1. GENERAL 

This instrument is a leakage current clamp meter with high precision and wide range 

combined by newest CT technologies which enabled to make up CT utilities extremely. Also, 

it can measure phase current of CVT and or CV cable in high voltage circuit very simply by 

our originally developed measuring method. Until now, it has been very dangerous to open 

the circuit by mold disconnector or pillar disconnector due to flow of big arc current. This 

instrument can measure phase current and can prevent danger when opening circuits. 

 

2. SPECIFICATIONS 

2-1 Current Detection Part 

CT Inside Diameter 

φ

40mm 

Method 

: Split-core type ZCT 

Withstanding Volt

.

age : 

AC2200V/1 

minute 

 

2-2 Measuring Part 

Measuring Function 

: AC Leakage Current, loading current; 
 Phase current of hi-voltage circuit (measuring at low 
voltage corresponding field). 

Measuring Method 

: CT clamp method (max. applicable conductor 

φ

40mm)

Measuring Range 

: AC current 0~300.0mA/300A (50/60Hz) 
  Line current CVT cable and CV cable 

Range Swtich 

: mA, A, Phase Current CVT, Phase Current CV 

AC Current Detection 

:    Average sensing 

A/D Conversion 

:    Successive approximation method 

Display 

: Max. 3199 count, LCD with annunciator 

Over Range Indication 

: “OL” mark on LCD 

Sampling Rate 

: 2 times/sec. 

Data Hold Indication 

: “DH” mark on LCD 

Low Battery Indication 

: “B” mark on LCD 

Auto Power Off 

: approx. 10 minutes after the final rotary switch 
operation. 
To power on again, set rotary switch to OFF. 

m(meter) Display Switch 

: The length of high voltage circuit will be displayed in 
line current measuring range (estimated value), 
calculated by storey capacitance. 

 
 

Summary of Contents for M-140HC

Page 1: ...instruction manual completely and apply this instrument correctly Keep this instruction manual carefully to take out whenever you need MULTI MEASURING INSTRUMENTS CO LTD Akihabara Murai Bldg 7F 1 26...

Page 2: ...from mis operations WARNING POSSIBLE ELECTRICAL SHOCK This instrument is for the use of low voltage circuit Do not make measurements of power lines carrying more than AC 600V Before use check and conf...

Page 3: ...ng Part Measuring Function AC Leakage Current loading current Phase current of hi voltage circuit measuring at low voltage corresponding field Measuring Method CT clamp method max applicable conductor...

Page 4: ...Consumption approx 3 5mA approx 150h for continuous use Dimension Weight 45 W x195 H x24 D mm approx 180g Accessories AAA battery LR03 x 3 installed in the instrument instruction manual x 1 soft carry...

Page 5: ...h By push one time DH sign will be on LCD and the data will be hold By push once more this function will be released m Conversion Switch In case of hi voltage phase current measurement the storey capa...

Page 6: ...ve the battery cover to the direction of arrow mark 2 Pick up the exhausted batteries 3 Confirm the polarities and put the new batteries 4 Replace the battery cover to the original position and fix sc...

Page 7: ...r range OL mark will appear on LCD use data hold where displayed value cannot be seen clearly POSSIBLE ELECTRICAL SHOCK For safety use the instrument in circuit less than 600V Before operation confirm...

Page 8: ...3 Phase Current Measurement of Hi Voltage Circuit with shielded grounding line 1 Measurement of CVT Cable In case of CVT cable as the right drawing this instrument can measure phase current by clampin...

Page 9: ...nt of CV Cable Move CV cable to the search coil of CT like as at the right drawing and read the max value by keeping close and turning the instrument for 90o Set range switch from OFF to CV position d...

Page 10: ...contact the dealer where you bought the instrument The warranty period is 12 months from the date of purchase and the instrument shall be repaired at free of charge provided that we judge the cause o...

Reviews: