Troubleshooting 16
22
Indoor unit A room
temperature (T1A)
If the temperature is lower than 0
o
C, the digital display shows
“0.” If the temperature is higher than 70
o
C, the digital display
shows “70.” If the indoor unit is not connected, the digital
display shows: “--”
23
Indoor unit B room
temperature (T1B)
24
Indoor unit C room
temperature (T1C)
25
Indoor unit D room
temperature (T1D)
26
Indoor unit E room
temperature (T1E)
27
Indoor unit A evaporator
temperature (T2A)
If the temperature is lower than -9
o
C, the digital display shows
“-9.” If the temperature is higher than 70
o
C, the digital display
shows “70.” If the indoor unit is not connected, the digital
display shows: “--”
28
Indoor unit B evaporator
temperature (T2B)
29
Indoor unit C evaporator
temperature (T2C)
30
Indoor unit D evaporator
temperature (T2D)
31
Indoor unit E evaporator
temperature (T2E)
32
Condenser pipe temperature
(T3)
33
Outdoor ambient temperature
(T4)
34
Compressor discharge
temperature (TP)
The display value is between 30–129
o
C. If the temperature
is lower than 30
o
C, the digital display shows “30.” If the
temperature is higher than 99
o
C, the digital display shows
single and double digits. For example, if the digital display
shows “0.5”, the compressor discharge temperature is 105
o
C.
35
AD value of current
The display value is a hex number.
For example, the digital display tube shows “Cd”, it means AD
value is 205.
36
AD value of AC voltage
37
AD value of DC voltage
38
EXV open angle for A indoor
unit
Actual data/4.
If the value is higher than 99, the digital display shows single
and double digits.
For example, if the digital display shows “2.0”, the EXV open
angle is 120×4=480p.
39
EXV open angle for B indoor
unit
40
EXV open angle for C indoor
unit
41
EXV open angle for D indoor
unit
42
EXV open angle for E indoor
unit
43
MVI valve open angle
44
EVI valve open angle
Summary of Contents for DIY-MULTI2-18HP230C
Page 1: ...4TH GENERATION MULTI ZONE SERVICE MANUAL...
Page 2: ......
Page 5: ......
Page 6: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Page 20: ...5 8...
Page 21: ......
Page 22: ......
Page 24: ...Outdoor unit printed circuit board diagram 17122000051368...
Page 27: ...Outdoor unit printed circuit board diagram 17122300001076...
Page 29: ...Outdoor unit IPM board diagram 17122000018251...
Page 31: ...Outdoor unit printed circuit board diagram 17122000037804...
Page 33: ...Outdoor unit IPM board diagram 17122000042012...
Page 42: ...Outdoor Unit Disassembly 3 2 Dimension 2 1 Panel Plate B30 1 drive 2...
Page 43: ...Outdoor Unit Disassembly 4 2 2 Panel Plate CA30 1 drive 2 1 drive 3 1 drive 4...
Page 44: ...Outdoor Unit Disassembly 5 2 3 Panel Plate CA30 1 drive 2 for US models...
Page 45: ...Outdoor Unit Disassembly 6 2 4 Panel Plate D30 1 drive 2 1 drive 3 1 drive 4 1 drive 5...
Page 46: ...Outdoor Unit Disassembly 7 2 5 Panel Plate D30 1 drive 3 1 drive 4 for US models...
Page 47: ...Outdoor Unit Disassembly 8 2 6 Panel Plate X330 1 drive 2...
Page 48: ...Outdoor Unit Disassembly 9 2 7 Panel Plate X430 1 drive 3...
Page 49: ...Outdoor Unit Disassembly 10 2 8 Panel Plate X430 1 drive 2 for US models...
Page 50: ...Outdoor Unit Disassembly 11 2 6 Panel Plate E30 1 drive 5 for US models...