LEGAL202107V01 

                                                                                      

 

 

2. 

Product Identification 

 

Each module has two labels providing the following information: 

1.  Nameplate:  describes the product type; rated power, rated current, rated voltage, open circuit voltage, 

short  circuit  current, all as measured under standard test conditions; weight, dimensions  etc.; the 
maximum system voltage is 600 volts or 1000 volts depending on the product family DC for UL standard 
and 1000/1500 volts DC for IEC standard. Depending on the products some are UL/IEC listed to 1000/1500 
volts while other UL products are 600 volts. Check your nameplate or contact your local representative for 
details.

 

 

2.  Barcode: each individual module has a unique serial number. The serial number has 17 digits. The 9th 

and 10th digits are year codes, and the 11th and 12th digits are weekly codes. For example, 
7755S105201000001 means that the module is assembled and inspected in the 10th week of 2010. Each 
module has only one bar code. It is permanently attached to the interior of the module and is visible from 
the top front of the module. This bar code is inserted prior to laminating. 

 

 

Example barcode label 

 

 

Do not remove any labels. Removing a label will make the modul warranty void. 

 

Summary of Contents for MSMD M10-60 Series

Page 1: ...M nchen Solar Installation Manual M nchen Energieprodukte GmbH www muenchen energieprodukte de...

Page 2: ...y 3 1 4 Fire Safety 4 2 Product Identification 5 3 Mechanical installation 6 3 1 Selecting the location 6 3 2 General Installation 6 3 3 Installation methods 7 3 4 Attachment guidelines 8 4 Electrical...

Page 3: ...t light energy to direct current electrical energy They are designed for outdoor use Modules can be ground mounted mounted on rooftops The proper design of support structures lies within the responsib...

Page 4: ...eriod of time always cover the modules and ensure that the glass faces down on a soft flat surface to prevent water from collecting inside the module and causing damage to exposed connectors 1 3 Insta...

Page 5: ...ctors to connect modules to form a string or connect to another device Removing the connectors will void the warranty 1 4 Fire Safety Consult your local authority for guidelines and requirements for b...

Page 6: ...o 1000 1500 volts while other UL products are 600 volts Check your nameplate or contact your local representative for details 2 Barcode each individual module has a unique serial number The serial num...

Page 7: ...ys use a tested and certified mounting structure approved for your system design In regions with heavy snowfall in winter select the height of the mounting system so that the lowest edge of the module...

Page 8: ...maximum permissible loads and are not subject to excessive forces due to the thermal expansion of thesupport structures Never allow modules overlap or exceeds the rooftop Refertothefollowinginstallati...

Page 9: ...t of 1600 Pa 0 232psi 2500 Pa 0 363 psi and 3600 Pa 0 522 psi respectively under UL 1703 standard The diagrams in the tables below are designed for illustration purpose For each installation modules c...

Page 10: ...0 Pa safety factor 1 5 M2 30 series M3 30 series M3 60 series M6 60 series Test load positive 5400 Pa negative 2400 Pa Design load positive 3600 Pa negative 1600 Pa safety factor 1 5 M2 30 series M3 3...

Page 11: ...Pa negative 3800 Pa Design load positive 3600 Pa negative 2533Pa safety factor 1 5 M2 30 series M3 30 series M3 60 series M6 60 series M6 72 series M10 60 series M10 72 series Clamp zone A 1 4 long f...

Page 12: ...sitive 5400 Pa negative 3800 Pa Design load positive 3600 Pa negative 2533Pa safety factor 1 5 M6 60 series M6 72 series M10 60 series M10 72 series Clamp zone A0 1 4 short frame length 50 mm A1 100 m...

Page 13: ...gative 3800 Pa Design load positive 3600 Pa negative 2533Pa safety factor 1 5 M2 30 series M3 30 series M3 60 series M6 60 series M6 72 series M10 60 series M10 72 series Attentions The module clamps...

Page 14: ...7V01 13 The mounting holes reserved for tracker mounting system with special accessories The length of module is over 2 meters whose load value with tracker needsto be confirmed by module supplier res...

Page 15: ...connected to the PV output Voltages are additive when modules are connected in series and modules currents are additive when Modules are connected in parallel as illustrated in Figure 1 Modules with...

Page 16: ...e maximum number of modules that can be connected in series within a string for the specific project must be calculated based on the actual local temperature If there is reverse current exceeding the...

Page 17: ...maximum series fuse rating of module and local electrical installation code always make sure M nchen Solar PV modules are assembled with the appropriate string fuse for circuit protection There is no...

Page 18: ...allation is finished and after connection to the grid please do a professional hand over to the owner including an installation protocol is required Provide a clear documentation of the system to the...

Page 19: ...F to bond solar modules to module mounting brackets grounding part is tested to UL467 3 Use WEEB DPF to bond solar modules to module mounting brackets grounding part is tested to UL467 Recommend faste...

Page 20: ...tions every six months to verify that they are clean secure undamaged and free of corrosion Or else the warranty may be voided In the event of a ground fault condition NEVER wash or spray modules with...