Installing the FieldServer
Gardner Denver Driver Manual
6
RS-232 Connection:
Gardner Denver ES
FS-8917-03
FS-8917-16
FS-8917-03
FieldServer
Blue/White
Orange/White
Rx Tx GND
Brown
Connect to the RS-232 port on
the FieldServer
FS-8917-03 Pinouts
FS Function DB9F Pin#
TX
2
RX
3
GND
5
CTS
8
3.1
Hardware Connection Tips / Hints
•
If inter-controller communications are set up for the controller, connect to the RS-232 port only.
•
If inter-controller communications are not used, connect to either the RS-232 or RS-485 port.