34
PIPING
NOTES:
1.
This drawing is meant to show system piping concept only.
Installer is responsible for all equipment & detailing required by local codes.
2.
All closely spaced tees shall be within 4 pipe diameter center to center spacing.
3.
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream
of all closely spaced tees.
4.
The minimum pipe size for connecting a Super Stor water heater is 1 inch.
5.
The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches.
6.
All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.
7.
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119
˚
F.
8.
Install a minimum of 12 diameters of straight pipe upstream of all circulators.
9.
A purging valve may be used in lieu of the ball valve / hose bib combination shown.
make-up water
closely
spaced
tees
space heating zone circuit
purging
valves
Munchkin heater
T/P
PB1
P2
Super Stor
indirect DHW tank
anti-scald
mixing valve
Munchkin heater
T/P
PB2
zone
circulators
Standard Munchkin heater
Preferred piping
(multiple heaters / zoning with circulators)
Space heating mode
Drawing 2E
Fig. 5-11