F18
Gas Valve not correctly connected/internal fault.
Just before ignition, a test is per-
formed on the gas connection. If there is a failure in the gas valve connection and or the valve
is not connected, this fault code will appear.
Remedy
– Check the connection to gas valve. Check the wiring to the board. If the problem
persists, change gas valve cable. Manually reset by pushing the
S4/reset
.
F30
Watchdog.
Call Factory for further assistance.
Remedy
– Call Factory for further assistance
F31
Parameter Memory.
External Parameter memory corrupted
Remedy
– Call Factory for further assistance
F32
Parameter memory write error.
External Parameter memory fault
Remedy
– Call Factory for further assistance
F33
Programming Error.
Programming with PC not successful
Remedy
– Call Factory for further assistance
SERVICING
Boiler & Indirect Temperature (˚F)
Resistance (ohms)
32
32550
41
25340
50
19870
59
15700
68
12490
77
10000
86
8059
95
6535
104
5330
113
4372
122
3605
131
2989
140
2490
149
2084
158
1753
167
1481
176
1256
185
1070
194
915
203
786
212
667
RESISTANCE TABLES