background image

hydro-guard

® 

 

remote Pressure Monitoring System

Installation

2

3

10. The pressure monitor will begin 

operating once the sensor cable 

is plugged into the RTU and the 

pressure sensor is exposed to line 

pressure. The first reading may take 

up to 24 hours to be transmitted to 

the website. The Device will reveal 

system pressures with no additional 

inputs. In order to customize 

4. After the drilling operation is 

complete and corporation valve is 

closed, apply a suitable sealant or 

joint sealing tape on the inlet side 

of the ¾” threads on the supplied 

bushing. Securely attach the ¾” end 

of the bushing to the outlet of the 

corporation valve.
NOTE: Avoid use of excessive 

sealant. Avoid contact with sensor 

transducer tip.
5. Securely attach the pressure 

sensor to the ¼” end of the bushing. 

Utilize a suitable sealant or joint 

sealing tape on the inlet threads 

of the pressure sensor to ensure a 

proper seal.
NOTE: Avoid use of excessive 

sealant. Avoid contact with sensor 

transducer tip.
6. Prior to installation of pressure 

sensor dry the interior of the 

corporation stop threaded 

connection. 
7. Once the sensor has been 

attached, turn the corporation valve 

to the “open” position. Run sensor 

cable through composite valve box 

when installing pressure sensor. 

Refer to the installation instructions 

for the Mueller

®

 composite valve box 

(Form MC014).
NOTE: When paving and 

compacting asphalt, use a Mueller 

iron lid (P/N: AJBV-4CWATER) 

to prevent damage to the RTU. 

Once asphalt work is completed, 

replace iron lid with the RTU. Be 

sure the sensor tip is exposed to 

line pressure prior to connecting 

the sensor cable to the RTU.
8. Once the corporation stop has 

been opened and pressurized, 

plug the male end of the multi-pin 

connector of the sensor cable into 

the mated connector of the RTU 

(located on bottom of RTU). 
9. Once the RTU and cable are 

connected, insert the RTU into the 

ductile iron top section.
NOTE: Be certain that the lid of 

the RTU is mounted flush with the 

surface of the ductile iron valve 

box top section.

pressure level notifications, the 

following four (4) values may be 

set on the measurements screen: 

Warning High, Warning Low, Critical 

High, and Critical Low. Entering the 

above mentioned inputs into the 

system is described in the “Getting 

Started” on page 4. 

typical ValVe Box installation

A. Install service 

saddle.

B. Install guide 

plate.

C. Thread corporation 

valve into service 

saddle. Valve should 

be open.

D. Perform drilling 

operation.

E. Apply joint-sealing 

tape to threads of 

pressure sensor.

G. Thread pressure 

sensor into 

corporation valve. 

Open valve.

I. First, ensure 

waterproof plug is 

plugged in. Install 

adjustable top into valve 

box. Plug sensor cable 

into Black connector on 

RTU and hand tighten 

connector. Insert RTU 

into adjustable top. 

Carefully back fill and 

pave area around valve

box per direction by 

engineer of record.

J. Installation complete.  

Ready for pressure 

monitoring. Log onto 

www.miwwt.net to view 

data.

§ 

F. Dry interior of 

threaded connection of 

corporation stop.

H. Install valve box 

over the assembly.

Waterproof 

plug

Summary of Contents for Hydro-guard

Page 1: ...res involving the Unit 2 Be sure the corporation valve or other isolation valve is closed prior to installation or removal of the pressure sensor 3 Always use all necessary safety equipment and follow...

Page 2: ...ommunication signal is not impeded into account and open the Device which is to be mapped Select Edit and enter longitude and latitude coordinates in the appropriate fields Shipping The Remote Pressur...

Page 3: ...prevent damage to the RTU Once asphalt work is completed replace iron lid with the RTU Be sure the sensor tip is exposed to line pressure prior to connecting the sensor cable to the RTU 8 Once the co...

Page 4: ...on the top navigation bar into the RTU and the pressure sensor is exposed to line pressure The first reading may take up to 24 hours to be transmitted to the website The Device will reveal system pre...

Page 5: ...edit settings for a specific monitored location click the associated icon on the map Registration page This page will allow the client administrator to enter a password select how the system shall se...

Page 6: ...ce SETTINGS web page and locate the calendar application at the lower section of the management screen Using the blue PLUS button open the drop down navigation Select CONNECT to select the date s and...

Page 7: ...ular site Latitude and Longitude GPS location of the unit is automatically determined when the Device is installed In the event the GPS signal is obstructed and unable to locate the Device the install...

Page 8: ...ast two days over the past week or even those recorded over the past two years can be viewed on the Measurements page Data trend mapping includes minimum maximum and averages for every hour as well as...

Page 9: ...second generation product to schedule data transfers from each RTU to a designated storage folder located on their computer or network To begin start Launch of software application and log into the u...

Page 10: ...e up to 24 hours for data and location to appear after installation Description Pressure Warning Low Critical Low Warning High Critical High Test_Device 3 Sensor Serial 1419200209 56 1 1 0 2 0 175 0 1...

Page 11: ...itoring System features an analytic function that allows an operator to compare measurements against one another for enhanced distribution system management hydro guard Remote Pressure Monitoring Syst...

Page 12: ...so that the antenna wires are free 3 Disconnect battery lead connectors and reconnect new battery pack using the mated connectors on the replacement battery Ensure wires are securely connected before...

Page 13: ...f cellular service and a 5 year battery Additional years of cellular service and a 5 year replacement battery may be purchased from Mueller Company Additional costs may include installation of the uni...

Page 14: ...be used ID Description 1 3 8 x 13 8 shoulder x 5 16 5 18 screw SS 2 Antenna Composite Lid 3 RTU Remote Telemetry Unit w Lithium Batteries 4 AJBV 4D Ductile Iron Adjustable Top 12 L 5 Mueller Composite...

Page 15: ...hydro guard Remote Pressure Monitoring System Notes 15...

Page 16: ...Co LLC its affiliates or other third parties Products marked with a section symbol are subject to patents or patent applications For details visit www mwppat com These products are intended for use in...

Reviews: