DCA125SSIU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (07/20/17) — PAGE 27
OUTPUT TERMINAL PANEL CONNECTIONS
3Ø-480/277V UVWO Terminal Output Voltages
1. Place the voltage selector switch in the 3Ø 480/277
position as shown in Figure 24.
Figure 24. Voltage Selector itch
3Ø-480/277V Position
2. Connect the load wires to the UVWO terminals as
shown in Figure 25.
Figure 25. UVWO Terminal Lugs 3Ø-480V
Connections
NOTICE
ALWAYS
make sure that the connections to the
UVWO and Ground terminals are
secure
and
tight
.
The possibility of arcing exists, that could cause a fire.
1Ø-240/120V UVWO Terminal Output Voltages
1. Place the voltage selector switch in the 1Ø 240/120
position as shown in Figure 26.
Figure 26. Voltage Selector itch
1Ø-240/120V Position
2. Connect the load wires to the UVWO terminals as
shown in Figure 27.
Figure 27. UVWO Terminal Lugs
1Ø-240/120V Connection
3. Turn the voltage regulator knob (Figure 22) clockwise
to increase voltage output, turn counterclockwise
to decrease voltage output. Use voltage regulator
adjustment knob whenever fine tuning of the output
voltage is required.