Configuring the FieldServer
Gardner Denver Driver Manual
9
5.3
Client Side Map Descriptor Parameters
5.3.1 FieldServer Specific Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name
Name of this Map Descriptor.
Up to 32 alphanumeric characters
Data_Array_Name
Name of Data Array where data is to
be stored in the FieldServer.
One of the Data Array names from
Section
Data_Array_Offset
Starting location in Data Array.
0 to (Data_Array_Length-1) as
specified in
Section
Function
Function of Client Map Descriptor.
RDBC, Passive_Client
5.3.2 Driver Related Map Descriptor Parameters
Column Title
Function
Legal Values
Node_Name
Name of Node to fetch data from.
One of the node names specified in
“Client Node Descriptor” above
Gar_Cmd
Data poll commands.
Service_Data, Operating_Mode,
Operating_Data
Gar_Data*
Data fields in a data poll command response
message. Can be used to poll for all or
specific data or just isolate specific items in
an “All” poll.
Service_Data:
All
, Advisories, Shutdown_codes,
Hourmeter_shutdown,
Hourmeter_total, Hourmeter_loaded,
Hourmeter_temp, Hourmeter_tmp_st,
Last_maint_A, Last_maint_B, Oilage
Operating_Mode:
All
,
Oper_mode, Seq_number,
Oper_state
Operating_Mode:
All
,
System_pressure,
Filter_pressure, Discharge_temp,
Reservoir_temp, Motor_current
5.3.3 Timing Parameters
Column Title
Function
Legal Values
Scan_Interval*
Rate at which data is polled. Note that the Poll_Delay Connection
parameter affects the effective scan interval.
≥0.1s,
0.1s