6. Measure  indoor  air  (entering  indoor  coil)  wet-bulb 

temperature with a sling psychrometer.

7. Compare superheat reading at service valve with the 

chart located on control box cover.

8. If  unit  has  a  higher  suction  line  temperature  than 

charted  temperature,  add  refrigerant  until  charted 

temperature is reached,

9. If  unit  has  a  lower  suction  line  temperature  than 

charted temperature, reclaim refrigerant until charted 

temperature is reached.

10. Remove charge if superheat is low and add charge if 

superheat is high.

Units with Indoor TXV

Units  installed  with  cooling  mode  TXV  require  charging 

with the subcooling method.

1. Operate unit a minimum of 10 minutes before checking 

charge.

2. Measure liquid service valve pressure by attaching an 

accurate  gage  to  service  port.  Determine  saturation 

temp. from T/P chart.

3. Measure  liquid  line  temperature  by  attaching  an 

accurate thermistor type or electronic thermometer to 

liquid line near outdoor coil.

4. Calculate  subcooling  (saturation  temp.  -  measured 

temp.) and compare to table on back of control box 

cover. 

5. Add refrigerant if subcooling is lower than range shown 

in table. Recover refrigerant to decrease subcooling.

6. If ambient temp. is lower than 65° F, weigh refrigerant 

according to the name plate data.

NOTE: If a TXV is installed on indoor unit, a hard start kit will 

be required on all models with reciprocating compressors. 

are also recommended for areas with utility power lower 

than 208 Vac.

System Operation

The  outdoor  unit  and  indoor  blower  cycle  on  demand 

from  the  room  thermostat.  When  the  thermostat  blower 

switch  is  in  the  ON  position,  the  indoor  blower  operates 

continuously.

Summary of Contents for Signature MAC16 A Series

Page 1: ...anual carefully before installation and keep it for future reference The Signature Series is NOT designed for amateur installation Installation SHOULD be performed by an authorized technician Please r...

Page 2: ...e performed by a licensed professional installer or equivalent service agency or the gas supplier WARNING result in hazards to you and others Installation MUST conform with local building codes and wi...

Page 3: ...th RTV or other silicon based caulk 6 Avoid direct tubing contact with water pipes duct work 7 Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct...

Page 4: ...nless it matches the one listed on the outdoor unit Refrigeration Line Sets Use only refrigeration grade copper tubes Split systems may be installed with up to 50 feet of line set no more than 20 feet...

Page 5: ...utdoor unit 3 Follow the vacuum pump manufacturer s instructions Allow the pump to operate until the system has been evacuated down to 300 microns Allow the pump to continue running for an additional...

Page 6: ...e to suction valve service port Determine saturation temp from T P chart 3 Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to suction line at service val...

Page 7: ...service valve pressure by attaching an accurate gage to service port Determine saturation temp from T P chart 3 Measure liquid line temperature by attaching an accurate thermistor type or electronic t...

Page 8: ...507043 04C Page 7 of 9 mrcool com Figure 3 A C Single Phase Wiring Diagram single speed condenser fan...

Page 9: ...Page 8 of 9 507043 04C mrcool com Figure 4 A C Single Phase Wiring Diagram multi speed condenser fan...

Page 10: ...rom the condenser coils SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODILY INJURY W...

Page 11: ...or manual are subject to change without prior notice Consult with the sales agency or manufacturer for details ELECTRICIAN and or HVAC TECHNICIAN LICENSE INSTALLATION DATE INSTALLATION LOCATION SERIAL...

Reviews: