4
T
1K1
1K2
BOILER
"TT"
GRAY
ZONE
CIRCULATOR
120 VOLT
L1 HOT (BLACK)
GRAY
BOILER
"TT"
THERMOSTAT
ZONE
R845A
SWITCHING
RELAY ZONE
1K1
L2 NEUTRAL
(WHITE)