MrCool Signature MAC16 A Series Installation Manual Download Page 6

507043-04C

Page 5 of 9

mrcool.com

Start-Up Procedure

1. Close electrical disconnects to energize system.
2. Set room thermostat at desired temperature. Be sure 

set point is below indoor ambient temperature.

3. Set the system switch of the thermostat on COOL and 

fan switch for continuous operation (ON) or AUTO, as 

desired.

4. Adjust  refrigerant  charge  per  “Adjusting  Charge” 

section.

Adjusting Charge

Factory charge is shown on the rating label located on the 

access panel.

All units are factory charged for 15 feet of connecting line 

set. Charge should be adjusted for line set lengths other 

than 15 feet. For line sets shorter than 15 feet in length, 

remove  charge.  For  line  sets  longer  than  15  feet,  add 

feet. For lines longer than 50 feet., refer to long line set 

guidelines.

Refrigeration Charge Adjustment

Liquid Line Diameter

Oz. Per Linear Foot

3/8”

0.6

Table 2. 

350-450  CFM  per  ton  (12,000  Btuh)  through  a  wet  coil. 

Refer to indoor unit instructions for methods of determining 

Cooling Cycle Charge Adjustment Procedure

Units with Indoor Pistons

Units installed with indoor pistons require charging with the 

superheat method.

within ± 20 % of its rated CFM.

1. Operate unit a minimum of 10 minutes before checking 

charge.

2. Measure  suction  pressure  by  attaching  a  gage  to 

suction valve service port. Determine saturation temp 

from T/P chart.

3. Measure suction temperature by attaching an accurate 

thermistor  type  or  electronic  thermometer  to  suction 

line at service valve.

4. Calculate  superheat  (measured  temp.  -  saturation 

temp.).

5. Measure  outdoor  air  dry-bulb  temperature  with 

thermometer.

Remove access panel to gain access to unit wiring. Extend 

wires from disconnect through power wiring hole provided 

and into unit control box. Flexible conduit is required for the 

swing out control box feature.

The unit cabinet must have an uninterrupted or unbroken 

ground.  The  ground  must  be  installed  in  accordance 

with all electrical codes. Failure to follow this warning 

 WARNING

Connect ground wire to ground connection in control box 

for safety. Connect power wiring to contactor.

High voltage power connections to 3-phase models is made 

Contol Wiring

The control voltage is 24 VAC. NEC Class I insulated 18 

AWG is required for control wiring. For lengths longer than 

150 feet, contact your local distributor for technical service.

Ensure  the  room  thermostat  is  properly  installed  per 

instructions shipped with room thermostat. Generally the 

thermostat  should  not  be  exposed  to  sunlight,  drafts  or 

vibration and should not be mounted on exterior walls.

Low voltage wiring must be separated from high voltage 

wiring.

 WARNING

Low voltage connections should be in accordance to the 

wiring diagram.

Figure 2. Typical Low Voltage Connection

Summary of Contents for Signature MAC16 A Series

Page 1: ...anual carefully before installation and keep it for future reference The Signature Series is NOT designed for amateur installation Installation SHOULD be performed by an authorized technician Please r...

Page 2: ...e performed by a licensed professional installer or equivalent service agency or the gas supplier WARNING result in hazards to you and others Installation MUST conform with local building codes and wi...

Page 3: ...th RTV or other silicon based caulk 6 Avoid direct tubing contact with water pipes duct work 7 Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct...

Page 4: ...nless it matches the one listed on the outdoor unit Refrigeration Line Sets Use only refrigeration grade copper tubes Split systems may be installed with up to 50 feet of line set no more than 20 feet...

Page 5: ...utdoor unit 3 Follow the vacuum pump manufacturer s instructions Allow the pump to operate until the system has been evacuated down to 300 microns Allow the pump to continue running for an additional...

Page 6: ...e to suction valve service port Determine saturation temp from T P chart 3 Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to suction line at service val...

Page 7: ...service valve pressure by attaching an accurate gage to service port Determine saturation temp from T P chart 3 Measure liquid line temperature by attaching an accurate thermistor type or electronic t...

Page 8: ...507043 04C Page 7 of 9 mrcool com Figure 3 A C Single Phase Wiring Diagram single speed condenser fan...

Page 9: ...Page 8 of 9 507043 04C mrcool com Figure 4 A C Single Phase Wiring Diagram multi speed condenser fan...

Page 10: ...rom the condenser coils SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODILY INJURY W...

Page 11: ...or manual are subject to change without prior notice Consult with the sales agency or manufacturer for details ELECTRICIAN and or HVAC TECHNICIAN LICENSE INSTALLATION DATE INSTALLATION LOCATION SERIAL...

Reviews: