1.4530.019 – Run Enable not active
Yellow alarm. Initiated by F-series.
Cause
Corrective action
F-series setting is incorrect.
u
Check setting.
1.4530.020 – Spring Check Failed
Yellow alarm. Initiated by F-series.
Cause
Corrective action
F-series setting is incorrect.
u
Check setting.
1.4530.021 – Internal Fault
Yellow alarm. Initiated by F-series.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart F-series.
1.4530.022 – CAN Fault
Red alarm. Initiated by F-series.
Cause
Corrective action
CAN bus connection faulty.
u
Check cabling and setting.
1.4540.009 – Zero Pressure Detected
Yellow alarm. Initiated by TecJet.
Cause
Corrective action
No gas pressure/gas flow
detected.
u
Check gas pressure.
1.4540.010 – Zero Flow Detected
Yellow alarm. Initiated by TecJet.
Cause
Corrective action
No gas pressure/gas flow
detected.
u
Check gas pressure.
1.4540.011 – Flow Not Reached
Red alarm. Initiated by TecJet.
Cause
Corrective action
No gas flow detected.
1. Check inlet and outlet.
2. Check gas pressure, gas quality, gas filter, gas line for
obstruction.
3. Check engine for overloading.
MS150103/01E 2015-03
| Troubleshooting | 83
TIM-ID: 0000038611 - 002