6 Electrical connection
61
BA6820378-03 EN
6.8 Connecting analog outputs
Analog 1
Analog 2
Temperature
Humidity
The analog outputs are active outputs. Observe the load resis-
tance of 0...600 Ω.
In order to connect the cable for transmitting analog signal 1 for the tempera-
ture, proceed as follows:
1. Insert the wires into terminals 10(CL+) and 11(CL-).
2. Twist the shielding (if present) and insert it into terminal 12.
3. Tighten the screw terminals.
In order to connect the cable for transmitting analog signal 2 for the humidity,
proceed as follows:
1. Insert the wires into terminals 13(CL+) and 14(CL-).
2. Twist the shielding (if present) and insert it into terminal 15.
3. Tighten the screw terminals.
Figure 41: Analog outputs 1 and 2