DCA400SSI GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (11/03/08) — PAGE 37
GENERATOR SHUT-DOWN PROCEDURES
NORMAL SHUTDOWN PROCEDURE
To shutdown the generator, use the following procedure:
Place both the
1.
MAIN, GFCI and LOAD
circuit breakers
as shown in Figure 35 to the
OFF
position.
Place the engine speed switch (Figure 53) in the “LOW”
2.
(down) position.
Engine Speed Switch (Low)
Figure 53.
Let the engine cool by running it at low speed for 3-5
3.
minutes with no load applied.
Place the
4.
MPEC Control Switch
(Figure 54) to the
OFF/RESET
position.
MPEC Control Switch (Off/Reset)
Figure 54.
Verify that
5.
all
the status LEDs on the MPEC display
are
OFF
(not lit).
Remove all loads from the generator.
6.
Inspect entire generator for any damage or loosening
7.
of components that may have occurred during
operation.
WARNING
NEVER
stop the engine suddenly except in an
emergency.
EMERGENCY SHUTDOWN PROCEDURE
To stop the engine in the event of an emergency,
1.
PUSH
the emergency stop button (Figure 55) inward. This
button is located on the engine operating panel, see
Figure 5.
Emergency Stop Button
Figure 55.
Summary of Contents for Power WHISPERWATT DCA400SSI
Page 21: ...DCA400SSI GENERATOR OPERATION AND PARTS MANUAL REV 2 11 03 08 PAGE 21 NOTES ...
Page 53: ...DCA400SSI GENERATOR OPERATION AND PARTS MANUAL REV 2 11 03 08 PAGE 53 NOTES ...
Page 62: ...PAGE 62 DCA400SSI GENERATOR OPERATION AND PARTS MANUAL REV 2 11 03 08 CONTROL BOX ASSY ...
Page 74: ...PAGE 74 DCA400SSI GENERATOR OPERATION AND PARTS MANUAL REV 2 11 03 08 BATTERY ASSY ...
Page 76: ...PAGE 76 DCA400SSI GENERATOR OPERATION AND PARTS MANUAL REV 2 11 03 08 MUFFLER ASSY ...
Page 90: ...PAGE 90 DCA400SSI GENERATOR OPERATION AND PARTS MANUAL REV 2 11 03 08 RUBBER SEALS ASSY ...
Page 97: ...DCA400SSI GENERATOR OPERATION AND PARTS MANUAL REV 2 11 03 08 PAGE 97 NOTES ...