![multimatic MD-1000I User Manual Download Page 86](http://html.mh-extra.com/html/multimatic/md-1000i/md-1000i_user-manual_1854492086.webp)
MD-1000I / MD-2000I / MD-3000I
Technical Information
11.
Technical
Information
Model
MD-1000I
MD-2000I
MD-3000I
Output
Output in VA
1000 VA
2000 VA
3000 VA
Output in W
800 W
1600 W
2400 W
Power factor
0.8
Topology Online
double-conversion
Placement Tower
or
19"-rack
Safety CE
Input
Voltage range
120/140/160 - 288 VAC
Basis charge percent (0~33/33~66/66~100%)
Under voltage
120/140/160Vac
Under voltage start
170Vac
Over voltage
288 VAC
Voltage
Over voltage start
278 VAC
Frequency
50/60 Hz auto-select, ± 5Hz
Phases Single-phase
with
earth
PF
> 0.99 at full measured linear load
Typical transfer time
0 ms.
Leakage current
≤
3.5 mA
Surge protection
300 Joule
Output
Voltage
230V, adjustable to 200/208/220/230/240
Voltage setting
≤
± 1% until weak battery warning
Frequency (synchro-
nised range)
3Hz or 1Hz (setting via software)
Frequency (battery
mode)
±0.1% (0.05~0.06Hz) if not synchronised with
line
Crest factor
3:1
Total harmonic distor-
tion
3% THD (linear l ad)
o
7% THD (non-linear load)
Dynamic response
(ms)
<=
60ms/5%
Output (INV.
mode)
Wave form type
True sine wave
Efficiency
AC mode (full load)
85%
85%
88%
Battery mode (full
load)
83% 83% 85%
Battery system
Type 12V/7.2Ah
12V/7.2Ah
12V/9Ah
Number of batteries
3
6
6
Back-up time (full load)
>7min.
>7min.
>5min.
Recharge time
4 hours to 90%
Charge current (max.)
1.1A
2.16A
2.7A
Charge voltage VDC (DC high)
41.0Vdc±0.5
82.0Vdc±0.5
82.0Vdc±0.5V
MD Series
86
Summary of Contents for MD-1000I
Page 15: ...MD 1000I MD 2000I MD 3000I Introduction MD Series 15 ...
Page 21: ...MD 1000I MD 2000I MD 3000I Safety Instructions MD Series 21 ...
Page 51: ...MD 1000I MD 2000I MD 3000I Storage and Unpacking MD Series 51 ...
Page 59: ...MD 1000I MD 2000I MD 3000I System Function MD Series 59 ...
Page 92: ...12 Declaration of Conformity MD Series 92 ...
Page 93: ...MD Series 93 ...
Page 94: ...MD Series 94 ...