SDTA-01
4BINSTALLATION
14
4.3.4 Connecting the Secondary Circuit
for more information on cabling the
secondary
circuit.
1.
Link the secondary to a MULTITEL Power Monitoring System using two
24-gauge stranded wires.
Table 4 – Wiring of the secondary circuit to the SDTA-01
J8
JX*
RED OUTPUT
1 AN+
BLACK OUTPUT
2 AN-
2.
Put the cover back on the SDTA-01 and its screws.
* JX is the corresponding connector on the MPMS.
NOTE
: use the cable conduit #3110 to keep the output cable away from the primary
circuit. Pin 1 of J8 is linked to the positive analog channel of the MULTITEL power
monitoring system and pin 2 of J8 is linked to the negative analog channel. Crimp for
a MXP2 188 installation or screw directly into the Weidmuller connector for a
Mirador or Site Manager installation.
4.3.5 Definition of Connectors
The following section contains a description of connectors J3 and J8.
Table 5 - Definition of J3
PIN
NAME
USE
TYPE
1
AC1
110 VAC or 220 VAC input voltage
IN
2
AC2
110 VAC or 220 VAC input voltage
IN
Table 6 - Definition of J8
PIN
NAME
USE
TYPE
1
OUTPUT1
17 VAC output voltage
OUT
2
OUTPUT2
17 VAC output voltage
OUT
Summary of Contents for SDTA-01
Page 1: ...SDTA 01 Step Down Transformer Adapter Version 2 1 User s Manual...
Page 2: ......
Page 4: ...2...