60 hz gENERATOR • OpERATiON ANd pARTs mANuAl — REv. #0 (03/13/14) — pAgE 29
BATTERY (gA6hEB)
This unit is of negative ground
dO NOT
connect in reverse.
Always maintain battery fluid level between the specified
marks. Battery life will be shortened, if the fluid levels are
not properly maintained. Add only distilled water when
replenishment is necessary.
Check to see whether the battery cables are loose. Poor
contact may result in poor starting or malfunctions. Always
keep the terminals firmly tightened. Coating the terminals
with an approved battery terminal treatment compound
will help prevent corrosion. Replace battery with only
recommended type battery.
The battery is sufficiently charged if the specific gravity
of the battery fluid is 1.28 (at 68° F). If the specific gravity
should fall to 1.245 or lower, it indicates that the battery is
dead and needs to be recharged or replaced.
Before charging the battery with an external electric source,
be sure to disconnect the battery cables.
BATTERY CABlE iNsTAllATiON
AlWAYs
be sure the battery cables are properly connected
to the battery terminals (Figure 30). The
red
cable is
connected to the positive terminal of the battery, and the
black
cable is connected to the negative terminal of the
battery.
Figure 34. Battery Connections
NOTICE
Inadequate battery cable connections may cause poor
starting of the generator, and create other malfunctions..
POSITIVE
NEGATIVE
mainTenanCe
When connecting battery do the following:
1.
NEvER
use worn or damaged battery cables. Replace
defective battery cables immediately.
2. Place a small amount of battery terminal treatment
compound around both battery terminals. This will
ensure a good connection and will help prevent
corrosion around the battery terminals.
pOlARiTY
The polarity of the battery is extremely important. When an
inverted circuit connection takes place, the circuit will be in
short circuit instantaneously resulting in possible damage
to the control box electronics and starter.
When connecting the battery cables to the battery terminals
be sure to check the polarity.
TEsTiNg ThE gFCi mOdulE
If tripping of the
main
circuit breaker persists after a load is
replaced with a known good one (no short circuit), perform
this test with no load.
1. Start the generator as outlined in the start up procedure
in this manual.
2. Place the main circuit breaker (Figure 35) in the
ON
position.
Figure 35. Circuit Breaker ON (GFCI Test)
NOTICE
AlWAYs
disconnect the negative terminal first and
reconnect negative terminal last.
NOTICE
If the battery cables are connected incorrectly, electrical
damage to the generator will occur. Pay close attention
to the polarity markings on the battery when connecting
the battery cables.
OFF
ON
Summary of Contents for GA6HB
Page 13: ...GA6HB 6HEB 60 hz GENERATOR operation and parts manual rev 0 03 13 14 page 13 note...
Page 31: ...GA6HB 6HEB 60 hz GENERATOR operation and parts manual rev 0 03 13 14 page 31 notes...
Page 37: ...GA6HB 6HEB 60 hz GENERATOR operation and parts manual rev 0 03 13 14 page 37 notes...
Page 85: ...GA6HB 6HEB 60 hz GENERATOR operation and parts manual rev 0 03 13 14 page 85 notes...