MD-1000I / MD-2000I / MD-3000I
UPS Installation and Hook-Up
MD Series
62
6.2
UPS Communication Interfaces
The UPS has convenient communication features for data transfer.
Only a single communication port can be active. The USB port has priority over
the RS-232 port.
If a communication cable is connected, the software can exchange data with
the UPS. The software gathers information from the UPS about the power sup-
ply status. In the event of a power emergency, the software backs up the data
and shuts down the equipment properly.
6.2.1
RS-232 port
Use only those cables specified in the Chapter "Accessories" (1 : 1).
Pin
Configuration
2
RS-232 Tx
Receiving line Rx or shut down SD
3
RS-232 RX
Transmitting line Tx
5 Ground
GND
The communication interface is completely isolated via galvanic means.
6.2.2
SNMP communication interface
The UPS can be ordered or fit with a SNMP interface.