7 Operation
Maschinenfabrik Reinhausen GmbH 2018
40
1800059/09 EN
RS
7.1.2 Flap valve in OFF position
Note that protective relay RS 2004 features an automatic reset mechanism
which means that the flap valve does not remain in the OFF position after
tripping. If the protective relay RS 2004 has not tripped due to an error in
the tripping circuit, also proceed as described below for RS 2004.
If the flap valve is in the OFF position, proceed as follows:
1. Ensure that the transformer is not started up under any circumstances.
2. Contact and inform Maschinenfabrik Reinhausen of the following:
ð
Serial number of protective relay and on-load tap-changer
ð
What was the load of the transformer at the instant of tripping?
ð
Was the on-load tap-changer moved immediately before or during trip-
ping?
ð
Did any other protective devices of the transformer respond at the in-
stant of tripping?
ð
Were switching operations in the network being carried out at the in-
stant of tripping?
ð
Were overvoltages registered at the instant of tripping?
3. Take further action in agreement with Maschinenfabrik Reinhausen.
7.1.3 Re-commissioning the transformer
Once the reason for the protective relay tripping has been established and
remedied, you can re-commission the transformer:
1. Check the protective relay [
2. Commission the transformer.
Summary of Contents for RS 2001
Page 1: ...Protective relay RS Operating instructions 1800059 09 EN ...
Page 50: ......
Page 51: ......